We propose to adopt a new airworthiness directive (AD) for certain Bombardier, Inc. Model BD-100-1A10 (Challenger 300) airplanes. This proposed AD was prompted by testing of the spoiler electronic control unit (SECU) software for an upgrade, which revealed a timing error between the command and monitor channels. This proposed AD would require revising the maintenance or inspection program to incorporate repetitive operational tests of the aileron disconnect system, and corrective action if necessary. This proposed AD would also require modification and reidentification of the SECU, which would terminate the repetitive operational tests. We are proposing this AD to prevent a timing error in the SECU software, which, in combination with failure of the roll disconnect switch, could result in complete loss of spoiler functionality and consequent reduced controllability of the airplane.

Federal Register, Volume 80 Issue 32 (Wednesday, February 18, 2015)
[Federal Register Volume 80, Number 32 (Wednesday, February 18, 2015)]
[Proposed Rules]
[Pages 8564-8566]
From the Federal Register Online  [www.thefederalregister.org]
[FR Doc No: 2015-02695]


=======================================================================
-----------------------------------------------------------------------

DEPARTMENT OF TRANSPORTATION

Federal Aviation Administration

14 CFR Part 39

[Docket No. FAA-2015-0088; Directorate Identifier 2014-NM-179-AD]
RIN 2120-AA64


Airworthiness Directives; Bombardier, Inc. Airplanes

AGENCY: Federal Aviation Administration (FAA), DOT.

ACTION: Notice of proposed rulemaking (NPRM).

-----------------------------------------------------------------------

SUMMARY: We propose to adopt a new airworthiness directive (AD) for 
certain Bombardier, Inc. Model BD-100-1A10 (Challenger 300) airplanes. 
This proposed AD was prompted by testing of the spoiler electronic 
control unit (SECU) software for an upgrade, which revealed a timing 
error between the command and monitor channels. This proposed AD would 
require revising the maintenance or inspection program to incorporate 
repetitive operational tests of the aileron disconnect system, and 
corrective action if necessary. This proposed AD would also require 
modification and reidentification of the SECU, which would terminate 
the repetitive operational tests. We are proposing this AD to prevent a 
timing error in the SECU software, which, in combination with failure 
of the roll disconnect switch, could result in complete loss of spoiler 
functionality and consequent reduced controllability of the airplane.

DATES: We must receive comments on this proposed AD by April 6, 2015.

ADDRESSES: You may send comments, using the procedures found in 14 CFR 
11.43 and 11.45, by any of the following methods:
     Federal eRulemaking Portal: Go to http://www.regulations.gov. Follow the instructions for submitting comments.
     Fax: 202-493-2251.
     Mail: U.S. Department of Transportation, Docket 
Operations, M-30, West Building Ground Floor, Room W12-140, 1200 New 
Jersey Avenue SE., Washington, DC 20590.
     Hand Delivery: U.S. Department of Transportation, Docket 
Operations, M-30, West Building Ground Floor, Room W12-140, 1200 New 
Jersey Avenue SE., Washington, DC, between 9 a.m. and 5 p.m., Monday 
through Friday, except Federal holidays.
    For service information identified in this proposed AD, contact 
Bombardier, Inc., 400 C[ocirc]te-Vertu Road West, Dorval, Qu[eacute]bec 
H4S 1Y9, Canada; telephone 514-855-5000; fax 514-855-7401; email 
[email protected]; Internet http://www.bombardier.com. You 
may view this referenced service information at the FAA, Transport 
Airplane Directorate, 1601 Lind Avenue SW., Renton, WA. For information 
on the availability of this material at the FAA, call 425-227-1221.

Examining the AD Docket

    You may examine the AD docket on the Internet at http://www.regulations.gov by searching for and locating Docket No. FAA-2015-
0088; or in person at the Docket Management Facility between 9 a.m. and 
5 p.m., Monday through Friday, except Federal holidays. The AD docket 
contains this proposed AD, the regulatory evaluation, any comments 
received, and other information. The street address for the Docket 
Operations office (telephone 800-647-5527) is in the ADDRESSES section. 
Comments will be available in the AD docket shortly after receipt.

FOR FURTHER INFORMATION CONTACT: Assata Dessaline, Aerospace Engineer, 
Avionics and Service Branch, ANE-172, FAA, New York Aircraft 
Certification Office, 1600 Stewart Avenue, Suite 410, Westbury, New 
York 11590; telephone 516-228-7301; fax 516-794-5531.

SUPPLEMENTARY INFORMATION:

Comments Invited

    We invite you to send any written relevant data, views, or 
arguments about this proposed AD. Send your comments to an address 
listed under the ADDRESSES section. Include ``Docket No. FAA-2015-0088; 
Directorate Identifier 2014-NM-179-AD'' at the beginning of your 
comments. We specifically invite comments on the overall regulatory, 
economic, environmental, and energy aspects of this proposed AD. We 
will consider all comments received by the closing date and may amend 
this proposed AD based on those comments.
    We will post all comments we receive, without change, to http://www.regulations.gov, including any personal information you provide. We 
will also post a report summarizing each substantive verbal contact we 
receive about this proposed AD.

