82_FR_34568 82 FR 34427 - Energy Conservation Program for Certain Commercial and Industrial Equipment: Test Procedure for Certain Categories of Commercial Air Conditioning and Heating Equipment

82 FR 34427 - Energy Conservation Program for Certain Commercial and Industrial Equipment: Test Procedure for Certain Categories of Commercial Air Conditioning and Heating Equipment

DEPARTMENT OF ENERGY

Federal Register Volume 82, Issue 141 (July 25, 2017)

Page Range34427-34449
FR Document2017-15580

In response to statutory requirements to review its test procedures in response to any updates of the relevant industry test procedures, as referenced in the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard 90.1 (ASHRAE Standard 90.1), the U.S. Department of Energy (DOE) is initiating a data collection process to consider amendments to DOE's test procedures for commercial package air conditioning and heating equipment with test procedure updates included in ASHRAE Standard 90.1- 2016--specifically, those evaporatively-cooled commercial unitary air conditioners (ECUACs), water-cooled commercial unitary air conditioners (WCUACs), and air-cooled commercial unitary air conditioners (ACUACs) which have a rated cooling capacity greater than or equal to 65,000 Btu/h and less than 760,000 Btu/h; and all classes of computer room air conditioners (CRACs); as well as to consider adopting a new test procedure for dedicated outdoor air systems (DOASes), equipment covered by ASHRAE Standard 90.1 for the first time. In response to other statutory requirements for DOE to review its test procedures at least once every seven years, DOE is also reviewing its test procedures for ECUACs and WCUACs with a rated cooling capacity less than 65,000 Btu/h, as well as all classes of variable refrigerant flow multi-split air conditioners and heat pumps (VRF multi-split systems) but excluding single-phase systems with a rated cooling capacity less than 65,000 Btu/h, which are covered as consumer products. To inform interested parties and to facilitate this process, DOE has gathered data and has identified several issues that might warrant modifications to the currently applicable Federal test procedures, topics on which DOE is particularly interested in receiving comment. In overview, the issues outlined in this document mainly concern incorporation by reference of the most recent version of the relevant industry standard(s); efficiency metrics and calculations; clarification of test methods; and any additional topics that may inform DOE's decisions in a future test procedure rulemaking, including methods to reduce regulatory burden while ensuring the procedures' accuracy. These topics (and others identified by commenters) are ones which may be addressed in proposed test procedure amendments in a subsequent notice of proposed rulemaking (NOPR). DOE welcomes written comments and data from the public on any subject related to the test procedures for this equipment, including topics not specifically raised in this RFI.

Federal Register, Volume 82 Issue 141 (Tuesday, July 25, 2017)
[Federal Register Volume 82, Number 141 (Tuesday, July 25, 2017)]
[Proposed Rules]
[Pages 34427-34449]
From the Federal Register Online  [www.thefederalregister.org]
[FR Doc No: 2017-15580]


========================================================================
Proposed Rules
                                                Federal Register
________________________________________________________________________

This section of the FEDERAL REGISTER contains notices to the public of 
the proposed issuance of rules and regulations. The purpose of these 
notices is to give interested persons an opportunity to participate in 
the rule making prior to the adoption of the final rules.

========================================================================


Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / 
Proposed Rules

[[Page 34427]]



DEPARTMENT OF ENERGY

10 CFR Parts 429 and 431

[EERE-2017-BT-TP-0018]
RIN 1904-AD93


Energy Conservation Program for Certain Commercial and Industrial 
Equipment: Test Procedure for Certain Categories of Commercial Air 
Conditioning and Heating Equipment

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy (DOE).

ACTION: Request for information (RFI).

-----------------------------------------------------------------------

SUMMARY: In response to statutory requirements to review its test 
procedures in response to any updates of the relevant industry test 
procedures, as referenced in the American Society of Heating, 
Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard 90.1 
(ASHRAE Standard 90.1), the U.S. Department of Energy (DOE) is 
initiating a data collection process to consider amendments to DOE's 
test procedures for commercial package air conditioning and heating 
equipment with test procedure updates included in ASHRAE Standard 90.1-
2016--specifically, those evaporatively-cooled commercial unitary air 
conditioners (ECUACs), water-cooled commercial unitary air conditioners 
(WCUACs), and air-cooled commercial unitary air conditioners (ACUACs) 
which have a rated cooling capacity greater than or equal to 65,000 
Btu/h and less than 760,000 Btu/h; and all classes of computer room air 
conditioners (CRACs); as well as to consider adopting a new test 
procedure for dedicated outdoor air systems (DOASes), equipment covered 
by ASHRAE Standard 90.1 for the first time. In response to other 
statutory requirements for DOE to review its test procedures at least 
once every seven years, DOE is also reviewing its test procedures for 
ECUACs and WCUACs with a rated cooling capacity less than 65,000 Btu/h, 
as well as all classes of variable refrigerant flow multi-split air 
conditioners and heat pumps (VRF multi-split systems) but excluding 
single-phase systems with a rated cooling capacity less than 65,000 
Btu/h, which are covered as consumer products. To inform interested 
parties and to facilitate this process, DOE has gathered data and has 
identified several issues that might warrant modifications to the 
currently applicable Federal test procedures, topics on which DOE is 
particularly interested in receiving comment. In overview, the issues 
outlined in this document mainly concern incorporation by reference of 
the most recent version of the relevant industry standard(s); 
efficiency metrics and calculations; clarification of test methods; and 
any additional topics that may inform DOE's decisions in a future test 
procedure rulemaking, including methods to reduce regulatory burden 
while ensuring the procedures' accuracy. These topics (and others 
identified by commenters) are ones which may be addressed in proposed 
test procedure amendments in a subsequent notice of proposed rulemaking 
(NOPR). DOE welcomes written comments and data from the public on any 
subject related to the test procedures for this equipment, including 
topics not specifically raised in this RFI.

DATES: Written comments, data, and information are requested and will 
be accepted on or before August 24, 2017.

ADDRESSES: Interested persons are encouraged to submit comments using 
the Federal eRulemaking Portal at https://www.regulations.gov. Follow 
the instructions for submitting comments. Alternatively, interested 
persons may submit comments, identified by docket number EERE-2017-BT-
TP-0018, by any of the following methods:
     Federal eRulemaking Portal: www.regulations.gov. Follow 
the instructions for submitting comments.
     Email: [email protected]. Include 
EERE-2017-BT-TP-0018 in the subject line of the message.
     Postal Mail: Appliance and Equipment Standards Program, 
U.S. Department of Energy, Building Technologies Office, Mailstop EE-
5B, Test Procedure RFI for Commercial Package Air Conditioning and 
Heating Equipment, Docket No. EERE-2017-BT-TP-0018 and/or RIN 1904-
AD93, 1000 Independence Avenue SW., Washington, DC 20585-0121. If 
possible, please submit all items on a compact disc (CD), in which case 
it is not necessary to include printed copies.
     Hand Delivery/Courier: Appliance and Equipment Standards 
Program, U.S. Department of Energy, Building Technologies Office, 950 
L'Enfant Plaza, SW., 6th Floor, Washington, DC 20024. Telephone: (202) 
586-6636. If possible, please submit all items on a CD, in which case 
it is not necessary to include printed copies.
    No telefacsimilies (faxes) will be accepted. For detailed 
instructions on submitting comments and additional information on the 
rulemaking process, see section III of this document (Public 
Participation).
    Docket: The docket for this activity, which includes Federal 
Register notices, comments, and other supporting document/materials, is 
available for review at www.regulations.gov. All documents in the 
docket are listed in the www.regulations.gov index. However, not all 
documents listed in the index may be publicly available, such as 
information that is exempt from public disclosure.
    The docket Web page can be found at: https://www.regulations.gov/docket?D=EERE-2017-BT-TP-0018. The docket Web page will contain simple 
instructions on how to access all documents, including public comments, 
in the docket. See section III of this document, Public Participation, 
for information on how to submit comments through www.regulations.gov.

FOR FURTHER INFORMATION CONTACT: Ms. Catherine Rivest, U.S. Department 
of Energy, Office of Energy Efficiency and Renewable Energy, Building 
Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington, 
DC 20585-0121. Telephone: (202) 586-7335. Email: 
[email protected].
    Mr. Eric Stas, U.S. Department of Energy, Office of the General 
Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC 20585. 
Telephone: (202) 586-9507. Email: [email protected].
    For further information on how to submit a comment, or review other 
public comments and the docket,

[[Page 34428]]

contact the Appliance and Equipment Standards Program staff at (202) 
586-6636 or by email: [email protected].

SUPPLEMENTARY INFORMATION:

Table of Contents

I. Authority and Background
II. Discussion
    A. Test Procedure for Computer Room Air Conditioners
    1. Scope
    a. Computer Room Cooling Application
    b. Configurations
    2. Energy Efficiency Descriptor
    a. Integrated Efficiency Metrics
    b. Part-Load Operation Due to Unit Oversizing
    c. Operation Modes Other Than Standard Cooling Mode
    3. Industry Test Standards
    a. Standard Models and Application Classes in AHRI 1360-2016
    b. ASHRAE 37 and Secondary Method
    c. Minimum External Static Pressure
    d. Setting Indoor Airflow
    e. Refrigerant Charging Instruction
    B. Test Procedure for Dedicated Outdoor Air Systems
    1. Definition
    a. Air Intake Source and Dehumidification Capability
    b. Reheat
    2. Energy Efficiency Descriptors
    a. Dehumidification Metric
    b. Heating Metric
    3. Test Method
    a. Airflow
    b. Liquid Flow
    c. Test Conditions
    d. Tolerances
    e. Capacity Measurement
    f. Test Set-Up
    C. Test Procedure for Air-Cooled, Water-Cooled, and 
Evaporatively-Cooled Equipment
    1. Energy Efficiency Descriptor
    2. Addressing Changes to AHRI 340/360
    a. Head Pressure Controls
    b. Refrigerant Charging Requirements
    c. Adjustment for Different Atmospheric Pressure Conditions
    d. Measurement of Condenser Air Inlet Temperature (ACUAC and 
ECUAC)
    e. Tolerance of Tested Indoor Airflow Relative to Rated Indoor 
Airflow (ECUAC and WCUAC)
    f. Vertical Separation of Indoor and Outdoor Units
    g. Outdoor Entering Air Wet-Bulb Temperature (ECUAC)
    h. Single-Zone Variable-Air-Volume and Multi-Zone Variable-Air-
Volume
    3. Additional Test Method Issues
    a. Length of Refrigerant Line Exposed to Outdoor Conditions
    b. Atmospheric Pressure Measurement
    c. Consistency Among Test Procedures for Small and Large ECUAC 
and WCUAC Equipment Classes
    d. Make-Up Water Temperature (ECUAC)
    e. Secondary Measurement Method for Capacity (ECUAC)
    f. Piping Evaporator Condensate to Condenser Pump (ECUAC)
    g. Purge Water Settings (ECUAC)
    h. Condenser Spray Pumps (ECUAC)
    i. Additional Steps To Verify Proper Operation (ECUAC)
    D. Test Procedure for Variable Refrigerant Flow Multi-Split Air 
Conditioners and Heat Pumps
    1. Energy Efficiency Descriptors
    2. Representativeness and Repeatability
    3. Test Method
    a. Transient Testing: Oil Recovery Mode
    b. Airflow Setting and Minimum External Static Pressure
    c. Condenser Head Pressure Controls
    d. Air Volume Rate for Non-Ducted Indoor Units
    e. Secondary Test Method
    f. Heat Recovery
    4. Representations
    a. Tested Combination
    b. Determination of Represented Values
    E. Other Test Procedure Topics
III. Submission of Comments

I. Authority and Background

    Title III, part C \1\ of the Energy Policy and Conservation Act of 
1975 (EPCA or the Act), Public Law 94-163 (42 U.S.C. 6311-6317, as 
codified), added by Public Law 95-619, title IV, section 441(a), 
established the Energy Conservation Program for Certain Industrial 
Equipment, which includes provisions covering the types of commercial 
heating and air conditioning equipment that are the subject of this 
notice.\2\ This covered equipment includes small, large, and very large 
commercial package air conditioning and heating equipment, which 
specifically includes variable refrigerant flow multi-split air 
conditioners and heat pumps (VRF multi-split systems),\3\ computer room 
air conditioners (CRACs), dedicated outdoor air systems (DOASes), 
evaporatively-cooled commercial unitary air conditioners (ECUACs) less 
than 760,000 Btu/h, water-cooled commercial unitary air conditioners 
(WCUACs) less than 760,000 Btu/h, and air-cooled commercial unitary air 
conditioners (ACUACs) greater than or equal to 65,000 Btu/h and less 
than 760,000 Btu/h, all of which are addressed in this document. (42 
U.S.C. 6311(1)(B)-(D))
---------------------------------------------------------------------------

