[Federal Register Volume 64, Number 147 (Monday, August 2, 1999)] [Notices] [Pages 41973-41975] From the Federal Register Online via the Government Publishing Office [www.gpo.gov] [FR Doc No: 99-19697] ----------------------------------------------------------------------- NUCLEAR REGULATORY COMMISSION [Docket Nos. 50-327 and 50-328] Tennessee Valley Authority; Notice of Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing The U.S. Nuclear Regulatory Commission (the Commission) is considering issuance of an amendment to Facility Operating License Nos. DPR-77 and DPR-79 issued to the Tennessee Valley Authority (TVA, the licensee) for operation of the Sequoyah Nuclear Plant (SQN), Units 1 and 2, located in Hamilton County, Tennessee. The proposed amendment would change the SQN Technical Specification (TS) requirements, Sections 3.8.2.1 and 3.8.2.2, by providing an allowance to use a fully qualified and tested spare vital bus electrical inverter in place of any of the eight normal inservice inverters. Before issuance of the proposed license amendment, the Commission will have made findings required by the Atomic Energy Act of 1954, as amended (the Act) and the Commission's regulations. The Commission has made a proposed determination that the amendment request involves no significant hazards consideration. Under the Commission's regulations in 10 CFR 50.92, this means that operation of the facility in accordance with the proposed amendment would not (1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) involve a significant reduction in a margin of safety. As required by 10 CFR 50.91(a), the licensee has provided its analysis of the issue of no significant hazards consideration, which is presented below: A. The proposed amendment does not involve a significant increase in the probability or consequences of an accident previously evaluated The proposed changes to the onsite power distribution systems of the SQN TSs will not alter the safety function of the inverters or the 120-V [volt] vital instrument power boards. While additional automatic and manual transfer capabilities have been added, the function of the inverters will remain the same and the availability of a spare inverter will provide improved capability to tolerate inverter failures and support maintenance activities. These improvements will reduce the potential for unit trips and required shutdowns as a result of inverter failures. The new design, along with the operating requirements, have been evaluated and determined to not present the potential to increase the probability of an accident. In addition, the inverters and the associated 120-V vital instrument power boards are utilized to support instrumentation that monitor critical plant parameters to aid in the detection of accidents and to support the mitigation of accidents, but are not considered to be an initiator of a design basis accident. Therefore, the probability of an accident is not increased by the proposed changes to the TSs and the potential for unit shutdowns will be minimized. The functions of the inverters remain the same based on the proposed change to the TSs. Other design changes, that are independent of the requested change, will improve the ability of the inverters to supply power for the identification and mitigation of accidents. Since the inverter functions and their operation will not be affected by the proposed TS change, the consequences of an accident will not be increased although the consequences should be further minimized as a result of the inverter design changes. B. The proposed amendment does not create the possibility of a new or different kind of accident from any accident previously evaluated. The inverters and the 120-V vital instrument power boards are not considered to be an initiator of a design basis accident. These features provide power to instrumentation that support the identification and mitigation of accidents as well as system control functions during normal plant operations. The functions of the inverters are not altered by the proposed TS change and will not create the possibility of a new or different accident. C. The proposed amendment does not involve a significant reduction in a margin of safety. The plant setpoints and limits that are utilized to ensure safe operation and detect accident conditions are not impacted by the proposed TS change. The inverters and 120-V vital instrument power boards will continue to provide reliable power to the safety-related instrumentation for the identification and mitigation of accidents and in support of plant operation. The ability to utilize spare inverters that can provide the desired level of redundancy will enhance the safety functions during periods of inverter maintenance or failure that would otherwise have to rely on a single power source without a backup source. Therefore, the margin of safety is not reduced based on the additional capability to utilize a spare inverter that enhances the level of safety without change to plant safety limits. The NRC staff has reviewed the licensee's analysis and, based on this review, it appears that the three standards of 10 CFR 50.92(c) are satisfied. Therefore, the NRC staff proposes to determine that the amendment request involves no significant hazards consideration. The Commission is seeking public comments on this proposed [[Page 41974]] determination. Any comments received within 30 days after the date of publication of this notice will be considered in making any final determination. Normally, the Commission will not issue the amendment until the expiration of the 30-day notice period. However, should circumstances change during the notice period such that failure to act in a timely way would result, for example, in derating or shutdown of the facility, the Commission may issue the license amendment before the expiration of the 30-day notice period, provided that its final determination is that the amendment involves no significant hazards consideration. The final determination will consider all public and State comments received. Should the Commission take this action, it will publish in the Federal Register a notice of issuance and provide for opportunity for a hearing after issuance. The Commission expects that the need to take this action will occur very infrequently. Written comments may be submitted by mail to the Chief, Rules and Directives Branch, Division of Administrative Services, Office of Administration, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, and should cite the publication date and page number of this Federal Register notice. Written comments may also be delivered to Room 6D59, Two White Flint North, 11545 Rockville Pike, Rockville, Maryland, from 7:30 a.m. to 4:15 p.m. Federal workdays. Copies of written comments received may be examined at the NRC Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC. The filing of requests for hearing and petitions for leave to intervene is