Discussion

    Transport Canada Civil Aviation (TCCA), which is the aviation 
authority for Canada, has issued Canadian Airworthiness Directive CF-
2014-24, dated August 5, 2014 (referred to after this as the Mandatory 
Continuing Airworthiness Information, or ``the MCAI''), to correct an 
unsafe condition for certain Bombardier, Inc. Model BD-

[[Page 8565]]

100-1A10 (Challenger 300) airplanes. The MCAI states:

    During testing of the software for an upgrade of the spoiler 
electronic control unit (SECU), a timing error between the Command 
and Monitor channels was found in the SECU software. This timing 
error, if not corrected, in combination with the failure of the roll 
disconnect switch, may lead to a complete loss of spoiler 
functionality and result in a reduction or complete loss of 
aeroplane roll control.
    This [TCCA] AD mandates the SECU software modification to 
correct the timing error and to change the inspection interval for a 
maintenance task based on System Functional Hazard Analysis [by 
revising the inspection or maintenance program.]

    You may examine the MCAI in the AD docket on the Internet at http://www.regulations.gov by searching for and locating Docket No. FAA-2015-
0088.

Related Service Information Under 1 CFR Part 51

    Bombardier, Inc. has issued Service Bulletin 100-27-16, dated 
October 31, 2013. The service information describes procedures for 
modification and reidentification of the SECU. The actions described in 
this service information are intended to correct the unsafe condition 
identified in the MCAI. This service information is reasonably 
available; see ADDRESSES for ways to access this service information.

FAA's Determination and Requirements of This Proposed AD

    This product has been approved by the aviation authority of another 
country, and is approved for operation in the United States. Pursuant 
to our bilateral agreement with the State of Design Authority, we have 
been notified of the unsafe condition described in the MCAI and service 
information referenced above. We are proposing this AD because we 
evaluated all pertinent information and determined an unsafe condition 
exists and is likely to exist or develop on other products of the same 
type design.
    This AD requires revisions to certain operator maintenance 
documents to include new actions (e.g., inspections). Compliance with 
these actions is required by 14 CFR 91.403(c). For airplanes that have 
been previously modified, altered, or repaired in the areas addressed 
by this AD, the operator may not be able to accomplish the actions 
described in the revisions. In this situation, to comply with 14 CFR 
91.403(c), the operator must request approval for an alternative method 
of compliance according to paragraph (j)(1) of this AD. The request 
should include a description of changes to the required inspections 
that will ensure the continued operational safety of the airplane.

Costs of Compliance

    We estimate that this proposed AD affects 107 airplanes of U.S. 
registry.
    We also estimate that it would take up to 6 work-hours per product 
to comply with the basic requirements of this proposed AD. The average 
labor rate is $85 per work-hour. Based on these figures, we estimate 
the cost of this proposed AD on U.S. operators to be up to $54,570, or 
up to $510 per product.
    We have received no definitive data on the parts cost for doing the 
modification in this proposed AD.

Authority for This Rulemaking

    Title 49 of the United States Code specifies the FAA's authority to 
issue rules on aviation safety. Subtitle I, section 106, describes the 
authority of the FAA Administrator. ``Subtitle VII: Aviation 
Programs,'' describes in more detail the scope of the Agency's 
authority.
    We are issuing this rulemaking under the authority described in 
``Subtitle VII, Part A, Subpart III, Section 44701: General 
requirements.'' Under that section, Congress charges the FAA with 
promoting safe flight of civil aircraft in air commerce by prescribing 
regulations for practices, methods, and procedures the Administrator 
finds necessary for safety in air commerce. This regulation is within 
the scope of that authority because it addresses an unsafe condition 
that is likely to exist or develop on products identified in this 
rulemaking action.

Regulatory Findings

    We determined that this proposed AD would not have federalism 
implications under Executive Order 13132. This proposed AD would not 
have a substantial direct effect on the States, on the relationship 
between the national Government and the States, or on the distribution 
of power and responsibilities among the various levels of government.
    For the reasons discussed above, I certify this proposed 
regulation:
    1. Is not a ``significant regulatory action'' under Executive Order 
12866;
    2. Is not a ``significant rule'' under the DOT Regulatory Policies 
and Procedures (44 FR 11034, February 26, 1979);
    3. Will not affect intrastate aviation in Alaska; and
    4. Will not have a significant economic impact, positive or 
negative, on a substantial number of small entities under the criteria 
of the Regulatory Flexibility Act.

List of Subjects in 14 CFR Part 39

    Air transportation, Aircraft, Aviation safety, Incorporation by 
reference, Safety.

The Proposed Amendment

    Accordingly, under the authority delegated to me by the 
Administrator, the FAA proposes to amend 14 CFR part 39 as follows:

PART 39--AIRWORTHINESS DIRECTIVES

0
1. The authority citation for part 39 continues to read as follows:

    Authority: 49 U.S.C. 106(g), 40113, 44701.


Sec.  39.13  [Amended]

0
2. The FAA amends Sec.  39.13 by adding the following new airworthiness 
directive (AD):

Bombardier, Inc.: Docket No. FAA-2015-0088; Directorate Identifier 
2014-NM-179-AD.