    \1\ For editorial reasons, upon codification in the U.S. Code, 
part C was redesignated part A-1.
    \2\ All references to EPCA in this document refer to the statute 
as amended through the Energy Efficiency Improvement Act of 2015, 
Public Law 114-11 (April 30, 2015).
    \3\ Not including single-phase VRF less than 65,000 Btu/h.
---------------------------------------------------------------------------

    Under EPCA, the energy conservation program consists essentially of 
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation 
standards, and (4) certification and enforcement procedures. Relevant 
provisions of the Act include definitions (42 U.S.C. 6311), energy 
conservation standards (42 U.S.C. 6313), test procedures (42 U.S.C. 
6314), labeling provisions (42 U.S.C. 6315), and the authority to 
require information and reports from manufacturers (42 U.S.C. 6316).
    Federal energy efficiency requirements for covered equipment 
established under EPCA generally supersede State laws and regulations 
concerning energy conservation testing, labeling, and standards. (See 
42 U.S.C. 6316(a) and (b); 42 U.S.C. 6297) DOE may, however, grant 
waivers of Federal preemption for particular State laws or regulations, 
in accordance with the procedures and other provisions of EPCA. (42 
U.S.C. 6316(b)(2)(D))
    The Federal testing requirements consist of test procedures that 
manufacturers of covered equipment must use as the basis for: (1) 
Certifying to DOE that their equipment complies with the applicable 
energy conservation standards adopted pursuant to EPCA (see 42 U.S.C. 
6316(b); 42 U.S.C. 6296), and (2) making representations about the 
efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE must 
use these test procedures to determine whether the equipment complies 
with relevant standards promulgated under EPCA.
    Under 42 U.S.C. 6314, EPCA sets forth the general criteria and 
procedures DOE is required to follow when prescribing or amending test 
procedures for covered equipment. EPCA requires that any prescribed or 
amended test procedures must be reasonably designed to produce test 
results which reflect energy efficiency, energy use or estimated annual 
operating cost of a covered equipment during a representative average 
use cycle or period of use and requires that the test procedure not be 
unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
    EPCA requires that the test procedures for commercial package air 
conditioning and heating equipment be those generally accepted industry 
testing procedures or rating procedures developed or recognized by the 
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) or by the 
American Society of Heating, Refrigerating and Air-Conditioning 
Engineers (ASHRAE), as referenced in ASHRAE Standard 90.1, ``Energy 
Standard for Buildings Except Low-Rise Residential Buildings'' (ASHRAE 
Standard 90.1), and that if such an industry test procedure is amended, 
DOE must update its test procedure to be consistent with the amended 
industry test procedure, unless DOE determines, by rule published in 
the Federal Register and

[[Page 34429]]

supported by clear and convincing evidence, that the amended test 
procedure would not meet the requirements in 42 U.S.C. 6314(a)(2) and 
(3) related to representative use and test burden. (42 U.S.C. 
6314(a)(4))
    ASHRAE Standard 90.1 was updated on October 26, 2016,\4\ and this 
update made changes to the test procedure references in ASHRAE Standard 
90.1-2013 for CRACs, as well as ACUACs, ECUACs, and WCUACs with cooling 
capacity >=65,000 Btu/h and <760,000 Btu/h.\5\ Additionally, ASHRAE 
Standard 90.1-2016 added efficiency levels and a test procedure for 
DOAS. These changes on the part of ASHRAE trigger DOE's obligation to 
review these test procedures pursuant to the requirements of EPCA.
---------------------------------------------------------------------------

    \4\ There is no publication date printed on ASHRAE Standard 
90.1-2016, but ASHRAE issued a press release on October 26, 2016, 
which can be found at https://www.ashrae.org/news/2016/ashrae-ies-publish-2016-energy-efficiency-standard.
    \5\ For water-source heat pumps, ASHRAE Standard 90.1-2016 
included reference to a reaffirmation of the existing test 
procedure, and as such, does not constitute a change requiring DOE 
action.
---------------------------------------------------------------------------

    EPCA also requires that DOE conduct an evaluation of test 
procedures at least once every seven years for each class of covered 
equipment to determine if an amended test procedure would more 
accurately or fully comply with the requirements in 42 U.S.C. 
6314(a)(2) and (3). (42 U.S.C. 6314(a)(1)(A)) After this evaluation, 
DOE must either prescribe amended test procedures or publish a notice 
in the Federal Register regarding its determination not to amend test 
procedures. (42 U.S.C. 6314(a)(1)(A)(i) and (ii)) In either case, if 
DOE determines that a test procedure amendment is warranted, it must 
publish proposed test procedures and offer the public an opportunity to 
present oral and written comments on them. (42 U.S.C. 6314(b)) To amend 
a test procedure, DOE must determine the extent to which the proposed 
test procedure would alter the equipment's measured energy efficiency. 
If DOE determines that the amended test procedure would alter the 
measured efficiency of the covered equipment, DOE must amend the 
applicable energy conservation standard accordingly. (42 U.S.C. 
6314(a)(4)(C); 42 U.S.C. 6293(e))
    Although ASHRAE Standard 90.1-2016 did not include revisions to the 
test procedures for VRF equipment or ECUACs and WCUACs with cooling 
capacity <65,000 Btu/h, DOE is including such equipment in this RFI 
under DOE's 7-year lookback authority. The test procedures under review 
in this RFI are shown in Table I.1.

                Table I.1--Commercial Air Conditioning and Heating Equipment Included in the RFI
----------------------------------------------------------------------------------------------------------------
                                       Review test procedure
                                       due to  amendments to     Last test procedure    7-Year review due (final
      Equipment included in RFI           industry test or          (final rule)                 rule)
                                         rating procedure?
----------------------------------------------------------------------------------------------------------------
CRAC................................  Yes....................  77 FR 28928 (May 16,    May 16, 2019.
                                                                2012).
DOAS................................  Yes....................  N/A...................  N/A.
ECUAC...............................  Yes (>=65,000 Btu/h      77 FR 28928 (May 16,    May 16, 2019.
                                       only*).                  2012).
WCUAC...............................  Yes (>=65,000 Btu/h      77 FR 28928 (May 16,    May 16, 2019.
                                       only*).                  2012).
ACUAC >= 65,000 Btu/h**.............  Yes....................  80 FR 79655 (Dec. 23,   Dec. 23, 2022.
                                                                2015).
VRF (except single-phase <65,000 Btu/ No.....................  77 FR 28928 (May 16,    May 16, 2019.
 h***).                                                         2012).
----------------------------------------------------------------------------------------------------------------
* DOE is considering ECUAC and WCUAC with cooling capacity less than 65,000 Btu/h in this rulemaking notice
  under its 7-year lookback authority.
** DOE will be considering ACUAC with cooling capacity less than 65,000 Btu/h under its 7-year lookback
  authority in a separate test procedure rulemaking.
*** Single-phase VRF with rated cooling capacity less than 65,000 Btu/h are covered under DOE's consumer product
  regulations for central air conditioners.

    Upon completion of this proceeding, DOE expects to satisfy for all 
the equipment categories listed in Table I.1, both the requirements of 
EPCA pertaining to DOE action prompted by amendments to industry test 
or rating procedures, as well as EPCA's 7-year review requirements. In 
support of its test procedures, DOE conducts in-depth technical 
analyses of publicly-available test standards and other relevant 
information. DOE continually seeks data and public input to improve its 
testing methodologies to more accurately reflect customer use and to 
produce repeatable results. In general, DOE is requesting comment and 
supporting data regarding representative and repeatable methods for 
measuring the energy use of the equipment that is the subject of this 
RFI. As such, DOE is interested in feedback on any aspect of the test 
procedures for the identified equipment, but it is especially 
interested in receiving comment and information on the specific topics 
discussed below.

II. Discussion

    This RFI discusses each category of equipment under consideration 
in separate sections set forth below. DOE seeks input to aid in the 
development of the technical and economic analyses regarding whether 
amended test procedures for each category of equipment may be 
warranted. Specifically, DOE is requesting comment on any opportunities 
to streamline and simplify testing requirements for each category of 
equipment discussed in this notice.
    Additionally, DOE welcomes comments on other issues relevant to the 
conduct of this rulemaking that may not specifically be identified in 
this document. In particular, DOE notes that under Executive Order 
13771, ``Reducing Regulation and Controlling Regulatory Costs,'' 
Executive Branch agencies such as DOE are directed to manage the costs 
associated with the imposition of expenditures required to comply with 
Federal regulations. See 82 FR 9339 (Feb. 3, 2017). Pursuant to that 
Executive Order, DOE encourages the public to provide input on measures 
DOE could take to lower the cost of its regulations applicable to the 
commercial equipment addressed in this notice consistent with the 
requirements of EPCA.
    Within each section, DOE raises relevant issues regarding scope, 
efficiency metric, and test method, with a focus on changes identified 
by review of the updated test procedures in ASHRAE Standard 90.1-2016. 
As required by statute, DOE is considering amendments to the current 
test procedures (and in the case of DOAS, adoption of a new test 
procedure) to be consistent with those specified in

[[Page 34430]]

ASHRAE 90.1-2016, where possible. Further, DOE requests comment on the 
benefits and burdens of adopting the industry test procedures 
referenced in ASHRAE 90.1-2016, without modification.

A. Test Procedure for Computer Room Air Conditioners

    DOE's test procedure for CRACs, set forth at 10 CFR 431.96, 
currently incorporates by reference ASHRAE 127-2007, ``Method of 
Testing for Rating Computer and Data Processing Room Unitary Air 
Conditioners'', (omit section 5.11), with additional provisions 
indicated in 10 CFR 431.96(c) and (e). The energy efficiency metric is 
sensible coefficient of performance (SCOP) for all CRAC equipment 
categories. ASHRAE 90.1-2016 updated its test procedure reference for 
CRACs from ASHRAE 127-2007 to AHRI 1360-2016, ``Performance Rating of 
Computer and Data Processing Room Air Conditioners'', which in turn 
references ASHRAE 127-2012. This update on the part of ASHRAE triggered 
DOE to review its test procedure for CRACs. In addition, DOE is aware 
that the ASHRAE 127 committee is working on an updated version of that 
standard, and DOE may consider the updated version when it is 
available.
    In order to ensure that potential adoption of AHRI 1360-2016 as the 
DOE test procedure for CRACs would satisfy statutory requirements, the 
following sections consider issues related to the reduced scope of AHRI 
1360-2016 relative to ASHRAE 127-2007, as well as updates in the 
industry test standards to the test method and rating conditions. DOE 
also explores other CRAC-related issues including definitions and the 
efficiency metric.
1. Scope
a. Computer Room Cooling Application
    The definition for ``computer room air conditioner'' in DOE's 
regulations does not include physical design differences, component 
characteristics, or performance features that distinguish CRACs from 
other commercial package air conditioning and heating equipment (e.g., 
CUACs) used for comfort cooling.\6\ In March 2012, DOE published a 
supplemental notice of proposed rulemaking (SNOPR) refining its 
proposed definition of ``computer room air conditioner.'' 77 FR 16769, 
16772-16773 (March 22, 2012). In response to this SNOPR, several 
stakeholders commented about differences in performance features 
between CRACs and CUACs. Carrier commented that CRACs are designed to 
handle different load characteristics, most notably by focusing on 
sensible load and not latent cooling. (EERE-2011-BT-STD-0029, Carrier, 
No. 28 at p. 1) Panasonic commented that CRACs have a different 
operating range and that they operate with tighter tolerances on 
temperature and relative humidity than do CUACs. (EERE-2011-BT-STD-
0029, Panasonic, No. 20 at pp. 68-69) Despite these comments, DOE was 
unable to determine any specific requirements on sensible load that 
would consistently differentiate CRACs from CUACs and allow it to 
incorporate performance characteristics into the CRAC definition. 
Therefore, on May 16, 2012, DOE adopted the current definition for 
``computer room air conditioner'' that distinguishes them from CUACs 
based on application differences. 77 FR 28928, 28947-28948 (May 16, 
2012; ``May 2012 final rule'').
---------------------------------------------------------------------------

    \6\ DOE defines ``computer room air conditioner'' as a basic 
model of commercial package air-conditioning and heating equipment 
(packaged or split) that is: used in computer rooms, data processing 
rooms, or other information technology cooling applications; rated 
for sensible coefficient of performance (SCOP) and tested in 
accordance with 10 CFR 431.96, and is not a covered consumer product 
under 42 U.S.C. 6291(1)-(2) and 6292. A computer room air 
conditioner may be provided with, or have as available options, an 
integrated humidifier, temperature, and/or humidity control of the 
supplied air, and reheating function. 10 CFR 431.92.
---------------------------------------------------------------------------