discussed below. By September 1, 1999, the licensee may file a request for a hearing with respect to issuance of the amendment to the subject facility operating license and any person whose interest may be affected by this proceeding and who wishes to participate as a party in the proceeding must file a written request for a hearing and a petition for leave to intervene. Requests for a hearing and a petition for leave to intervene shall be filed in accordance with the Commission's ``Rules of Practice for Domestic Licensing Proceedings'' in 10 CFR Part 2. Interested persons should consult a current copy of 10 CFR 2.714 which is available at the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, and at the local public document room located at the Chattanooga-Hamilton County Library, 1001 Broad Street, Chattanooga, Tennessee 37402. If a request for a hearing or petition for leave to intervene is filed by the above date, the Commission or an Atomic Safety and Licensing Board, designated by the Commission or by the Chairman of the Atomic Safety and Licensing Board Panel, will rule on the request and/or petition; and the Secretary or the designated Atomic Safety and Licensing Board will issue a notice of hearing or an appropriate order. As required by 10 CFR 2.714, a petition for leave to intervene shall set forth with particularity the interest of the petitioner in the proceeding, and how that interest may be affected by the results of the proceeding. The petition should specifically explain the reasons why intervention should be permitted with particular reference to the following factors: (1) The nature of the petitioner's right under the Act to be made party to the proceeding; (2) the nature and extent of the petitioner's property, financial, or other interest in the proceeding; and (3) the possible effect of any order which may be entered in the proceeding on the petitioner's interest. The petition should also identify the specific aspect(s) of the subject matter of the proceeding as to which petitioner wishes to intervene. Any person who has filed a petition for leave to intervene or who has been admitted as a party may amend the petition without requesting leave of the Board up to 15 days prior to the first prehearing conference scheduled in the proceeding, but such an amended petition must satisfy the specificity requirements described above. Not later than 15 days prior to the first prehearing conference scheduled in the proceeding, a petitioner shall file a supplement to the petition to intervene which must include a list of the contentions which are sought to be litigated in the matter. Each contention must consist of a specific statement of the issue of law or fact to be raised or controverted. In addition, the petitioner shall provide a brief explanation of the bases of the contention and a concise statement of the alleged facts or expert opinion which support the contention and on which the petitioner intends to rely in proving the contention at the hearing. The petitioner must also provide references to those specific sources and documents of which the petitioner is aware and on which the petitioner intends to rely to establish those facts or expert opinion. Petitioner must provide sufficient information to show that a genuine dispute exists with the applicant on a material issue of law or fact. Contentions shall be limited to matters within the scope of the amendment under consideration. The contention must be one which, if proven, would entitle the petitioner to relief. A petitioner who fails to file such a supplement which satisfies these requirements with respect to at least one contention will not be permitted to participate as a party. Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene, and have the opportunity to participate fully in the conduct of the hearing, including the opportunity to present evidence and cross- examine witnesses. If a hearing is requested, the Commission will make a final determination on the issue of no significant hazards consideration. The final determination will serve to decide when the hearing is held. If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and make it immediately effective, notwithstanding the request for a hearing. Any hearing held would take place after issuance of the amendment. If the final determination is that the amendment request involves a significant hazards consideration, any hearing held would take place before the issuance of any amendment. A request for a hearing or a petition for leave to intervene must be filed with the Secretary of the Commission, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, Attention: Rulemakings and Adjudications Staff, or may be delivered to the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, by the above date. A copy of the petition should also be sent to the Office of the General Counsel, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, and to General Counsel, Tennessee Valley Authority, 400 West Summit Hill Drive, ET10H, Knoxville, Tennessee 37902, attorney for the licensee. Nontimely filings of petitions for leave to intervene, amended petitions, supplemental petitions and/or requests for hearing will not be entertained absent a determination by the Commission, the presiding officer or the presiding Atomic Safety and Licensing Board that the petition and/or request should be granted based upon a balancing of the factors specified in 10 CFR 2.714(a)(1)(i)-(v) and 2.714(d). For further details with respect to this action, see the application for amendment dated June 24, 1999, which [[Page 41975]] is available for public inspection at the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, and at the local public document room located at the Chattanooga-Hamilton County Library, 1001 Broad Street, Chattanooga, Tennessee 37402. Dated at Rockville, Maryland, this 26th day of July 1999. For the Nuclear Regulatory Commission. Ronald W. Hernan, Senior Project Manager, Section 2, Project Directorate II, Division of Licensing Project Management, Office of Nuclear Reactor Regulation. [FR Doc. 99-19697 Filed 7-30-99; 8:45 am] BILLING CODE 7590-01-P
Document
Tennessee Valley Authority; Notice of Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing
[Federal Register Volume 64, Number 147 (Monday, August 2, 1999)] [Notices] [Pages 41973-41975] From the Federal Register Online via the Government Publishing Office [ www.gpo.g...
Legal Citation
Federal Register Citation
Use this for formal legal and research references to the published document.
64 FR 41973
Web Citation
Suggested Web Citation
Use this when citing the archival web version of the document.
“Tennessee Valley Authority; Notice of Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing,” thefederalregister.org (August 2, 1999), https://thefederalregister.org/documents/99-19697/tennessee-valley-authority-notice-of-consideration-of-issuance-of-amendment-to-facility-operating-license-proposed-no-si.