(a) Comments Due Date

    We must receive comments by April 6, 2015.

(b) Affected ADs

    None.

(c) Applicability

    This AD applies to Bombardier, Inc. Model BD-100-1A10 
(Challenger 300) airplanes, equipped with a spoiler electronic 
control unit (SECU) having part number (P/N) C47330-006, C47330-007, 
or C47330-008; certificated in any category.

(d) Subject

    Air Transport Association (ATA) of America Code 27, Flight 
Controls.

(e) Reason

    This AD was prompted by testing of the spoiler electronic 
control unit (SECU) software, which revealed a timing error between 
the command and monitor channels in the software. We are issuing 
this AD to prevent a timing error in the SECU software, which, in 
combination with failure of the roll disconnect switch, could result 
in complete loss of spoiler functionality and consequent reduced 
controllability of the airplane.

(f) Compliance

    Comply with this AD within the compliance times specified, 
unless already done.

(g) Revise the Maintenance or Inspection Program

    Within 600 flight hours since the most recent operational test 
of the aileron disconnect system for spoiler functionality as of the 
effective date of this AD, or within 400 flight hours after the 
effective date of this AD, whichever occurs first: Revise the 
maintenance or inspection program, as applicable, to incorporate 
repetitive operational tests of the aileron disconnect system for 
spoiler functionality, and all

[[Page 8566]]

applicable corrective actions, using a method approved by the 
Manager, New York ACO, ANE-170, FAA.
    Note 1 to paragraph (g) of this AD: Guidance on operational 
tests of the aileron disconnect system can be found in the BD-100-
1A10 Time Limits/Maintenance Checks (TLMC) Manual.

(h) Modification of the SECU

    Within 1,600 flight hours or 48 months after the effective date 
of this AD, whichever occurs first: Modify and re-identify the SECU, 
in accordance with the Accomplishment Instructions of Bombardier 
Service Bulletin 100-27-16, dated October 31, 2013. Doing the 
actions required by this paragraph terminates the actions required 
by paragraph (g) of this AD.

(i) Parts Installation Prohibition

    As of the effective date of this AD, no person may install an 
SECU, P/N C47330-006, C47330-007, or C47330-008, on any airplane.

(j) Other FAA AD Provisions

    The following provisions also apply to this AD:
    (1) Alternative Methods of Compliance (AMOCs): The Manager, New 
York Aircraft Certification Office (ACO), ANE-170, FAA, has the 
authority to approve AMOCs for this AD, if requested using the 
procedures found in 14 CFR 39.19. In accordance with 14 CFR 39.19, 
send your request to your principal inspector or local Flight 
Standards District Office, as appropriate. If sending information 
directly to the ACO, send it to ATTN: Program Manager, Continuing 
Operational Safety, FAA, New York ACO, 1600 Stewart Avenue, Suite 
410, Westbury, NY 11590; telephone 516-228-7300; fax 516-794-5531. 
Before using any approved AMOC, notify your appropriate principal 
inspector, or lacking a principal inspector, the manager of the 
local flight standards district office/certificate holding district 
office. The AMOC approval letter must specifically reference this 
AD.
    (2) Contacting the Manufacturer: For any requirement in this AD 
to obtain corrective actions from a manufacturer, the action must be 
accomplished using a method approved by the Manager, New York ACO, 
ANE-170, FAA; or TCCA; or Bombardier, Inc.'s TCCA DAO. If approved 
by the DAO, the approval must include the DAO-authorized signature.

(k) Related Information

    (1) Refer to Mandatory Continuing Airworthiness Information 
(MCAI) Canadian Airworthiness Directive CF-2014-24, dated August 5, 
2014, for related information. This MCAI may be found in the AD 
docket on the Internet at http://www.regulations.gov by searching 
for and locating Docket No. FAA-FAA-2015-0088.
    (2) For service information identified in this AD, contact 
Bombardier, Inc., 400 C[ocirc]te-Vertu Road West, Dorval, 
Qu[eacute]bec H4S 1Y9, Canada; telephone 514-855-5000; fax 514-855-
7401; email [email protected]; Internet http://www.bombardier.com. You may view this service information at the 
FAA, Transport Airplane Directorate, 1601 Lind Avenue SW., Renton, 
WA. For information on the availability of this material at the FAA, 
call 425-227-1221.

    Issued in Renton, Washington, on February 2, 2015.
Dionne Palermo,
Acting Manager, Transport Airplane Directorate, Aircraft Certification 
Service.
[FR Doc. 2015-02695 Filed 2-17-15; 8:45 am]
BILLING CODE 4910-13-P