    A review of 1000 CRAC models in DOE's Compliance Certification 
Management System (CCMS) shows that all of these models have a sensible 
heat ratio (SHR) above 80 percent. In contrast, commercial air 
conditioners used for comfort cooling generally have SHRs between 65 
percent and 80 percent. DOE notes that the indoor air test condition 
for CUACs has a higher relative humidity than the test condition for 
CRACs. Therefore, the SHR for any air conditioner will be higher when 
tested using the CRAC test condition than when using the CUAC test 
conditions. However, DOE is considering whether a specific SHR (e.g., 
80 percent at the test condition of CRACs) would be sufficient to 
differentiate CRACs from other CUACs.
    Issue CRAC-1: DOE requests comment on the extent to which models of 
commercial package air conditioners are marketed and/or installed for 
use in both comfort cooling and computer room cooling applications. DOE 
also seeks comment on whether there are models rated for energy 
efficiency ratio (EER) or seasonal energy efficiency ratio (SEER) and 
not SCOP that are used for computer room cooling--if so, DOE requests 
comment and data on the extent of the use of such equipment for 
computer room cooling.
    Issue CRAC-2: DOE seeks comment and data on whether a specific 
sensible heat ratio could be selected that would effectively and 
consistently distinguish CRACs from other classes of commercial package 
air conditioners. DOE also seeks comment on any other design 
differences or performance features that would help resolve this issue.
b. Configurations
    The following sections discuss configurations of CRACs that DOE has 
identified on the market and for which DOE is considering potential 
modifications to its current test procedure.
i. Airflow Direction and Mounting Location
    DOE's minimum efficiency standards for CRACs in 10 CFR 431.97 apply 
to down-flow and up-flow units, which is terminology typically applied 
to floor-mounted units. However, DOE's test procedure for CRACs in 10 
CFR 431.96 is not limited to floor-mounted units. On January 15, 2015, 
DOE published a final guidance document (``January 2015 Guidance 
Document'') to clarify the coverage of horizontal free-discharge CRACs 
under DOE's regulations for CRACs set forth in 10 CFR part 431.\7\ In 
the January 2015 Guidance Document, DOE clarified that while horizontal 
free-discharge CRACs are not subject to the energy conservation 
standards for CRACs, the 2012 test procedure final rule did not have an 
exception for any specific airflow direction (i.e., down-flow, up-flow 
or horizontal-flow) or mounting type (i.e., floor-mount, ceiling-
mount).\8\ Therefore, any manufacturer making representations of the 
energy consumption of CRACs (including ceiling-mounted ducted or free-
discharge units or horizontal free-discharge units and all other 
equipment that meets the CRAC definition) must base these 
representations on tests conducted according to the current DOE test 
procedure. A manufacturer may request a test procedure waiver for a

[[Page 34431]]

basic model if it contains design features that prevent testing 
according to the DOE test procedure, or such testing may generate 
results that are unrepresentative of the true energy consumption of the 
basic model. 10 CFR 431.401. To date, DOE has not received any such 
waiver requests.
---------------------------------------------------------------------------

    \7\ The January 2015 Guidance document can be found as Document 
Number 2 in Docket Number EERE-2014-BT-GUID-0022.
    \8\ On October 7, 2015, DOE published a draft guidance document 
(``October 2015 Guidance Document'') seeking comment concerning the 
coverage of ceiling-mount ducted and free-discharge CRACs. (The 
October 2015 Guidance document can be found as Document Number 3 in 
Docket Number EERE-2014-BT-GUID-0022.) DOE has not yet finalized 
this guidance with respect to ceiling-mounted ducted and free-
discharge CRACs. The draft guidance also took the position that such 
CRACs were not subject to standards, but the test procedure did not 
have an exception for any specific airflow direction.
---------------------------------------------------------------------------

    DOE notes that the scope of AHRI Standard 1360-2016 (AHRI 1360-
2016), ``2016 Standard for Performance Rating of Computer and Data 
Processing Room Air Conditioners'', the test procedure referenced in 
ASHRAE 90.1-2016, excludes ceiling-mounted units, only covering floor-
mounted units. As stated in the October 2015 Guidance Document, ASHRAE 
127-2007 can be used to test ceiling-mounted units. DOE understands 
that the ASHRAE 127 committee is considering additional provisions that 
would apply specifically to ceiling-mounted equipment, but a revised 
ASHRAE 127 standard is not yet available. For those CRACs not addressed 
by AHRI 1360-2016, DOE may consider continuing to reference ASHRAE 127-
2007 or updating to a revised version of ASHRAE 127 when published, if 
appropriate.
    Issue CRAC-3: DOE requests comment on the appropriate test 
procedure for ceiling-mounted CRACs, considering that AHRI 1360-2016 
does not address them, and the test burden associated with any such 
procedure.
ii. Three-Phase Portable Units
    Several manufacturers market portable units for commercial use in 
data centers and computer rooms. On June 1, 2016, under its authority 
for regulating consumer products, DOE published a final rule that 
established a test procedure for portable air conditioners. 81 FR 
35242. In addition, DOE issued a final rule to establish energy 
conservation standards for portable air conditioners. In a final 
determination published on April 18, 2016, DOE established a definition 
for ``portable air conditioner'' that excludes units that use three-
phase power as a means of differentiating the portable air conditioners 
that are consumer products (and thus determined to be covered products) 
from those that could normally not be used in residential applications. 
81 FR 22514, 22519-22520. DOE identified several models of portable 
units that are marketed for commercial computer room cooling 
applications and use three-phase power instead of single-phase power. 
This equipment does not meet DOE's definition for ``portable air 
conditioner'' and is not subject to DOE's current test procedures or 
standards for portable air conditioners. DOE considers any portable 
unit marketed for computer room cooling that is rated with SCOP and is 
not a covered consumer product under 42 U.S.C. 6291(1)-(2) and 6292 to 
meet its definition of ``computer room air conditioner.'' DOE is 
considering amendments to its test procedure for computer room air 
conditioners to better reflect usage in the field of portable units 
used for computer room cooling that are not covered consumer products, 
as applicable.
    Issue CRAC-4: DOE requests comments on whether any specific 
provisions should be considered to address how to test portable units 
used in computer room cooling applications, such as whether they are 
typically ducted and, if so, what a representative minimum external 
static pressure (ESP) and return air temperature would be.
iii. Single Package Non-Floor-Mounted Air Conditioners
    DOE identified several manufacturers that produce single package 
non-floor-mounted air conditioners (other than portable units) that are 
marketed specifically for cooling computer rooms, telecommunication 
rooms, and data centers. DOE identified such air conditioners designed 
for both interior and exterior installation. Of the exterior-mount 
units DOE identified, some meet DOE's definition for ``single package 
vertical air conditioner'' (one type of single-package vertical unit 
(SPVU)), while others are rooftop units. All of these identified models 
appear to meet DOE's definition for computer room air conditioners. 
Therefore, DOE is considering whether amendments are needed in its test 
procedure for CRACs to better reflect the in-field energy use and 
installation practices of single-package non-floor-mounted air 
conditioners used for computer room cooling.
    Issue CRAC-5: DOE seeks information on the extent to which single-
package non-floor-mounted air conditioners are used in computer room 
applications.
    Issue CRAC-6: DOE seeks comment on whether special test procedure 
provisions should be developed for different kinds of single package 
non-floor-mounted air conditioners that are used for computer room 
cooling, including: (1) Whether such units are typically installed with 
supply/return air ducting; and (2) whether the test set-up described in 
ANSI/ASHRAE 37-2009, ``Methods of Testing for Rating Electrically 
Driven Unitary Air-Conditioning and Heat Pump Equipment,'' (ASHRAE 37-
2009) is appropriate and if any additional test set-up provisions would 
be needed.
    Issue CRAC-7: DOE requests comment on whether there are other 
configurations of commercial package air conditioners that are marketed 
for computer room cooling applications and that meet DOE's definition 
for CRAC, beyond floor-mounted units (i.e., up-flow, down-flow, and 
horizontal discharge), ceiling-mounted units, portable units, indoor 
single package units, rooftop units, and certain SPVUs.
2. Energy Efficiency Descriptor
    When ASHRAE 90.1-2016 amended its energy efficiency levels, it also 
updated its test procedure from ASHRAE 127-2007 to AHRI 1360-2016. AHRI 
1360-2016 defines standard rating configurations and conditions and 
provides additional requirements for testing CRACs, but does not 
include a method of test. Instead, AHRI 1360-2016 references ASHRAE 
127-2012 as the method of test. This test procedure change also updated 
the ASHRAE 90.1 efficiency metric for CRACs from SCOP to net sensible 
coefficient of performance (NSenCOP). DOE's current efficiency metric 
for CRACs is SCOP. As compared with SCOP, the new metric NSenCOP 
specifies different operating conditions for water-cooled and glycol-
cooled models and adjusts the efficiency to account for the energy use 
associated with the water or glycol pump. These changes presumably 
result in a more accurate representation of the energy use associated 
with the equipment. Because ASHRAE 90.1 changed the metric to NSenCOP, 
EPCA requires that DOE must consider updating to NSenCOP as well. For 
completeness, DOE reviews other issues related to efficiency metrics 
for CRACs in this section, including: (1) Integrated efficiency 
metrics; (2) part-load operation due to unit oversizing; and (3) 
operation modes other than standard cooling mode. If DOE ultimately 
decides to change its metric from SCOP to NSenCOP, DOE would need to 
develop a crosswalk analysis to translate DOE's existing standards--
which are in terms of SCOP--to the NSenCOP metric.
a. Integrated Efficiency Metrics
    ASHRAE 127-2007 includes the integrated efficiency metric, adjusted 
sensible coefficient of performance (ASCOP), which is calculated based 
on the SCOPs at four different rating conditions (A, B, C, and D), 
representing different ambient conditions, with weightings for the SCOP 
at each rating condition based on the climate at a specific location. 
ASHRAE 127-2012 and AHRI 1360-2016 include an updated integrated 
efficiency metric, integrated net sensible coefficient of

[[Page 34432]]

performance iNSenCOP, instead of ASCOP. There are differences between 
ASCOP and iNSenCOP, similar to those between SCOP and NSenCOP, but both 
are weighted averages of sensible-capacity-based efficiencies measured 
for operation at different ambient conditions.
    The ASCOP and iNSenCOP test methods in ASHRAE 127-2007, ASHRAE 127-
2012, and AHRI 1360-2016 require units to maintain a constant sensible 
cooling capacity at lower ambient temperatures. However, it is not 
clear how the lower-ambient tests are to be conducted. As the ambient 
temperature decreases, the maximum cooling capacity of a CRAC will 
inherently increase. ASHRAE 127-2012 does not provide guidance 
regarding how the unit should be controlled in order to deliver the 
same amount of sensible cooling as its capacity increases for the 
lower-ambient tests.
    Issue CRAC-8: DOE requests comment on whether DOE should consider 
adopting an integrated efficiency metric (e.g., iNSenCOP). Also if so, 
DOE requests comment on how the requirement to maintain a constant 
sensible cooling capacity associated with the iNSenCOP test procedure 
should be implemented during testing.
b. Part-Load Operation Due to Unit Oversizing
    CRACs typically operate at part-load (i.e., less than designed full 
cooling capacity) in the field. Reasons for this may include, but are 
not limited to, redundancy in installed units to prevent server 
shutdown if a CRAC unit stops working, and server room designers 
building in extra cooling capacity to accommodate additional server 
racks in the future. At part-load, single-speed systems cycle on and 
off to match the cooling requirement, while variable speed systems 
might operate at a different speed, but both control strategies change 
performance as compared to full-load operation. While the DOE test 
procedure measures performance at full-load, DOE estimated in its May 
2012 final rule analysis that CRAC units operate on average at a 
sensible load of 65 percent of the full-load sensible capacity. (EERE-
2011-BT-STD-0029-0021, pp. 4-15, 4-16). This may indicate a difference 
between DOE test procedure operating requirements and typical field 
operation. Therefore, DOE is considering whether this practice of 
oversizing should be factored into a CRAC efficiency metric to the 
extent that it would better represent an average use cycle.
    Issue CRAC-9: DOE requests information on the range of typical 
field load levels for CRACs at conditions close to or at the maximum 
ambient outdoor air temperature conditions specified in the DOE test 
procedure for various unit capacities. DOE seeks input on typical rules 
of thumb for oversizing and whether the issues of oversizing of this 
equipment should be addressed in the efficiency metric.
c. Operation Modes Other Than Standard Cooling Mode
    Many CRACs operate in air circulation mode. DOE understands that 
redundant units are usually installed in the computer room, and some of 
the redundant units can be controlled to operate in air circulation 
mode for better air movement. In this mode, the direct expansion 
refrigerant system is shut down, and only evaporator blowers and 
controls are on. DOE is considering whether the energy consumption of 
air circulation mode should be considered in the CRAC energy efficiency 
metric.
    Issue CRAC-10: DOE seeks comment on the conditions under which 
CRACs will operate in air circulation mode (i.e., operating the indoor 
fan without actively cooling) in the field, whether each CRAC switches 
automatically between standard cooling mode and air circulation mode, 
and if so, the time percentage that CRACs operate in such circulation 
mode. DOE also seeks comment on what fan setting(s) is used for air 
circulation mode and whether DOE should consider this energy use in the 
CRAC efficiency metric.
3. Industry Test Standards
    In its test procedure for CRACs, DOE currently incorporates by 
reference ASHRAE 127-2007 (omitting section 5.11). 10 CFR 431.96. As 
mentioned previously, ASHRAE published an updated version of this test 
standard in 2012, ASHRAE 127-2012. ASHRAE 127-2012 includes several 
modifications from ASHRAE 127-2007, which are discussed in the 
following sections. DOE is aware that ASHRAE is working to update 
ASHRAE 127-2012, and DOE may consider the newer version of the test 
standard if it is published during the course of this rulemaking. As 
discussed previously, DOE is also aware that the referenced industry 
test procedure in ASHRAE Standard 90.1-2016 has changed to AHRI 1360-
2016. The scope of AHRI 1360-2016 covers only floor-mounted computer 
and data processing room air conditioners, including up-flow, down-
flow, and horizontal-flow units. AHRI 1360-2016 defines standard 
configurations and provides rating conditions and additional 
requirements for testing CRACs, but does not include a method of test. 
Instead, AHRI 1360-2016 references ASHRAE 127-2012 to conduct the test. 
Consequently, DOE will consider adopting both industry test standards. 
In the following sections, DOE discusses specific test procedure-
related issues and questions regarding ASHRAE 127-2012 and AHRI 1360-
2016.
a. Standard Models and Application Classes in AHRI 1360-2016
    Indoor floor-mounted CRACs can be installed in different 
configurations, which vary by direction of airflow and connections 
(e.g., raised floor plenum, ducted, free air). Instead of specifying 
test conditions for all possible combinations, AHRI 1360-2016 includes 
the concept of ``standard models'' that characterize common 
configurations and specify standard rating conditions (e.g., external 
static pressure, return air temperature) for each style of indoor 
floor-mounted CRAC. Table C.1 of Appendix C of AHRI 1360-2016 defines 
four different standard models: (1) Down-flow (with raised floor plenum 
discharge and free air return); (2) horizontal-flow (with free air 
discharge and free air return); (3) up-flow ducted (with ducted 
discharge and free air return); and (4) up-flow non-ducted (with free 
air discharge and free air return). AHRI 1360-2016 also specifies which 
of the four standard model test set-ups and standard rating conditions 
apply for down-flow, horizontal-flow, and up-flow CRACs. For example, 
down-flow units are tested with a raised floor plenum discharge and a 
free air return.
    DOE notes that for up-flow CRACs, AHRI 1360-2016 includes two 
standard models with associated standard rating conditions, one for 
ducted discharge connections and one for free air discharge. However, 
connection variations are characteristics of installations. A given up-
flow unit could be installed either with or without a duct. DOE's 
research has not revealed that up-flow CRACs have physical 
characteristics that clearly distinguish them as ducted or non-ducted 
models. Hence, it is not clear which of the AHRI 1360-2016 up-flow 
standard model requirements would be used for testing.
    Issue CRAC-11: DOE requests comment on what equipment 
characteristics can be used to determine whether up-flow CRACs should 
be tested as ducted or non-ducted models. DOE also requests comments on 
whether up-flow units can be sold for both up-flow ducted and up-flow 
non-ducted applications and whether such

