Energy Efficiency Program for Certain Commercial and Industrial Equipment: Test Procedures and Efficiency Standards for Commercial Air Conditioners and Heat Pumps
Department of Energy Office of Energy Efficiency and Renewable Energy 10 CFR Part 431 [Docket No. EE-RM/TP-99-460] RIN 1904-AA97 Environmental Protection Agency 40 CFR Part 52 [...
On page 48837 and 48838, in §431.271, Tables 1 and 2 should read as follows:
TABLE 1.—Minimum Cooling Efficiency Levels
Product
Category
Cooling capacity
Subcategory
Efficiency Level 1
Small Commercial Packaged Air Conditioning and Heating Equipment
Air Cooled, 3 Phase
<65,000 Btu/h
Split System
Single Package
SEER = 10.0
SEER = 9.7
Air Cooled
≥65,000 Btu/h and <135,000 Btu/h
All
EER = 8.9
Water Cooled Evaporatively Cooled, and Water-Source
<65,000 Btu/h
≥65,000 Btu/h and <135,000 Btu/h
All
All
EER = 9.3
EER = 10.5
Large Commercial Packaged Air Conditioning and Heating Equipment
Air Cooled
≥135,000 Btu/h and <240,000 Btu/h
All
EER = 8.5
Water-Cooled, and Evaporatively Cooled
≥135,000 Btu/h and <240,000 Btu/h
All
EER = 9.6
Packaged Terminal Air Conditioners and Heat Pumps
All
<7,000 Btu/h
≥7,000 Btu/h and ≤15,000 Btu/h
>15,000 Btu/h
All
EER = 8.88
EER = 10.0−(0.16 × capacity [in thousands of Btu/h at 95° outdoor dry-bulb temperature])
EER = 7.6
1
All EER values must be rated at 95°F outdoor dry-bulb temperature for air-cooled products and evaporatively-cooled products and at 85°F entering water temperature for water-source and water-cooled products.
( printed page 63678)
TABLE 2.—MINIMUM HEATING EFFICIENCY LEVELS
Product
Category
Cooling capacity
Subcategory
Efficiency Level 2
Small Commercial Packaged Air Conditioning and Heating Equipment
Air Cooled, 3 Phase
<65,000 Btu/h
Split System
Single Package
HSPF = 6.8
HSPF = 6.6
Water-Source
<135,000 Btu/h
Split System and Single Package
COP = 3.8
Air Cooled
≥65,000 Btu/h and <135,000 Btu/h
All
COP = 3.0
Large Commercial Packaged Air Conditioning and Heating Equipment
Air Cooled
≥135,000 Btu/h and <240,000 Btu/h
Split System and Single Package
COP = 2.9
Packaged Terminal Heat Pumps
All
All
All
COP = 1.3+(0.16 × the applicable minimum cooling EER prescribed in Table 1—Minimum Cooling Efficiency Levels)
2
All COP values must be rated at 47°F outdoor dry-bulb temperature for air-cooled products and evaporatively-cooled products and at 70°F entering water temperature for water-source products.
Correction
In rule document 00-25599 beginning on page 60101 in the issue of Tuesday, October 10, 2000, make the following corrections:
1. On page 60102, in §52.1770 (c), in the table, in the section “Subchapter 2D—Air Pollution Control Requirements”, in the first line, the column for “State effective date” should read “1/15/98” and the column for “EPA approval date” should read “11/10/99”.
2. On page 60103, in the same section of the table, in the last line, in the column for “State effective date”, “Annual Emissions Reporting” should read “1/15/98”. The column for “EPA approval date” should read “11/10/99” and the column for “Comments” should read “*”.
Correction
In notice document 00-25579 beginning on page 59463, in the issue of Thursday, October 5, 2000, make the following correction:
On page 59463, in the third column, in the seventh line from the bottom, “ Sec. 3, SE
1/4
NW
1/2
” should read “ Sec. 3, SE
1/4
NW
1/4
”.
Use this for formal legal and research references to the published document.
65 FR 63677
Web Citation
Suggested Web Citation
Use this when citing the archival web version of the document.
“Energy Efficiency Program for Certain Commercial and Industrial Equipment: Test Procedures and Efficiency Standards for Commercial Air Conditioners and Heat Pumps,” thefederalregister.org (October 24, 2000), https://thefederalregister.org/documents/C0-19723/energy-efficiency-program-for-certain-commercial-and-industrial-equipment-test-procedures-and-efficiency-standards-for-c.