                                                    8564                Federal Register / Vol. 80, No. 32 / Wednesday, February 18, 2015 / Proposed Rules

                                                    aguacatae, C. perseae, Copturus                         DEPARTMENT OF TRANSPORTATION                          514–855–5000; fax 514–855–7401; email
                                                    aguacatae, or Stenoma catenifer’’ and                                                                         thd.crj@aero.bombardier.com; Internet
                                                    adding the words ‘‘listed in the                        Federal Aviation Administration                       http://www.bombardier.com. You may
                                                    operational workplan’’ in their place.                                                                        view this referenced service information
                                                    ■ l. In paragraph (f), by removing the
                                                                                                            14 CFR Part 39                                        at the FAA, Transport Airplane
                                                    word ‘‘will’’ and adding the word                       [Docket No. FAA–2015–0088; Directorate                Directorate, 1601 Lind Avenue SW.,
                                                    ‘‘may’’ in its place.                                   Identifier 2014–NM–179–AD]                            Renton, WA. For information on the
                                                                                                                                                                  availability of this material at the FAA,
                                                      The revisions and additions read as                   RIN 2120–AA64                                         call 425–227–1221.
                                                    follows:
                                                                                                            Airworthiness Directives; Bombardier,                 Examining the AD Docket
                                                    § 319.56–30      Hass avocados from Mexico.             Inc. Airplanes                                           You may examine the AD docket on
                                                    *      *     *     *      *                                                                                   the Internet at http://
                                                                                                            AGENCY: Federal Aviation
                                                       (c) Safeguards in Mexico. The                        Administration (FAA), DOT.                            www.regulations.gov by searching for
                                                    avocados must have been grown in an                                                                           and locating Docket No. FAA–2015–
                                                                                                            ACTION: Notice of proposed rulemaking
                                                    orchard located in a municipality that                                                                        0088; or in person at the Docket
                                                                                                            (NPRM).                                               Management Facility between 9 a.m.
                                                    meets the requirements of paragraph
                                                    (c)(1) of this section. The orchard in                  SUMMARY:   We propose to adopt a new                  and 5 p.m., Monday through Friday,
                                                    which the avocados are grown must                       airworthiness directive (AD) for certain              except Federal holidays. The AD docket
                                                    meet the requirements of paragraph                      Bombardier, Inc. Model BD–100–1A10                    contains this proposed AD, the
                                                    (c)(2) of this section. The avocados must               (Challenger 300) airplanes. This                      regulatory evaluation, any comments
                                                    be packed for export to the United                      proposed AD was prompted by testing                   received, and other information. The
                                                    States in a packinghouse that meets the                 of the spoiler electronic control unit                street address for the Docket Operations
                                                    requirements of paragraph (c)(3) of this                (SECU) software for an upgrade, which                 office (telephone 800–647–5527) is in
                                                    section. The Mexican national plant                     revealed a timing error between the                   the ADDRESSES section. Comments will
                                                    protection organization (NPPO) must                     command and monitor channels. This                    be available in the AD docket shortly
                                                    provide an annual operational workplan                  proposed AD would require revising the                after receipt.
                                                    to APHIS that details the activities that               maintenance or inspection program to                  FOR FURTHER INFORMATION CONTACT:
                                                    the Mexican NPPO will, subject to                       incorporate repetitive operational tests              Assata Dessaline, Aerospace Engineer,
                                                    APHIS’ approval of the workplan, carry                  of the aileron disconnect system, and                 Avionics and Service Branch, ANE–172,
                                                    out to meet the requirements of this                    corrective action if necessary. This                  FAA, New York Aircraft Certification
                                                    section; APHIS will be directly involved                proposed AD would also require                        Office, 1600 Stewart Avenue, Suite 410,
                                                    with the Mexican NPPO in the                            modification and reidentification of the              Westbury, New York 11590; telephone
                                                    monitoring and supervision of those                     SECU, which would terminate the                       516–228–7301; fax 516–794–5531.
                                                    activities. The personnel conducting the                repetitive operational tests. We are                  SUPPLEMENTARY INFORMATION:
                                                    trapping and pest surveys must be                       proposing this AD to prevent a timing                 Comments Invited
                                                    hired, trained, and supervised by the                   error in the SECU software, which, in
                                                    Mexican NPPO or by the State delegate                   combination with failure of the roll                    We invite you to send any written
                                                    of the Mexican NPPO.                                    disconnect switch, could result in                    relevant data, views, or arguments about
                                                                                                            complete loss of spoiler functionality                this proposed AD. Send your comments
                                                    *      *     *     *      *                                                                                   to an address listed under the
                                                                                                            and consequent reduced controllability
                                                       (3) * * *                                            of the airplane.                                      ADDRESSES section. Include ‘‘Docket No.
                                                       (vii) The avocados must be packed in                                                                       FAA–2015–0088; Directorate Identifier
                                                                                                            DATES: We must receive comments on                    2014–NM–179–AD’’ at the beginning of
                                                    clean, new boxes or bulk shipping bins,                 this proposed AD by April 6, 2015.
                                                    or in clean plastic reusable crates. The                                                                      your comments. We specifically invite
                                                                                                            ADDRESSES: You may send comments,                     comments on the overall regulatory,
                                                    boxes, bins, or crates must be clearly
                                                                                                            using the procedures found in 14 CFR                  economic, environmental, and energy
                                                    marked with the identity of the grower,
                                                                                                            11.43 and 11.45, by any of the following              aspects of this proposed AD. We will
                                                    packinghouse, and exporter.
                                                                                                            methods:                                              consider all comments received by the
                                                       (viii) * * * If, at the port of export for             • Federal eRulemaking Portal: Go to                 closing date and may amend this
                                                    consignments shipped by air or sea, the                 http://www.regulations.gov. Follow the                proposed AD based on those comments.
                                                    packed avocados are transferred into a                  instructions for submitting comments.                   We will post all comments we
                                                    non-refrigerated container, the boxes,                    • Fax: 202–493–2251.                                receive, without change, to http://
                                                    bins, or crates must be covered with a                    • Mail: U.S. Department of                          www.regulations.gov, including any
                                                    lid, insect-proof mesh, or other material               Transportation, Docket Operations, M–                 personal information you provide. We
                                                    to protect the avocados from fruit-fly                  30, West Building Ground Floor, Room                  will also post a report summarizing each
                                                    infestation prior to leaving the                        W12–140, 1200 New Jersey Avenue SE.,                  substantive verbal contact we receive
                                                    packinghouse. Those safeguards must be                  Washington, DC 20590.                                 about this proposed AD.
                                                    intact at the time the consignment                        • Hand Delivery: U.S. Department of
                                                    arrives in the United States.                           Transportation, Docket Operations, M–                 Discussion
                                                                                                            30, West Building Ground Floor, Room                    Transport Canada Civil Aviation
mstockstill on DSK4VPTVN1PROD with PROPOSALS