[[Page 34433]]

models are currently tested using both ducted and non-ducted standard 
rating conditions.
    DOE also notes that, in addition to the four standard models of 
floor-mounted CRACs, Table C.1 of AHRI 1360-2016 also includes many 
additional combinations of connections, referred to as application 
configurations, but does not provide standard rating conditions for 
these configurations.
    Issue CRAC-12: DOE requests confirmation that, although floor-
mounted CRACs may be sold to be installed in multiple configurations, 
all models are capable of being tested as one of the four standard 
models identified in Table C.1 of AHRI 1360-2016.
    AHRI 1360-2016 does not include standard models or standard rating 
conditions for ceiling-mount or non-floor mount CRACs. The current DOE 
test procedure, which incorporates by reference ASHRAE 127-2007, 
specifies different test operating conditions (e.g., different external 
static pressure) than AHRI 1360-2016.
    Issue CRAC-13: DOE requests comment on whether the test 
requirements of ASHRAE 127-2007 are representative of average use 
cycles for ceiling-mount and other non-floor-mounted CRACs. If not, DOE 
requests comment on which, if any, of the test requirements of AHRI 
1360-2016 would more appropriately represent average use cycles for 
such CRACs.
b. ASHRAE 37 and Secondary Method
    ASHRAE 127-2007 references ANSI/ASHRAE 37-2005, ``Methods of 
Testing for Rating Unitary Air-Conditioning and Heat Pump Equipment'' 
(ASHRAE 37-2005), while 127-2012 and AHRI 1360-2016 reference the 
updated version, ASHRAE 37-2009. ASHRAE 37-2005 and the updated ASHRAE 
37-2009 describe test methods for measuring cooling capacity, heating 
capacity, and electrical energy use of air conditioners and heat pumps. 
However, it is not clear whether the industry test standards for CRACs 
reference specific provisions or all of the provisions of ASHRAE 37-
2005 or ASHRAE 37-2009.\9\ No alternate methods for determining cooling 
capacity are included in ASHRAE 127 or AHRI 1360. Therefore, DOE 
expects that manufacturers do use the test methods of ASHRAE 37-2005 or 
ASHRAE 37-2009 to determine cooling capacity, sensible cooling 
capacity, and electric energy use of CRACs. DOE is considering updating 
the DOE test procedure to clarify that the test method is based on 
ASHRAE 37-2009, except as modified or adjusted by ASHRAE 127-2012 or 
AHRI 1360-2016.
---------------------------------------------------------------------------

    \9\ For example, in ASHRAE 127-2007, the reference to ASHRAE 37-
2005 is located under a subsection 5.1.4.5.2 titled, ``Raised Floor 
Plenum Systems'' which is located under section 5.1.4.5 titled 
``External Resistance, Ducted Connected, Floor Plenum and Free Air 
Discharge.''
---------------------------------------------------------------------------

    Issue CRAC-14: DOE seeks comment on whether the test method of 
ASHRAE 37-2009 is appropriate for measuring capacity, sensible 
capacity, and electric energy use for all configurations of CRACs 
(including configurations for which DOE does not currently prescribe 
energy conservation standards).
    Table 2b in section 8 of ASHRAE 37-2009 includes test operating 
tolerances (maximum allowable observed range) and condition tolerances 
(maximum variation of the average from a specified test condition) for 
several parameters, including air and fluid temperatures, in order to 
reduce the uncertainty of the measurement of cooling capacity, heating 
capacity, and/or energy use of air conditioners or heat pumps. However, 
this section of ASHRAE 37-2009 is not explicitly referenced by the CRAC 
industry test standards. Section 5.1 of ASHRAE 127-2007 and section 
5.2.1 of ASHRAE 127-2012 only include an operation tolerance for the 
room temperature, and no versions of ASHRAE 127 or AHRI 1360 include 
any other tolerances. DOE considers the tolerances of Table 2b of 
ASHRAE 37-2009 to be relevant for CRACs and important to reduce 
variability of key CRAC performance measurements.
    Issue CRAC-15: DOE requests comment on whether any operating or 
condition tolerances included in Table 2b in section 8 of ASHRAE 37-
2009 are not appropriate for CRACs. If any are not appropriate, DOE 
requests an explanation as to why and suggestions on how the tolerances 
should be changed.
    Section 7.2.1 of ASHRAE 37-2009 requires that when testing 
equipment with a total cooling capacity less than 135,000 Btu/h, 
simultaneous capacity tests using the indoor air enthalpy method and 
one other applicable method must be conducted. Specifically, these 
other test methods include the outdoor air enthalpy method, the 
compressor calibration method, the refrigerant enthalpy method, and the 
outdoor liquid coil method. Table 1 in section 7 of ASHRAE 37-2009 
specifies which of these test methods are applicable for each equipment 
configuration and method of heat rejection in cooling mode. Section 
10.1.2 of ASHRAE 37-2009 requires that the total cooling capacity 
calculated from the two simultaneously conducted methods agree within 
6.0 percent.
    For CRACs with cooling capacity less than 135,000 Btu/h, DOE is 
considering whether its test procedure should require a secondary test 
method and how agreement between the primary and secondary methods 
should be evaluated. DOE is also considering whether the primary and 
secondary tests should be based on total cooling capacity or sensible 
cooling capacity. Basing these tests on sensible cooling capacity may 
be more appropriate because it is the basis of the CRAC efficiency 
metric in both ASHRAE Standard 90.1 and the current Federal standard.
    Issue CRAC-16: DOE seeks comment on whether a secondary test is 
appropriate for testing CRACs, for what range of cooling capacity such 
a requirement should apply for CRACs, how the requirement should be 
applied (given that most secondary test methods measure total rather 
than sensible capacity), and what level of agreement (in percent) 
should be required. DOE is also interested in detailed information on 
whether there would be a significant additional test burden resulting 
from a secondary test--and if so, the nature and extent of that burden.
    Many CRACs have compressors housed in their indoor units. ASHRAE 
37-2009 specifies modification of the indoor enthalpy method as 
depicted in its Figure 3, Calorimeter air enthalpy test method 
arrangement, for capturing the impact of compressor heat on the 
capacity measurement. However, none of the industry test standards 
explicitly call for using this test set-up for CRAC indoor units to 
take into consideration the cooling capacity reduction associated with 
compressor heat.
    Issue CRAC-17: DOE requests comment on whether it is appropriate to 
incorporate the impact of compressor heat in sensible capacity 
measurements for CRACs with compressors housed in their indoor units. 
DOE requests that the comments provide an explanation as to why it is 
or is not appropriate, and whether the answer depends on the specific 
CRAC configuration.
c. Minimum External Static Pressure
    ASHRAE 127-2007, ASHRAE 127-2012, and AHRI 1360-2016 all contain 
different minimum external static pressure (ESP) levels and categories, 
as indicated in Table II.1. In ASHRAE 127-2012, the minimum ESP levels 
are the same as for ASHRAE 127-2007, but ASHRAE 127-2012 defines 
``ducted systems'' as ``air conditioners intended to be connected to 
supply and/or return ductwork'' instead of ``to supply and return 
ductwork,'' as specified in ASHRAE 127-2007.

[[Page 34434]]



            Table II.1--External Static Pressure Requirements
------------------------------------------------------------------------
                                                            Minimum ESP
         Test standard                CRAC Category         (in. w.c.)
------------------------------------------------------------------------
ASHRAE 127-2007 and ASHRAE 127-  Ducted:                  ..............
 2012.                           Net Sensible Capacity <             0.8
                                  20 kW.                             1.0
                                 Net Sensible Capacity
                                  >= 20 kW.
                                 Free Discharge.........             0.0
AHRI 1360-2016.................  Up-flow Ducted:
                                 Net Sensible Capacity               0.3
                                  <65 kBtu/h.
                                 Net Sensible Capacity               0.4
                                  >=65 kBtu/h and <240
                                  kBtu/h.
                                 Net Sensible Capacity               0.5
                                  >=240 kBtu/h and <769
                                  kBtu/h.
                                 Horizontal and Up-flow              0.0
                                  Non-ducted.
                                 Down-flow..............             0.2
------------------------------------------------------------------------