                                                    *      *     *     *      *
                                                                                                            W12–140, 1200 New Jersey Avenue SE.,                  (TCCA), which is the aviation authority
                                                      Done in Washington, DC, this 11th day of
                                                                                                            Washington, DC, between 9 a.m. and 5                  for Canada, has issued Canadian
                                                    February 2015.
                                                                                                            p.m., Monday through Friday, except                   Airworthiness Directive CF–2014–24,
                                                    Kevin Shea,                                             Federal holidays.                                     dated August 5, 2014 (referred to after
                                                    Administrator, Animal and Plant Health                    For service information identified in               this as the Mandatory Continuing
                                                    Inspection Service.                                     this proposed AD, contact Bombardier,                 Airworthiness Information, or ‘‘the
                                                    [FR Doc. 2015–03289 Filed 2–17–15; 8:45 am]             Inc., 400 Côte-Vertu Road West, Dorval,              MCAI’’), to correct an unsafe condition
                                                    BILLING CODE 3410–34–P                                  Québec H4S 1Y9, Canada; telephone                    for certain Bombardier, Inc. Model BD–


                                               VerDate Sep<11>2014   17:51 Feb 17, 2015   Jkt 235001   PO 00000   Frm 00004   Fmt 4702   Sfmt 4702   E:\FR\FM\18FEP1.SGM   18FEP1


                                                                        Federal Register / Vol. 80, No. 32 / Wednesday, February 18, 2015 / Proposed Rules                                                 8565

                                                    100–1A10 (Challenger 300) airplanes.                    inspections that will ensure the                      List of Subjects in 14 CFR Part 39
                                                    The MCAI states:                                        continued operational safety of the                     Air transportation, Aircraft, Aviation
                                                      During testing of the software for an                 airplane.                                             safety, Incorporation by reference,
                                                    upgrade of the spoiler electronic control unit          Costs of Compliance                                   Safety.
                                                    (SECU), a timing error between the Command
                                                    and Monitor channels was found in the                      We estimate that this proposed AD                  The Proposed Amendment
                                                    SECU software. This timing error, if not                affects 107 airplanes of U.S. registry.                 Accordingly, under the authority
                                                    corrected, in combination with the failure of              We also estimate that it would take up
                                                    the roll disconnect switch, may lead to a
                                                                                                                                                                  delegated to me by the Administrator,
                                                                                                            to 6 work-hours per product to comply                 the FAA proposes to amend 14 CFR part
                                                    complete loss of spoiler functionality and              with the basic requirements of this
                                                    result in a reduction or complete loss of                                                                     39 as follows:
                                                    aeroplane roll control.                                 proposed AD. The average labor rate is
                                                      This [TCCA] AD mandates the SECU                      $85 per work-hour. Based on these                     PART 39—AIRWORTHINESS
                                                    software modification to correct the timing             figures, we estimate the cost of this                 DIRECTIVES
                                                    error and to change the inspection interval             proposed AD on U.S. operators to be up
                                                    for a maintenance task based on System                  to $54,570, or up to $510 per product.                ■ 1. The authority citation for part 39
                                                    Functional Hazard Analysis [by revising the                We have received no definitive data                continues to read as follows:
                                                    inspection or maintenance program.]                     on the parts cost for doing the                           Authority: 49 U.S.C. 106(g), 40113, 44701.
                                                      You may examine the MCAI in the                       modification in this proposed AD.
                                                    AD docket on the Internet at http://                                                                          § 39.13    [Amended]
                                                                                                            Authority for This Rulemaking
                                                    www.regulations.gov by searching for                                                                          ■ 2. The FAA amends § 39.13 by adding
                                                    and locating Docket No. FAA–2015–                          Title 49 of the United States Code                 the following new airworthiness
                                                    0088.                                                   specifies the FAA’s authority to issue                directive (AD):
                                                                                                            rules on aviation safety. Subtitle I,                 Bombardier, Inc.: Docket No. FAA–2015–
                                                    Related Service Information Under 1                     section 106, describes the authority of
                                                    CFR Part 51                                                                                                      0088; Directorate Identifier 2014–NM–
                                                                                                            the FAA Administrator. ‘‘Subtitle VII:                   179–AD.
                                                      Bombardier, Inc. has issued Service                   Aviation Programs,’’ describes in more
                                                    Bulletin 100–27–16, dated October 31,                   detail the scope of the Agency’s                      (a) Comments Due Date
                                                    2013. The service information describes                 authority.                                              We must receive comments by April 6,
                                                    procedures for modification and                            We are issuing this rulemaking under               2015.
                                                    reidentification of the SECU. The                       the authority described in ‘‘Subtitle VII,            (b) Affected ADs
                                                    actions described in this service                       Part A, Subpart III, Section 44701:                     None.
                                                    information are intended to correct the                 General requirements.’’ Under that
                                                    unsafe condition identified in the                      section, Congress charges the FAA with                (c) Applicability
                                                    MCAI. This service information is                       promoting safe flight of civil aircraft in               This AD applies to Bombardier, Inc. Model
                                                    reasonably available; see ADDRESSES for                 air commerce by prescribing regulations               BD–100–1A10 (Challenger 300) airplanes,
                                                    ways to access this service information.                for practices, methods, and procedures                equipped with a spoiler electronic control
                                                                                                            the Administrator finds necessary for                 unit (SECU) having part number (P/N)
                                                    FAA’s Determination and Requirements                                                                          C47330–006, C47330–007, or C47330–008;
                                                    of This Proposed AD                                     safety in air commerce. This regulation
                                                                                                                                                                  certificated in any category.
                                                                                                            is within the scope of that authority
                                                      This product has been approved by                     because it addresses an unsafe condition              (d) Subject
                                                    the aviation authority of another                       that is likely to exist or develop on                   Air Transport Association (ATA) of
                                                    country, and is approved for operation                  products identified in this rulemaking                America Code 27, Flight Controls.
                                                    in the United States. Pursuant to our                   action.
                                                    bilateral agreement with the State of                                                                         (e) Reason
                                                    Design Authority, we have been notified                 Regulatory Findings                                      This AD was prompted by testing of the
                                                    of the unsafe condition described in the                  We determined that this proposed AD                 spoiler electronic control unit (SECU)
                                                    MCAI and service information                                                                                  software, which revealed a timing error
                                                                                                            would not have federalism implications                between the command and monitor channels
                                                    referenced above. We are proposing this                 under Executive Order 13132. This                     in the software. We are issuing this AD to
                                                    AD because we evaluated all pertinent                   proposed AD would not have a                          prevent a timing error in the SECU software,
                                                    information and determined an unsafe                    substantial direct effect on the States, on           which, in combination with failure of the roll
                                                    condition exists and is likely to exist or              the relationship between the national                 disconnect switch, could result in complete
                                                    develop on other products of the same                   Government and the States, or on the                  loss of spoiler functionality and consequent
                                                    type design.                                            distribution of power and                             reduced controllability of the airplane.
                                                      This AD requires revisions to certain                 responsibilities among the various                    (f) Compliance
                                                    operator maintenance documents to                       levels of government.
                                                    include new actions (e.g., inspections).                                                                         Comply with this AD within the
                                                                                                              For the reasons discussed above, I                  compliance times specified, unless already
                                                    Compliance with these actions is                        certify this proposed regulation:                     done.
                                                    required by 14 CFR 91.403(c). For                         1. Is not a ‘‘significant regulatory
                                                    airplanes that have been previously                     action’’ under Executive Order 12866;                 (g) Revise the Maintenance or Inspection
                                                    modified, altered, or repaired in the                     2. Is not a ‘‘significant rule’’ under the          Program
                                                    areas addressed by this AD, the operator                DOT Regulatory Policies and Procedures                   Within 600 flight hours since the most
mstockstill on DSK4VPTVN1PROD with PROPOSALS




                                                    may not be able to accomplish the                       (44 FR 11034, February 26, 1979);                     recent operational test of the aileron
                                                    actions described in the revisions. In                    3. Will not affect intrastate aviation in           disconnect system for spoiler functionality as
                                                    this situation, to comply with 14 CFR                                                                         of the effective date of this AD, or within 400
                                                                                                            Alaska; and
                                                                                                                                                                  flight hours after the effective date of this AD,
                                                    91.403(c), the operator must request                      4. Will not have a significant                      whichever occurs first: Revise the
                                                    approval for an alternative method of                   economic impact, positive or negative,                maintenance or inspection program, as
                                                    compliance according to paragraph (j)(1)                on a substantial number of small entities             applicable, to incorporate repetitive
                                                    of this AD. The request should include                  under the criteria of the Regulatory                  operational tests of the aileron disconnect
                                                    a description of changes to the required                Flexibility Act.                                      system for spoiler functionality, and all



                                               VerDate Sep<11>2014   17:51 Feb 17, 2015   Jkt 235001   PO 00000   Frm 00005   Fmt 4702   Sfmt 4702   E:\FR\FM\18FEP1.SGM    18FEP1