    DOE is considering the test procedures and the ESP levels of AHRI 
1360-2016, but seeks input on the significant difference in the ESP 
values of the different test standards. Additionally, AHRI 1360-2016 
does not include minimum ESP requirements for ceiling-mounted units. 
AHRI-1360-2016 also made very significant changes to the ESPs for up-
flow ducted and down-flow configurations compared to ASHRAE 127-2012. 
DOE received no data or information from ASHRAE indicating the 
rationale for the changes or why lower static pressures are more 
representative of field performance. Thus, DOE is particularly 
interested in any information regarding the static pressures that are 
likely representative of all CRACs.
    Issue CRAC-18: DOE requests comment on whether the ESP levels 
required by AHRI 1360-2016 are representative of field operation for 
floor-mounted CRACs.
    Issue CRAC-19: DOE requests information on whether the ESP levels 
required by ASHRAE 127-2012 are representative of field operation for 
ceiling-mounted CRACs and for other non-floor-mounted CRAC 
configurations, and if not, what a representative minimum ESP would be.
    DOE's review of CRAC installation manuals suggests that some up-
flow units are installed with a plenum box that redirects the airflow 
from the upwards direction to the front or rear.
    Issue CRAC-20: DOE requests comment on the percentage of up-flow 
CRAC installations in which a plenum box that redirects air from the 
upward direction to the front or rear would be attached, and whether 
non-ducted units are tested with or without this plenum.
    DOE identified several models of air-cooled CRACs that have an 
indoor condenser and, therefore, may require ducting of condenser air. 
Neither AHRI 1360-2016 nor ASHRAE 127-2013 address the possibility of 
condenser ducting, and accordingly, would call for testing such CRACs 
like others in free-inlet and free-discharge mode. However, this might 
not be representative of field operation. The condenser fan for a CRAC 
with a ducted condenser has to overcome the additional pressure drop of 
the ducts; thus, imposing a minimum ESP requirement for testing may 
better reflect field operating conditions than testing the unit with 
free air inlet and discharge. However, this could require attaching an 
apparatus to allow adjustment of ESP, which would add to test burden. 
Alternatively, if a well-defined air duct set-up for indoor condensers 
could be developed (e.g., specific length and cross-sectional 
dimensions for the inlet and/or outlet air duct), a standardized 
airflow resistance could be imposed without requiring a similar 
connection and adjustment of the airflow and measurement apparatus as 
used for measurement of indoor airflow, which could significantly 
reduce test burden.
    Issue CRAC-21: DOE seeks comment on how to set up the condenser air 
flow when testing CRACs manufactured with condenser air inlet and 
outlet connections and high-static condenser fans, which indicate that 
such units can be installed indoors with the condenser air ducted to 
and from the outdoors. Additionally, DOE requests comment on whether 
some CRACs can be installed with or without condenser ducting, and if 
so, how often these units are typically installed with condenser 
ducting. DOE also seeks comment on whether certain CRAC configurations 
are more likely to be installed with condenser ducting.
d. Setting Indoor Airflow
    DOE currently requires manufacturers to certify the indoor airflow 
for CRACs. However, DOE's test procedure and industry test standards do 
not impose tolerances on achieving the certified airflow and/or the 
minimum ESP during testing. The performance of any air conditioner can 
be significantly affected by operation with indoor airflow that is very 
different from the intended airflow.
    For ACUACs with capacity >=65,000 Btu/h, DOE established a 
requirement that the full-load indoor airflow rate must be within 
3 percent of the certified airflow. 80 FR 79655, 79671 
(Dec. 23, 2015; ``December 2015 CUAC TP final rule''). Tolerance for 
ESP in this test is -0.00/+0.05 in. w.c. In contrast, for consumer 
central air conditioners and heat pumps (CAC/HPs), the method for 
setting indoor air volume rate for ducted units without variable-speed 
constant-air-volume-rate indoor fans is a multi-step process that 
addresses the discrete-step fan speed control of these units. In this 
method, (a) the air volume rate during testing may not be higher than 
the certified air volume rate, but may be 10 percent less, and (b) the 
ESP during testing may not be lower than the minimum specified ESP, but 
may be higher than the minimum if this is required to avoid having the 
air volume rate overshoot its certified value. 81 FR 36992, 37026 (June 
8, 2016; ``June 2016 CAC TP final rule'').
    Issue CRAC-22: DOE seeks information on how certified airflow is 
achieved in laboratory testing of CRACs, both with indoor blowers that 
are continuously variable and for indoor blowers that are adjustable in 
discrete steps. DOE also seeks comments on whether the tolerances for 
setting airflow of commercial CUACs or of CAC/HPs are appropriate for 
CRACs, and what tolerances would be appropriate for airflow and ESP.
e. Refrigerant Charging Instruction
    Neither the ASHRAE nor the AHRI testing standards for CRACs include 
specific instructions for refrigerant charging. The June 2016 CAC TP 
final rule provides a comprehensive approach for charging intended to 
improve test reproducibility. The approach indicates which set of 
installation instructions to use for charging, explains what to do if 
there are no instructions, indicates that target values of parameters 
are the centers of the ranges allowed by installation

[[Page 34435]]

instructions, and specifies tolerances for the measured values. 81 FR 
36992, 37030-37031. An approach that details methods such as these 
could improve the CRAC test method.
    Issue CRAC-23: DOE requests comments on what refrigerant charging 
requirements should be considered to establish reproducible test 
results for CRACs, and whether the approach developed for CAC/HP 
products may be appropriate. Also, DOE seeks comments on the typical 
operating conditions at which the unit is charged in the field and/or 
what conditions should be used to set refrigerant charge for testing 
purposes.
    Issue CRAC-24: DOE requests comments on any other issues related to 
the adoption of AHRI 1360-2016 as the test procedure for CRACs.

B. Test Procedure for Dedicated Outdoor Air Systems

    DOASes appear to meet the EPCA definition for ``commercial package 
air conditioning and heating equipment,'' \10\ and could be considered 
as a category of that covered equipment. (42 U.S.C. 6311(8)(A)) 
However, DOE has tentatively concluded that if DOASes are a category of 
``commercial package air conditioning and heating equipment,'' there 
are no existing DOE test procedures or energy conservation standards 
for that category of commercial package air conditioning and heating 
equipment. Specifically, DOE does not believe that DOAS are among the 
commercial ``central air conditioners and central air conditioning heat 
pumps'' for which EPCA originally established standards (42 U.S.C. 
6313(a)(1)-(2), (7)-(9)), and for which the current test procedure and 
standards are codified in Table 1 to 10 CFR 431.96 and Tables 1-4 of 10 
CFR 431.97 (as air conditioners and heat pumps).
---------------------------------------------------------------------------

    \10\ Under the statute, ``commercial package air conditioning 
and heating equipment'' means air-cooled, water-cooled, 
evaporatively-cooled, or water-source (not including ground-water-
source) electrically operated, unitary central air conditioners and 
central air conditioning heat pumps for commercial application.
---------------------------------------------------------------------------

    Neither EPCA nor DOE defines commercial ``central air conditioners 
and central air conditioning heat pumps.'' DOASes operate similarly to 
commercial central air conditioners and central air conditioning heat 
pumps, in that they provide space conditioning using a refrigeration 
cycle consisting of a compressor, condenser, expansion valve, and 
evaporator. However, DOASes are designed to provide 100 percent outdoor 
air to the conditioned space, while outdoor air makes up only a small 
portion of the total airflow for typical commercial air conditioners, 
usually less than 50 percent. When operating in humid conditions, the 
dehumidification load is a much larger percentage of total cooling load 
for a DOAS than for a typical commercial air conditioner. Additionally, 
compared to a typical commercial air conditioner, the amount of total 
cooling (both sensible and latent) is much greater per pound of air for 
a DOAS at design conditions (i.e., the warmest/most humid expected 
summer conditions), and a DOAS is designed to accommodate greater 
variation in entering air temperature and humidity. DOASes are 
typically installed in addition to a primary cooling system (e.g., 
CUAC, VRF, chilled water system, water-source heat pumps)--the DOAS 
conditions the outdoor ventilation air, while the primary system 
provides cooling to balance building shell and interior loads and solar 
heat gain. DOE is considering whether there is a need for definitions 
of ``commercial central air conditioners and central air conditioning 
heat pumps'' and ``dedicated outdoor air systems'' to clarify this 
distinction. If DOE determines this necessary, it would do so through a 
future rulemaking proceeding.
    ASHRAE 90.1-2016 created separate equipment classes for DOAS units 
and set minimum efficiency levels using the integrated seasonal 
moisture removal efficiency (ISMRE) metric for all DOAS classes and the 
integrated seasonal coefficient of performance (ISCOP) metric for air-
source heat pump and water-source heat pump DOAS classes. Both metrics 
are measured in accordance with AHRI Standard 920-2015, ``Performance 
Rating of DX-Dedicated Outdoor Air System Units'' (AHRI 920-2015). AHRI 
920-2015 references ASHRAE Standard 198-2013, ``Method of Test for 
Rating DX-Dedicated Outdoor Air Systems for Moisture Removal Capacity 
and Moisture Removal Efficiency'' (ASHRAE 198-2013), as the method of 
test for DOAS units.
    DOE must adopt the industry standard designated by ASHRAE 90.1 
unless it is not consistent with EPCA requirements. Accordingly, DOE is 
considering the test methods of AHRI 920-2015 and ASHRAE 198-2013, but 
may consider modifications of these test methods if necessary to 
fulfill the EPCA requirements. In the following sections, DOE reviews 
potential definitions and efficiency metrics for DOAS, as well as 
questions regarding the test method in the industry standards.
1. Definition
    As stated previously, DOE is considering how to define ``dedicated 
outdoor air system.'' Both AHRI 920-2015 and ASHRAE 198-2013 include 
definitions for DOAS. DOE may adopt one of these definitions, but it 
may also adjust the definition to assure that it is clear and complete. 
The following sections address different aspects of the definitions 
provided in the industry test standards.
a. Air Intake Source and Dehumidification Capability
    Both AHRI 920-2015 and ASHRAE 198-2013 define a DOAS as a product 
that dehumidifies 100-percent outdoor air to a low dew point. However, 
section 6.6 of ASHRAE 198-2013 provides requirements for dampers not 
used for introducing outdoor air, suggesting that some DOAS units take 
in some percentage of return air. Accordingly, DOE has identified 
models from multiple manufacturers that are advertised as DOASes, but 
which incorporate a damper-controlled return air inlet that allows 
return air to be mixed with outdoor air.
    CUACs also often incorporate a damper to mix return air and outdoor 
air. Additionally, CUACs also can dehumidify 100-percent outdoor air, 
although generally not to a dew point as low as DOASes. Hence, DOE is 
concerned that the dehumidification capability and/or the range of 
percentage of return air flow may have to be quantified to distinguish 
DOASes and CUACs.
    Issue DOAS-1: DOE requests information on the range of the maximum 
percentage of return air intake relative to total air flow of DOAS 
models in order to determine whether the maximum return air percentage 
is an important DOAS distinguishing feature.
    Issue DOAS-2: DOE requests comment on the differences in 
dehumidification capabilities of CUACs and DOASes when operating with 
100-percent outdoor air. Specifically, DOE seeks comment on whether a 
difference can be quantified to be a clear differentiating feature of 
DOASes--for example, can a specific dew point criterion for a given set 
of outdoor air conditions be established that can be achieved by any 
DOAS, but that no conventional CUAC can achieve?
b. Reheat
    DOE is interested in determining how the ability to reheat 
dehumidified air should be incorporated into the definition of a DOAS. 
The AHRI 920-2015 definition requires that a DOAS

[[Page 34436]]

include reheat ``capable of controlling the supply dry-bulb temperature 
of the dehumidified air to the designed supply air temperature,'' 
whereas the ASHRAE 198-2013 definition indicates only that DOASes may 
have this functionality. The ASHRAE 198-2013 definition indicates that 
the DOAS might also have a supplemental heat system ``for use when 
outdoor air requires heating beyond the capability of the refrigeration 
system and/or other heat transfer apparatus.'' Supplemental heating is 
also mentioned in the note below the AHRI 920-2015 definition.
    Issue DOAS-3: DOE requests comment on whether and how reheating 
functionality should be included in the DOAS definition. If reheat 
should be required for a unit to be considered a DOAS, DOE requests 
comment on whether a minimum reheat capacity should be specified in the 
definition. DOE also requests information to clarify the difference 
between a reheat system and a supplementary heat system in a DOAS--for 
example, if reheat is required for a DOAS, can it be a supplementary 
reheat system (i.e., one that uses a heat source other than warm 
refrigerant or heat recovered from the return air)?
2. Energy Efficiency Descriptors
a. Dehumidification Metric
    ISMRE is a seasonal efficiency metric calculated based on moisture 
removal efficiency (MRE) at four different dehumidification rating 
conditions. The weighted values are derived from bin hour data (i.e., 
temperature/humidity data for a selection of representative cities 
indicating the number of hours of occurrence of each ``bin'' 
representing a defined range of temperature and humidity) to represent 
seasonal operation. MRE is calculated as moisture removal capacity 
(MRC) divided by the total energy input, as described in ASHRAE 198-
2013 section 10.6.
    DOE is seeking clarification on the calculation procedure for 
ISMRE. ASHRAE 198-2013 indicates measuring MRE twice for each test 
condition, once with reheat on and once with reheat off. AHRI 920-2015 
does not specify which of these values of MRE is used in the 
calculation of ISMRE. AHRI 920-2015 section 6.1.3.1 calls for a 
supplemental heat penalty if the supply air temperature is less than 70 
[deg]F, but the incorporation of this penalty into the MRE equation is 
not clearly described. It is also not clear whether the ASHRAE 198-2013 
test method considers this penalty. Finally, the equation for the 
supplemental heat penalty in AHRI 920-2015 appears to be missing the 
supply air volume flow rate as a factor.
    Issue DOAS-4: DOE requests information to clarify the calculation 
procedure for ISMRE. Specifically, DOE requests input on which 
dehumidification test MRE should be used (and why), how and when the 
supplementary heat penalty is applied, and the basis for the 
supplementary heat equation.
    While the primary functions of DOASes are to provide ventilation 
and to dehumidify the outdoor air, the units also provide sensible 
cooling to the supplied air stream. However, the sensible cooling 
provided by the unit is not accounted for as part of the MRE or ISMRE 
efficiency metric. DOE is aware that the total sensible cooling 
provided may be significantly less than the latent cooling associated 
with removal of moisture--for example, conditions C and D of Tables 2 
and 3 of AHRI 1360-2016 specify inlet air conditions already cooler 
than the target 70 [deg]F supply temperature--but sensible cooling may 
be important enough to consider for the warmer test conditions.
    Issue DOAS-5: DOE requests comment on whether the DOAS efficiency 
metric should also account for sensible cooling provided for 
ventilation air during the cooling/dehumidification season.
    The ISMRE metric is based on testing at four different operating 
conditions, involving specification of both dry bulb and wet bulb 
outdoor temperature. A weighted average of the MRE measurements 
determined for the four conditions is calculated to obtain ISMRE. DOE 
test procedures must provide a measurement that is representative of an 
average use cycle for the tested equipment. (42 U.S.C. 6314(a)(2)) 
Among the considerations that might be relevant in defining the test 
conditions and weighting factors is the fact that ventilation air must 
be delivered to occupied spaces during occupied hours, which would put 
more emphasis on daytime hours for development of the metric.
    Issue DOAS-6: DOE seeks information about analysis of climate data 
relevant to the development of the ISMRE test conditions and weighting 
factors in order to confirm that the metric provides a measurement that 
is representative of an average use cycle for DOAS equipment.
b. Heating Metric
    ISCOP is a seasonal energy efficiency descriptor calculated as the 
weighted average of heating COP determined for two different heating 
rating conditions. DOE test procedures must provide a measurement that 
is representative of an average use cycle for the tested equipment. (42 
U.S.C. 6314(a)(2)) Section 6.4 of AHRI 920-2015 indicates that the 
weighting factors for the COPs are derived from bin hour data to 
represent a full year of operation.
    Issue DOAS-7: DOE seeks information about analysis of climate data 
relevant to the development of the ISCOP test conditions and weighting 
factors in order to allow confirmation that the metric provides a 
measurement that is representative of an average use cycle for DOAS 
heat pump equipment.
    ``Integrated seasonal coefficient of performance,'' as defined in 
AHRI 920-2015, is an energy efficiency metric for water-source heat 
pumps. However, DOE notes that ASHRAE 90.1-2016 includes ISCOP minimum 
efficiency levels for air-source heat pumps (heating mode) in Table 
6.8.1-16 in addition to water-source heat pumps. ASHRAE 198-2013 
section 10.9 claims that its equations for calculating COP are for 
water-source heat pumps, although the COP definition in ASHRAE 198-2013 
does not exclude air-source heat pumps, and the equations should apply 
equally well for air-source heat pumps. Finally, DOE notes that tests 
conducted at 35 [deg]F dry bulb temperature for consumer central air 
conditioning heat pumps (which are air-source) consider the impacts of 
defrosting of the outdoor coil in the energy use measurement (see 
section 3.9 of 10 CFR part 430, subpart B, appendix M), while defrost 
is not discussed at all in ASHRAE 198-2013. Defrost has a real impact 
on efficiency because of energy use associated with defrost and because 
a system cannot continue to provide heating during defrost operation, 
thereby reducing time-averaged capacity. Hence, consideration of 
defrost could provide a more field-representative measurement of 
performance.
    Issue DOAS-8: DOE seeks input on the calculation procedure for the 
COP of air-source heat pump DOASes, including whether testing for test 
condition E of AHRI 920-2015 Table 2 (35 [deg]F dry bulb/29 [deg]F wet 
bulb) should consider energy use associated with defrost.
    The COP equation of ASHRAE 198-2013 section 10.9 uses the term 
qhp to represent the heating capacity in the COP 
calculation. This term does not appear in the nomenclature section, but 
the subscript ``hp'' suggests that this includes only heat provided by 
the heat pumping function of the DOAS unit. However, the equation 
defining qhp is based on supply air temperature, suggesting 
that any of the possible

[[Page 34437]]

additional methods for providing heat (e.g., supplemental heat, heat 
recovery) may contribute to qhp and thereby boost COP by 
increasing the numerator of the COP equation. The COP equation includes 
only electric power input in the denominator and does not include 
energy use that might be associated with fuel-fired supplemental heat. 
In addition, the supplemental heat penalty of AHRI 920-2015 section 
6.1.3.1, which the section states applies to the heating test 
conditions as well as the dehumidification test conditions, seems to 
penalize the COP calculation excessively, because it does not indicate 
that the additional heating should be added to the qhp of 
the COP equation.
    Issue DOAS-9: DOE seeks input on the calculation for COP and how 
the supplemental heat penalty is included. DOE also seeks input on how 
the heating capacity and power/fuel consumption of various supplemental 
heating sources are accounted for as part of the COP equation and how 
DOAS manufacturers incorporate the impacts of these sources in their 
ISCOP calculations.
3. Test Method
a. Airflow
i. Supply Airflow
    Section 5.2.2 of AHRI 920-2015 specifies instructions regarding 
supply airflow rate. Section 5.2.2.1 of that industry standard requires 
either use of the supply airflow that occurs at the minimum external 
static pressure of Table 4 or a manufacturer-specified lower leaving 
airflow rate that occurs with higher external static pressure. Section 
5.2.2.3 of that industry standard further requires that the 
manufacturer specify a single airflow for all tests. However, many DOAS 
systems can operate over a range of airflow rates, and DOE expects that 
their indoor fans can be set up with a range of speeds to accommodate 
the airflow range and the variation in duct length in field 
installations. Further, some DOAS systems are employed for demand 
ventilation use, for which reduced airflow will likely be required for 
a significant portion of the unit's use. Such systems also are likely 
to have variable-speed indoor fans, whose speed settings for the test 
may also have to be defined clearly. The performance of the DOAS may 
vary significantly from the low end to the high end of the rated 
installation airflow range. DOE is concerned that the selected airflow 
rate may not provide a representative indication of field use, and that 
there may not be sufficient clarity regarding how to set up for testing 
a unit with multiple indoor fan speed options.
    Issue DOAS-10: DOE requests input on the appropriate selection of 
the supply airflow rate for testing units that can operate with a range 
of airflow rates. DOE requests information regarding how manufacturers 
select the airflow rate for testing and any data demonstrating the 
variation of DOAS unit performance over a range of installed airflow 
rates.
    Issue DOAS-11: DOE requests comment on whether it would be 
appropriate to develop a test that includes part-load (reduced 
ventilation air) test points to quantify the efficiency benefit of 
demand-controlled ventilation for DOASes that are capable of operating 
with this control.
ii. Return Airflow
    For testing DOAS units with energy recovery,\11\ Tables 2 and 3 in 
AHRI 920-2015 provide return airflow temperature conditions and 
indicate that they apply to units with energy recovery at balanced 
airflow (i.e., tested with supply airflow equal to exhaust airflow). It 
is unclear what airflow streams should be balanced, how to determine if 
they are balanced, and within what tolerances they should be balanced. 
DOE is considering clarifying the return airflow set-up procedures.
---------------------------------------------------------------------------

    \11\ DOAS units with energy recovery take in and discharge 
exhaust air, using a device such as an energy recovery wheel that 
can transfer heat and moisture from the exhaust air to the outdoor 
air, thereby preconditioning the outdoor air and reducing the load 
required to cool, dehumidify, or heat the air to the desired supply 
conditions.
---------------------------------------------------------------------------

    Issue DOAS-12: DOE requests comment regarding how manufacturers who 
have tested heat recovery DOAS set up return airflow for testing DOAS 
units with energy recovery as prescribed by the AHRI 920-2015 test 
standard. Further, DOE requests comment on whether balanced airflow is 
representative of field installation, and what ESP levels should be set 
up for the return airflow.
iii. Exhaust Air Transfer Ratio
    Exhaust air transfer ratio (EATR) is an indicator of the amount of 
air that leaks from the return air side of the energy recovery wheel to 
the supply air side. Such leakage could increase the apparent 
dehumidification provided by a DOAS unit because the return air is less 
humid than the outdoor air into which the return air could leak--thus, 
high leakage could boost the ISMRE rating without providing any real 
benefit. However, DOE recognizes that such leakage may be low enough in 
most energy recovery wheels that the EATR measurement would represent 
an unnecessary addition to test burden.
    Issue DOAS-13: DOE seeks comments on whether EATR should be 
included in DOE's test procedure for DOAS, and, if so, how it should be 
used in determining DOAS ratings. DOE requests information on the range 
of return air leakage typical for energy recovery wheels used in 
DOASes.
b. Liquid Flow
i. Water Flow Rate for Water-Source DOASes
    Neither AHRI 920-2015 nor ASHRAE 198-2013 provides requirements for 
outlet water temperature or water flow rate for water-cooled units. 
Instead, AHRI 920-2015 specifies a standard rating test water entering 
temperature in Table 2 and requires in section 6.1.4.3 that the 
manufacturer specify a water flow rate, unless it is controlled 
automatically by the device. However, ANSI/AHRI 340/360-2007 with 
addenda 1 and 2, ``Standard for Performance Rating of Commercial and 
Industrial Unitary Air-Conditioning and Heat Pump Equipment'' (AHRI 
340/360-2007) and ANSI/AHRI 210/240-2008 with addenda 1 and 2, 
``Standard for Performance Rating of Unitary Air-Conditioning & Air-
Source Heat Pump Equipment'' (AHRI 210/240-2008), which cover 
performance rating for water-cooled commercial air-conditioning 
equipment, employ a different method. Both of these standards specify 
water inlet and outlet temperatures for the standard rating conditions, 
rather than relying on manufacturers to determine water flow rate. 
Further, both standards specify that the full-load water flow rate 
determined for the standard rating conditions should also be used for 
IEER part-load rating conditions. DOE believes that these approaches to 
testing reflect the typical design temperature differential for cooling 
towers serving water-cooled equipment, and a very common approach for 
control of condenser water pumps, and hence it is not clear why the 
same approach would not be adopted for water-cooled DOAS.
    Issue DOAS-14: DOE requests information on how condenser water flow 
rates are set in the field and how they are controlled at part load. 
DOE also requests comment on whether the provisions of section 6.1.4.3 
of AHRI 920-2015 provide sufficient guidance regarding how to set up 
water flow for DOASes with automatic water flow control systems.

[[Page 34438]]