                                                    8566                Federal Register / Vol. 80, No. 32 / Wednesday, February 18, 2015 / Proposed Rules

                                                    applicable corrective actions, using a method           Renton, WA. For information on the                    30, West Building Ground Floor, Room
                                                    approved by the Manager, New York ACO,                  availability of this material at the FAA, call        W12–140, 1200 New Jersey Avenue SE.,
                                                    ANE–170, FAA.                                           425–227–1221.                                         Washington, DC, between 9 a.m. and 5
                                                      Note 1 to paragraph (g) of this AD:                      Issued in Renton, Washington, on February          p.m., Monday through Friday, except
                                                    Guidance on operational tests of the aileron            2, 2015.
                                                    disconnect system can be found in the BD–                                                                     Federal holidays.
                                                    100–1A10 Time Limits/Maintenance Checks                 Dionne Palermo,                                         For service information identified in
                                                    (TLMC) Manual.                                          Acting Manager, Transport Airplane                    this proposed AD, contact Airbus SAS,
                                                                                                            Directorate, Aircraft Certification Service.          Airworthiness Office—EAW, 1 Rond
                                                    (h) Modification of the SECU
                                                                                                            [FR Doc. 2015–02695 Filed 2–17–15; 8:45 am]           Point Maurice Bellonte, 31707 Blagnac
                                                       Within 1,600 flight hours or 48 months               BILLING CODE 4910–13–P                                Cedex, France; telephone +33 5 61 93 36
                                                    after the effective date of this AD, whichever
                                                                                                                                                                  96; fax +33 5 61 93 44 51; email
                                                    occurs first: Modify and re-identify the
                                                    SECU, in accordance with the                                                                                  account.airworth-eas@airbus.com;
                                                    Accomplishment Instructions of Bombardier
                                                                                                            DEPARTMENT OF TRANSPORTATION                          Internet http://www.airbus.com. You
                                                    Service Bulletin 100–27–16, dated October                                                                     may view this referenced service
                                                    31, 2013. Doing the actions required by this
                                                                                                            Federal Aviation Administration                       information at the FAA, Transport
                                                    paragraph terminates the actions required by                                                                  Airplane Directorate, 1601 Lind Avenue
                                                    paragraph (g) of this AD.                               14 CFR Part 39                                        SW., Renton, WA. For information on
                                                    (i) Parts Installation Prohibition                      [Docket No. FAA–2015–0242; Directorate                the availability of this material at the
                                                       As of the effective date of this AD, no
                                                                                                            Identifier 2014–NM–100–AD]                            FAA, call 425–227–1221.
                                                    person may install an SECU, P/N C47330–                 RIN 2120–AA64                                         Examining the AD Docket
                                                    006, C47330–007, or C47330–008, on any
                                                    airplane.                                               Airworthiness Directives; Airbus                         You may examine the AD docket on
                                                                                                            Airplanes                                             the Internet at http://
                                                    (j) Other FAA AD Provisions
                                                                                                                                                                  www.regulations.gov by searching for
                                                       The following provisions also apply to this          AGENCY: Federal Aviation                              and locating Docket No. FAA–2015–
                                                    AD:                                                     Administration (FAA), DOT.                            0242; or in person at the Docket
                                                       (1) Alternative Methods of Compliance                ACTION: Notice of proposed rulemaking
                                                    (AMOCs): The Manager, New York Aircraft
                                                                                                                                                                  Management Facility between 9 a.m.
                                                    Certification Office (ACO), ANE–170, FAA,
                                                                                                            (NPRM).                                               and 5 p.m., Monday through Friday,
                                                    has the authority to approve AMOCs for this                                                                   except Federal holidays. The AD docket
                                                                                                            SUMMARY:   We propose to adopt a new
                                                    AD, if requested using the procedures found                                                                   contains this proposed AD, the
                                                                                                            airworthiness directive (AD) for all
                                                    in 14 CFR 39.19. In accordance with 14 CFR                                                                    regulatory evaluation, any comments
                                                    39.19, send your request to your principal              Airbus Model A300 B4–603, B4–605R,
                                                                                                                                                                  received, and other information. The
                                                    inspector or local Flight Standards District            B4–620, B4–622, B4–622R airplanes; all
                                                                                                                                                                  street address for the Docket Operations
                                                    Office, as appropriate. If sending information          Airbus Model A300 C4–605R Variant F
                                                                                                                                                                  office (telephone 800–647–5527) is in
                                                    directly to the ACO, send it to ATTN:                   airplanes; and certain Airbus Model
                                                    Program Manager, Continuing Operational                 A300 F4–605R airplanes. This proposed                 the ADDRESSES section. Comments will
                                                    Safety, FAA, New York ACO, 1600 Stewart                 AD was prompted by the manufacturer’s                 be available in the AD docket shortly
                                                    Avenue, Suite 410, Westbury, NY 11590;                  review of all repairs accomplished using              after receipt.
                                                    telephone 516–228–7300; fax 516–794–5531.               the structural repair manual. This                    FOR FURTHER INFORMATION CONTACT: Dan
                                                    Before using any approved AMOC, notify                                                                        Rodina, Aerospace Engineer,
                                                                                                            review was done using revised fatigue
                                                    your appropriate principal inspector, or                                                                      International Branch, ANM–116,
                                                    lacking a principal inspector, the manager of           and damage tolerance calculations. This
                                                                                                            proposed AD would require an                          Transport Airplane Directorate, FAA,
                                                    the local flight standards district office/
                                                    certificate holding district office. The AMOC           inspection of the surrounding panels of               1601 Lind Avenue SW., Renton, WA
                                                    approval letter must specifically reference             the left and right forward passenger                  98057–3356; telephone 425–227–2125;
                                                    this AD.                                                doors, and corrective actions if                      fax 425–227–1149.
                                                       (2) Contacting the Manufacturer: For any             necessary. We are proposing this AD to                SUPPLEMENTARY INFORMATION:
                                                    requirement in this AD to obtain corrective             detect and correct previous incomplete
                                                    actions from a manufacturer, the action must                                                                  Comments Invited
                                                                                                            or inadequate repairs to the surrounding
                                                    be accomplished using a method approved
                                                                                                            panels of the left and right forward                    We invite you to send any written
                                                    by the Manager, New York ACO, ANE–170,
                                                    FAA; or TCCA; or Bombardier, Inc.’s TCCA                passenger doors and the fail-safe ring,               relevant data, views, or arguments about
                                                    DAO. If approved by the DAO, the approval               which could negatively affect the                     this proposed AD. Send your comments
                                                    must include the DAO-authorized signature.              structural integrity of the airplane.                 to an address listed under the
                                                                                                            DATES: We must receive comments on                    ADDRESSES section. Include ‘‘Docket No.
                                                    (k) Related Information
                                                                                                            this proposed AD by April 6, 2015.                    FAA–2015–0242; Directorate Identifier
                                                      (1) Refer to Mandatory Continuing                                                                           2014–NM–100–AD’’ at the beginning of
                                                    Airworthiness Information (MCAI) Canadian               ADDRESSES: You may send comments,
                                                                                                            using the procedures found in 14 CFR                  your comments. We specifically invite
                                                    Airworthiness Directive CF–2014–24, dated
                                                    August 5, 2014, for related information. This           11.43 and 11.45, by any of the following              comments on the overall regulatory,
                                                    MCAI may be found in the AD docket on the               methods:                                              economic, environmental, and energy
                                                    Internet at http://www.regulations.gov by                  • Federal eRulemaking Portal: Go to                aspects of this proposed AD. We will
                                                    searching for and locating Docket No. FAA–              http://www.regulations.gov. Follow the                consider all comments received by the
                                                    FAA–2015–0088.                                                                                                closing date and may amend this
mstockstill on DSK4VPTVN1PROD with PROPOSALS