ii. Energy Consumption of Pumps and Fans for Water-Source Condensers
    AHRI 920-2015 offers Equation 1 for calculating the total pump 
effect (PE), an estimate of the energy consumption of non-integral 
water pumps (i.e., pumps that are not part of the DOAS unit and whose 
power consumption would, therefore, not already be part of the measured 
power). Section 6.1.3 of AHRI 920-2015 implies that this calculation 
applies solely to water pumps serving refrigerant-to-liquid heat 
recovery devices--no indication is given whether the equation also 
applies for pumps serving water-source or water-cooled condensers--
although it is possible that the term ``refrigerant-to-liquid heat 
recovery device'' refers to the condenser of a water-source heat pump 
DOAS. Further, neither AHRI 920-2015 nor ASHRAE 198-2013 mention 
accounting for the energy consumption of heat recovery fans for water 
loops or water-cooled condensers. In contrast, AHRI 340/360-2007, which 
is used for rating water-cooled CUACs, provides in section 6.1 a power 
consumption allowance for both the cooling tower fan and the 
circulating water pump.
    Issue DOAS-15: DOE requests confirmation that the ``refrigerant-to-
liquid heat recovery device'' cited in section 6.1.3 of AHRI 920-2015 
is intended to include heat exchangers used for rejection of 
refrigerant circuit heat during the dehumidification cycle, and comment 
on whether Equation 1 of this section for estimating the energy usage 
of water pumps is appropriate for DOASes with water-cooled condensers.
    Issue DOAS-16: DOE requests comment on accounting for the energy 
consumption for heat-rejection fans employed in water-cooled or water-
loop DOASes.
iii. Energy Consumption for the Chiller System for Liquid-Cooled DOAS 
Using Chilled Water for Condenser Cooling
    One of the options for testing water-cooled DOAS is to provide 
condenser cooling water at 45 [deg]F, replicating operation in which 
condenser cooling is provided by a chilled water system. When operating 
in this fashion, the chilled water system must expend additional energy 
to maintain the 45 [deg]F supply water condition--it is not clear that 
this energy is considered in the ISMRE metric. Without this energy use 
contribution, the ratings for such equipment would appear to be have an 
unfair advantage in comparison to the ratings for DOAS rated using 
cooling tower water. The minimum efficiency levels in ASHRAE 90.1-2016 
for both equipment classes certainly do reflect this advantage, with 
the ISMRE levels being 4.9 for water-cooled DOAS using cooling tower 
water and 6.0 for those using chilled water. Although the 6.0 ISMRE 
level for chilled-water-cooled operation appears to be much more 
efficient, it does not include the energy use associated with the 
chiller system required to deliver the chilled water at the specified 
45 [deg]F.
    Issue DOAS-17: DOE requests comment on whether energy contributions 
should be considered for the chiller system of a water-cooled DOAS that 
is rated for use with chilled water for condenser cooling. If so, DOE 
requests comment on the appropriate representative value for the 
chiller system energy contribution.
c. Test Conditions
i. Supply Air Conditions
    AHRI 920-2015 includes a requirement of minimum supply air 
temperature of 70.0 [deg]F for all standard rating conditions and a 
maximum dew-point temperature of 55.0 [deg]F for standard rating 
conditions for dehumidification. ASHRAE 198-2013 requires a supply air 
temperature of 75.2 [deg]F or as close to this value as the controls 
will allow during testing.
    Issue DOAS-18: DOE requests comment or clarification related to the 
difference in target supply air temperature requirements between AHRI 
920-2015 and ASHRAE 198-2013. DOE requests comments as to the 
appropriate supply air temperature for use in the DOE test procedure 
for DOAS.
ii. Cooling Tower and Closed-Loop Water-Source Differences
    The water entering temperature test conditions in AHRI 920-2015 
Table 2 for testing water-cooled DOAS differ from the water-source heat 
pump inlet temperature conditions specified in Table 3 for water-source 
heat pump DOAS tested using the ``water source'' test conditions. 
Water-source water loops generally provide heat rejection using cooling 
towers. Hence, it is unclear that there is much value in having 
incremental differences for the dehumidification test conditions for 
these types of equipment.
    Issue DOAS-19: DOE requests comment on the need for different 
dehumidification test conditions for a water-cooled DOAS as compared to 
a water-source heat pump DOAS using the closed water loop test 
conditions.
iii. Water-Cooled Condensing and Ground-Source Equipment
    Tables 2 and 3 in AHRI 920-2015 include two categories for water-
cooled DOASes and three categories for heat pump DOASes. The test 
standard specifies a different set of inlet water/fluid temperatures 
for each category. The different categories and their associated rating 
conditions could require some DOASes to be tested separately as 
different basic models. For example, water-cooled DOASes that can be 
operated with either chilled water or condenser water would have to be 
tested and rated in both configurations. Similarly, ASHRAE 90.1-2016 
includes three rating subcategories for water-source heat pump DOASes--
ground-source, closed loop; ground-water-source; and water-source. The 
EPCA definition for ``commercial package air conditioning and heating 
equipment'' does not include ground-water-source products (42 U.S.C. 
6311(8)(A)), but ground-source and water-source heat pumps would be 
covered by DOE with two different rating conditions. DOE is considering 
whether such dual rating and certification is appropriate.
    Issue DOAS-20: DOE requests comment on whether condenser cooling by 
cooling tower water versus chilled water demarcates two distinct 
equipment categories, or whether a single piece of equipment could 
operate in both applications. Likewise, DOE requests comments on 
whether ground-source closed-loop DOASes represent equipment that is 
distinct from water-source models. For each of these pairs of 
categories, if they do only represent different test conditions for the 
same equipment, DOE requests input on whether testing and rating 
equipment for two applications is preferable, or whether a single set 
of test conditions and rating would be sufficient.
    Section 2 of ASHRAE 198-2013 specifically excludes DOASes with 
water coils that are supplied by a chiller located outside of the unit. 
However, AHRI 920-2015 Table 2 includes operating conditions for which 
a water-cooled condenser is supplied with chilled water, and ASHRAE 
90.1-2016 established standard levels for DOASes that operate with 
chilled water as the condenser cooling fluid.
    Issue DOAS-21: DOE seeks confirmation that the ASHRAE 198-2013 
chiller exclusion applies to cooling coils rather than condenser coils.
d. Tolerances
    Rating test tolerances for DOASes are listed in Table 1 of ASHRAE 
198-2013. This table specifies tolerances for

[[Page 34439]]

airflow rate and outdoor and return air dry-bulb and wet-bulb 
temperatures, but does not list any tolerances for supply airflow 
temperature. However, tolerances for supply temperature are included in 
other relevant test procedures, such as in Table 2b of ASHRAE 37-2009. 
DOE is considering adding operating tolerances for supply airflow dry-
bulb and wet-bulb temperatures to the test procedure.
    In addition, the operating and condition tolerances listed for 
airflow rate are 5 percent in Table 1 of ASHRAE 198-2013, which is 
looser than the airflow rate tolerance adopted for CUACs. In fact, DOE 
proposed to apply  5 percent condition tolerance on cooling 
full-load indoor airflow rate for CUACs (see 80 FR 46870, 46873 (August 
6, 2015; ``August 2015 CUAC TP NOPR'')), but received several comments 
suggesting that a 5-percent tolerance would result in too much 
variation in the measurement of EER and cooling capacity. Therefore, 
DOE adopted a 3-percent tolerance in the December 2015 CUAC TP final 
rule, as suggested by stakeholder comments. 80 FR 79655, 79659-79660 
(Dec. 23, 2015). DOE has concerns that the 5-percent condition 
tolerance on airflow in ASHRAE 198-2013 may result in too much test 
variability for DOASes.
    Issue DOAS-22: DOE requests comment on whether to adopt the 
operating condition tolerances for supply air temperature listed in 
Table 2b of ASHRAE 37-2009 for DOAS testing. DOE also seeks input 
regarding whether a 5-percent airflow tolerance is acceptable. Further, 
DOE requests any information or data regarding tolerances for any other 
test operating parameters. Specifically, DOE requests comment on 
whether there are any parameters whose tolerances should be tightened 
or relaxed to ensure limited variation and high certainty for the ISMRE 
and ISCOP results with appropriate test burden.
e. Capacity Measurement
    The air enthalpy method, as specified in section 6.1 of ASHRAE 198-
2013, is the only capacity measurement method required in the test 
procedure. There is no mention of a secondary test method for capacity 
measurement verification in AHRI 920-2015 or ASHRAE 198-2013. In 
contrast, secondary capacity measurements are generally required for 
testing of air conditioners with capacity less than 135,000 Btu/h (see, 
e.g., ASHRAE 37-2009 section 7.2.1). Measurement of air conditioning 
capacity is based on the measurements of air flow rate, temperature, 
and humidity, which can have an uncertainty range associated with them 
that makes use of a secondary method to check the primary method 
worthwhile to ensure accuracy. DOE is considering whether secondary 
measurements should be required for DOAS testing in order to ensure 
accuracy of measurements. Section 7 of ASHRAE 37-2009 describes several 
different test methods applicable to testing of unitary air-
conditioning and heat pump equipment. The cooling condensate method may 
be particularly relevant as a secondary test method for measuring the 
dehumidification performance of a DOAS.
    Issue DOAS-23: DOE requests comment on the need for a secondary 
test method requirement for DOAS testing. DOE seeks input regarding 
potentially applicable secondary test methods for the dehumidification 
and heating tests, and whether a secondary test method requirement and/
or the secondary method allowed by the test procedure should depend on 
cooling (or dehumidification) capacity or airflow rate. DOE is also 
interested in detailed information on the test burden that would be 
associated with a secondary test method.
f. Test Set-Up
    Figures 1 and 2 of ASHRAE 198-2013 show the typical test set-up for 
DOASes with and without energy recovery. The figures show airflow and 
condition measuring devices at both the inlet and the outlet of each 
airstream, but it is not clear in the test standard that both airflow 
measurement devices are required. DOE notes that typically only one 
airflow measuring device, which measures airflow downstream of the 
unit, is installed in air-conditioner and heat pump testing. ASHRAE 
198-2013 provides no description of the use of two sets of airflow 
measurements per airstream, for example, for a tolerance check of the 
airflow calculation or determination of leakage between air streams 
when testing a DOAS with energy recovery.
    Issue DOAS-24: DOE requests comments on whether it is beneficial or 
necessary to use two airflow measuring devices per airstream when 
testing DOAS equipment.
    Section 6.6 of ASHRAE 198-2013, which deals with Unit Preparation, 
describes that any energy recovery devices that include a purge or 
other function that transfers air from supply or exhaust shall be 
disabled to set at zero position.
    Issue DOAS-25: DOE seeks additional information on the purge 
function mentioned in section 6.6 of ASHRAE 198-2013. Specifically, are 
all purge devices adjustable to zero purge, and is it always clear how 
to set them to zero purge? Also, DOE requests feedback on whether it is 
appropriate to set purge to zero or whether it would be more 
appropriate to set purge to its highest setting or to some standard 
setting?
    Issue DOAS-26: DOE requests any additional comments related to the 
adoption of AHRI 920-2015 as the test procedure for DOAS.

C. Test Procedure for Air-Cooled, Water-Cooled, and Evaporatively-
Cooled Equipment

    DOE's test procedures for ACUACs, ECUACs, and WCUACs are codified 
at 10 CFR 431.96. Table 1 at 10 CFR 431.96 incorporates by reference 
AHRI 340/360-2007 for WCUACs and ECUACs with cooling capacity >=65,000 
Btu/h, excluding section 6.3. For ACUACs with cooling capacity >=65,000 
Btu/h, Table 1 refers to appendix A to subpart F of part 431, which 
references sections 3, 4, and 6 of AHRI 340/360-2007, excluding section 
6.3. Paragraphs (c) and (e) of 10 CFR 431.96 and appendix A to subpart 
F of part 431 contain additional test procedure provisions for WCUACs/
ECUACs and ACUACs, respectively. ASHRAE 90.1-2016 updated its test 
procedure reference for this equipment to AHRI 340/360-2015, 
``Performance Rating of Commercial and Industrial Unitary Air-
conditioning and Heat Pump Equipment'' (AHRI 340/360-2015), which has 
triggered the requirement for DOE to review its test procedures for 
this equipment.
    At 10 CFR 431.95 and Table 1 of 10 CFR 431.96, DOE incorporates by 
reference AHRI 210/240-2008 for testing of ACUACs, WCUACs, and ECUACs 
with cooling capacity <65,000 Btu/h, excluding section 6.5. While 
ASHRAE 90.1-2016 did not update its test procedure reference for this 
equipment, AHRI has made public a draft update of AHRI 210/240 (AHRI 
210/240-2015-Draft) that was submitted to the docket for the test 
procedure for CAC/HPs on August 14, 2015 (Docket No. EERE-2009-BT-TP-
0004). For this reason, and to comply with the statutory requirement to 
review test procedures at least once every seven years (42 U.S.C. 
6314(a)(1)(A)), DOE is reviewing its test procedures for ECUACs and 
WCUACs with cooling capacity less than 65,000 Btu/h in this RFI. DOE 
will consider ACUACs with a cooling capacity less than 65,000 Btu/h in 
a separate RFI.
    The following sections explore aligning the ECUAC and WCUAC metric 
with that of ACUAC, review updates in AHRI 340/360-2015 to determine if 
adopting that industry standard would meet EPCA requirements, and 
explore

[[Page 34440]]