                                                                                                            instructions for submitting comments.
                                                      (2) For service information identified in                • Fax: 202–493–2251.                               proposed AD based on those comments.
                                                    this AD, contact Bombardier, Inc., 400 Côte-              • Mail: U.S. Department of                           We will post all comments we
                                                    Vertu Road West, Dorval, Québec H4S 1Y9,                                                                     receive, without change, to http://
                                                    Canada; telephone 514–855–5000; fax 514–
                                                                                                            Transportation, Docket Operations, M–
                                                    855–7401; email thd.crj@                                30, West Building Ground Floor, Room                  www.regulations.gov, including any
                                                    aero.bombardier.com; Internet http://                   W12–140, 1200 New Jersey Avenue SE.,                  personal information you provide. We
                                                    www.bombardier.com. You may view this                   Washington, DC 20590.                                 will also post a report summarizing each
                                                    service information at the FAA, Transport                  • Hand Delivery: U.S. Department of                substantive verbal contact we receive
                                                    Airplane Directorate, 1601 Lind Avenue SW.,             Transportation, Docket Operations, M–                 about this proposed AD.


                                               VerDate Sep<11>2014   17:51 Feb 17, 2015   Jkt 235001   PO 00000   Frm 00006   Fmt 4702   Sfmt 4702   E:\FR\FM\18FEP1.SGM   18FEP1



Document Created: 2018-02-16 11:10:18
Document Modified: 2018-02-16 11:10:18
CategoryRegulatory Information
CollectionFederal Register
sudoc ClassAE 2.7:
GS 4.107:
AE 2.106:
PublisherOffice of the Federal Register, National Archives and Records Administration
SectionProposed Rules
ActionNotice of proposed rulemaking (NPRM).
DatesWe must receive comments on this proposed AD by April 6, 2015.
ContactAssata Dessaline, Aerospace Engineer, Avionics and Service Branch, ANE-172, FAA, New York Aircraft Certification Office, 1600 Stewart Avenue, Suite 410, Westbury, New York 11590; telephone 516-228-7301; fax 516-794-5531.
FR Citation80 FR 8564 
RIN Number2120-AA64
CFR AssociatedAir Transportation; Aircraft; Aviation Safety; Incorporation by Reference and Safety

2025 Federal Register | Disclaimer | Privacy Policy
USC | CFR | eCFR