additional test procedure issues related to the subject equipment.
1. Energy Efficiency Descriptor
    DOE's current energy efficiency descriptor for ECUACs and WCUACs is 
the energy efficiency ratio (EER). 10 CFR 431.96. The EER metric only 
captures performance at a single set of rating conditions with 
equipment operating at full-load, and it is calculated by dividing the 
full-load cooling capacity by the equipment power input. In contrast, 
DOE adopted integrated energy efficiency ratio (IEER) as an energy 
efficiency metric for ACUACs in the December 2015 CUAC TP final rule. 
80 FR 79655 (Dec. 23, 2015). ASHRAE 90.1-2016 also provides minimum 
efficiency IEER levels (in addition to EER levels) for ECUACs and 
WCUACs.
    AHRI 340/360-2007 includes a method for testing and calculating 
IEER for ECUACs and WCUACs. IEER is an energy efficiency descriptor 
that is calculated from test results at four sets of conditions 
including a full-load test at standard rating conditions and three 
part-load tests at different outdoor conditions for ECUACs and 
different entering water temperatures for WCUACs. IEER utilizes 
adjustment factors to account for cycling losses, when applicable, at 
part-load conditions. IEER also includes continuous indoor fan 
operation, during times when the compressor would be cycling to meet 
the required load, to account for fan operation during ventilation 
mode. After the measured efficiencies at the four test conditions are 
adjusted for cycling losses and continuous fan use, if applicable, the 
results are multiplied by weighting factors and added together to 
determine the IEER. The weighting factors used are as follows: 0.020 
for the full-load test, 0.617 for the 75-percent load test, 0.238 for 
the 50-percent load test, and 0.125 for the 25-percent load test.
    Issue CUAC-1: DOE seeks comment or data on whether the IEER part-
load conditions and IEER weighting factors are representative of the 
operation of field-installed ECUACs and WCUACs. DOE also seeks comment 
or data regarding the typical cycling losses of field-installed ECUACs 
and WCUACs.
    The Appliance Standards and Rulemaking Federal Advisory Committee 
(ASRAC) Commercial and Industrial Fans and Blowers Working Group 
developed recommendations regarding the energy conservation standards, 
test procedures, and efficiency metrics for commercial and industrial 
fans and blowers in a term sheet (Docket No. EERE-2013-BT-STD-0006-
0179), which was the culmination of a negotiated rulemaking involving 
that equipment. As part of this term sheet, Recommendation #3 discussed 
the need for DOE's test procedures and related efficiency metrics to 
properly account for the energy consumption of fans embedded in 
regulated commercial air-conditioning equipment.
    In addition, the working group agreed that in the next round of 
test procedure rulemakings, DOE should consider revising efficiency 
metrics that include energy use of supply and condenser fans to include 
the energy consumption during all relevant operating modes (e.g., 
auxiliary heating mode, ventilation mode, and part-load operation). The 
working group included ACUACs, ECUACs, and WCUACs in its list of 
regulated equipment for which fan energy use should be considered. 
(Docket No. EERE-2013-BT-STD-0006-0179 at pp. 3-4, 16)
    Consequently, DOE is considering what changes to its ACUAC, ECUAC, 
and WCUAC test procedures may more accurately represent fan energy use 
in field applications. DOE is aware that field-installed fan energy use 
will vary based on the use of the fan for ancillary functions (e.g., 
economizers, ventilation, filtration, and auxiliary heat). In order to 
properly account for fan energy use, DOE is requesting information on 
how frequently field installations use the supply fan of the CUAC for 
various ancillary functions.
    Issue CUAC-2: DOE requests information, including any available 
data, on how frequently CUAC supply fans are operated when there is no 
demand for heating or cooling (i.e., for fresh air ventilation or air 
circulation/filtration), and what the typical operating schedules or 
duty cycles are for this function. Additionally, DOE requests data or 
information regarding how frequently and what forms of primary and 
auxiliary heating are installed with CUACs and whether their operation 
is dependent on the supply fan of the CUAC. DOE requests data or 
information regarding how frequently the systems are used with 
economizers, how the economizers are integrated with the systems, and 
what control logic is typically used on the economizers. DOE also seeks 
comment and information regarding the use of the indoor supply fan of 
CUACs for any ancillary functions not mentioned above. Please 
differentiate by ACUAC, ECUAC, or WCUAC, as necessary.
    Another factor that influences fan energy use is the external 
static pressure that is required to overcome the air distribution 
system pressure drop. Both AHRI 210/240-2008 and AHRI 340/360-2007 
specify minimum external static pressures for testing based on the 
rated unit capacity of ECUACs and WCUACs. DOE is interested in ensuring 
that the external static pressures in the test procedures are 
representative of those experienced in field installations. In the 
December 2015 CUAC TP final rule, DOE summarized stakeholder comments 
regarding the possibility that external static pressures as measured in 
the field may be higher than those found in the industry test 
standards. 80 FR 79655, 79664 (Dec. 23, 2015). Based on this 
information, DOE is examining the external static pressures specified 
in the test procedures for ECUACs and WCUACs.
    Issue CUAC-3: DOE requests comment or data regarding the typical 
external static pressures in field installations of ECUACs and WCUACs 
and whether these field-installed external static pressures typically 
vary with capacity. DOE also seeks comment regarding whether the field 
applications of ECUACs and WCUACs are different from ACUACs with 
regards to the typical ducting installed on the system.
    Another issue related to fan energy is the default fan power for 
ACUACs, ECUACs, and WCUACs with a coil-only configuration (i.e., 
without an integral supply fan). Current test procedures for ACUACs, 
ECUACs, and WCUACs specify that indoor fan power of 365 Watts (W) per 
1000 standard cubic feet per minute (scfm) be added to power input for 
coil-only units and that the corresponding heat addition be subtracted 
from measured cooling. This value has been used to account for the fan 
energy use associated with coil-only units for many years, and more-
efficient motors and fans may be in use for which the current 365 W/
1000 scfm fan power value is not representative. It is also possible 
that the value is not consistent with field-typical external static 
pressures.
    Issue CUAC-4: DOE seeks comment or data on the prevalence of 
ACUACs, ECUACs, and WCUACs that are sold in coil-only configurations 
(i.e., neither with an integral supply fan, nor with a designated air 
mover such as a furnace or modular blower).
    Issue CUAC-5: DOE seeks comment or data on the typical efficiency 
or typical power use and flow of fans used with coil-only ACUACs, 
WCUACs, and ECUACs in field installations.
2. Addressing Changes to AHRI 340/360
    As noted previously, ASHRAE 90.1-2016 updated its reference from 
AHRI 340/360-2007 to AHRI 340/360-2015. The updated AHRI 340/360-2015 
includes significant changes from AHRI 340/360-2007 for ACUACs, ECUACs,

[[Page 34441]]

and WCUACs, and DOE seeks comment on those changes as discussed in this 
section. Several changes are relevant to all three categories of 
equipment, while other changes are only relevant to one or two of the 
equipment categories. Table II.2 illustrates to which equipment 
category each change is relevant. In some cases, a change may not be 
relevant to ACUACs because the change has already been adopted in the 
December 2015 CUAC TP final rule.

                                      Table II.2--AHRI 340/360-2015 Changes
----------------------------------------------------------------------------------------------------------------
                            Topic                                   ACUAC            ECUAC            WCUAC
----------------------------------------------------------------------------------------------------------------
Head Pressure Controls.......................................               X                X                X
Refrigerant Charging Requirements............................               X                X                X
Adjustment for Different Atmospheric Pressure Conditions.....               X                X                X
Measurement of Condenser Air Inlet Temperature...............               X                X   ...............
Tolerance of Tested Airflow Relative to Rated Airflow........  ...............               X                X
Vertical Separation of Indoor and Outdoor Units..............               X                X                X
Outdoor Entering Air Wet-Bulb Temperature....................  ...............               X   ...............
Single-Zone Variable-Air-Volume and Multi-Zone Variable-Air-                X                X                X
 Volume......................................................
----------------------------------------------------------------------------------------------------------------

a. Head Pressure Controls
    Condenser head pressure controls regulate the flow of refrigerant 
through the condenser and/or adjust operation of condenser fans to 
prevent condenser pressures from dropping too low during low-ambient 
operation. When employed, these controls ensure that the refrigerant 
pressure is high enough to maintain adequate flow through refrigerant 
expansion devices such as thermostatic expansion valves. AHRI 340/360-
2007 provides minimal guidance on head pressure controls, only 
mentioning in note 2 of Table 6 that the condenser airflow should be 
adjusted as required by the unit controls for head pressure control. 
AHRI 340/360-2015 states that any head pressure controls shall be left 
at the manufacturer's settings and operated in automatic mode, but 
that, if this results in unstable operation exceeding the tolerances of 
ASHRAE 37-2009, the time-averaged head pressure control test described 
in section F7 of appendix F of AHRI 340/360-2015 shall be used. This 
test requires measuring performance using two one-hour test periods, 
first after approaching the target ambient condition from warmer 
temperatures, and once after approaching from lower temperatures. 
During these tests, the looser tolerance requirements from Table 2b of 
ASHRAE 37-2009 for the ``heat portion'' of the heat with defrost test 
must be met. This issue was reviewed by DOE for ACUACs in the December 
2015 CUAC TP final rule. In that final rule, DOE clarified that head 
pressure controls must be active during the test, but DOE did not adopt 
the time-averaged head pressure control test specified in AHRI 340/360-
2015, indicating that AHRI 340/360-2015 was a draft document at the 
time and that DOE would reconsider adoption of the provisions for 
testing units with head pressure control later. 80 FR 79655, 79660 
(Dec. 23, 2015).
    Issue CUAC-6: DOE seeks information and data regarding testing of 
CUACs with head pressure control that would require the special test 
provisions described in AHRI 340/360-2015. Specifically, can such units 
be tested in compliance with the relaxed stability requirements of 
these test provisions? Do the test results accurately represent field 
use? Is the test burden associated with these tests appropriate?
b. Refrigerant Charging Requirements
    AHRI 340/360-2007 does not provide any specific guidance on setting 
the refrigerant charge of a unit.
    The DOE test procedures for ACUACs, ECUACs, and WCUACs state that 
if the manufacturer specifies a range of superheat, sub-cooling, and/or 
refrigerant pressures in the installation or operation manual, any 
value within that range may be used to determine refrigerant charge, 
unless the manufacturer clearly specifies a rating value in its 
installation or operation manual, in which case the specified value 
shall be used. 10 CFR 431.96(e)(1); section (5)(i) of appendix A to 
subpart F of part 431.
    AHRI 340/360-2015 states that equipment shall be charged with 
refrigerant at standard rating conditions (or conditions specified by 
the manufacturer in the installation instructions) in accordance with 
the manufacturer's installation instructions or label applied to the 
equipment. In contrast with the DOE test procedure, the industry test 
standard calls for the use of the average of ranges of sub-cooling or 
superheat specified in installation manuals.
    As discussed in section II.A.3.e, the June 2016 CAC TP final rule 
provides a comprehensive approach for charging that improves test 
reproducibility. The approach indicates which set of installation 
instructions to use for charging, explains what to do if there are no 
instructions, indicates that target values of parameters are the 
centers of the ranges allowed by installation instructions, and 
specifies tolerances for the measured values. 81 FR 36992, 37030-37031. 
These methods could be considered as an example for the CUAC test 
method.
    Issue CUAC-7: DOE seeks comment on whether it would be appropriate 
to adopt an approach for charging requirements for commercial CUACs 
similar or identical to the approach adopted in the June 2016 CAC TP 
final rule for residential products. DOE seeks comments regarding which 
parts of the approach should or should not be adopted, and for what 
reasons they might or might not be suitable for application to CUACs. 
DOE is also interested in receiving data that demonstrate how sensitive 
the performance of ACUACs, ECUACs, and WCUACs is relative to changes in 
the various charge indicators used for different charging methods, 
specifically the method based on sub-cooling.
c. Adjustment for Different Atmospheric Pressure Conditions
    In order to address potential differences in measured results 
conducted at different atmospheric pressure conditions, AHRI 340/360-
2015 introduced an adjustment for indoor supply fan power and 
corresponding fan heat. This adjusts the fan power based on the 
barometric pressure at the test site, multiplying the measured supply 
fan power by the square of the ratio of the measured air density 
(density of air at measured supply air temperature and humidity and 
measured atmospheric pressure) to the density of the supply air if it 
were at standard pressure (14.696 pounds per square inch). 
Consequently, the cooling capacity and efficiency are also impacted by 
this correction.
    The outdoor air mass flow rate and fan power will also vary with

[[Page 34442]]

atmospheric pressure; however, the outdoor fan speed is typically not 
adjustable, because most outdoor fans have single-speed direct-drive 
motors, and no rated outdoor air flow rate in scfm is set during the 
test for the majority of CUACs. To address the potential impact of 
barometric pressure on the outdoor fan air flow, AHRI 340/360-2015 
imposed a minimum atmospheric pressure of 13.7 pounds per square inch 
absolute (psia) for testing equipment.
    Issue CUAC-8: DOE requests test data that validate the supply fan 
power correction used in AHRI 340/360-2015. DOE is also interested in 
comments on whether the minimum atmospheric pressure of 13.7 psia will 
prevent any existing laboratories from testing equipment, and what 
burden, if any, is imposed by such a requirement. DOE also seeks any 
available test data showing the impact that variations in atmospheric 
pressure have on the performance (i.e., capacity and component power 
use) of ACUACs, ECUACs, and WCUACs.
d. Measurement of Condenser Air Inlet Temperature (ACUAC and ECUAC)
    A number of requirements have been added in Appendix C of AHRI 340/
360-2015 to help ensure accurate and reproducible measurement of the 
condenser air inlet temperature. These requirements include 
specifications on the acceptable number, geometry, placement, and 
construction details of air sampling trees; specifications on the 
required accuracy of dry bulb, wet bulb, and thermopile measurement 
devices; requirements on the set-up and number of aspirating 
psychrometers; and criteria for assessing acceptable air distribution 
and control of air temperature.
    Issue CUAC-9: DOE requests comment on whether any manufacturers 
have evaluated the condenser inlet air uniformity using the criteria in 
Appendix C of AHRI 340/360-2015 for ACUACs and ECUACs and if so, 
whether any alterations to the laboratory or test set-up were necessary 
to meet those requirements. Also, DOE requests comment on whether the 
requirements of Appendix C are sufficient to ensure reproducibility of 
results and/or any test data that demonstrate sufficient 
reproducibility.
    Due to the different heat exchange process of ECUAC condensers when 
compared to ACUACs, ECUACs may have lower condenser airflow and in 
turn, smaller openings for the condenser inlet air when compared to 
ACUACs of similar capacity. Consequently, the air sampler tree and 
thermopile requirements in AHRI 340/360-2015 may not be appropriate for 
ECUACs.
    Issue CUAC-10: DOE requests comments and data on the sizes of the 
smallest and largest openings for condenser inlet air on the sides of 
ECUACs. DOE seeks comment on whether the air sampler tree requirements 
in Appendix C of AHRI 340/360-2015, specifically the requirement of 10 
to 20 branch tubes, and the thermopile requirement of having 16 
thermocouples per air sampler tree, are feasible for all ECUACs. DOE 
also seeks information regarding any alternative methods or 
measurements for determining condenser inlet air uniformity that may be 
more suitable for ECUACs.
    Issue CUAC-11: DOE requests comments and data regarding whether a 
method of measuring and specifications for uniformity of the outdoor 
inlet wet bulb temperature would benefit test reproducibility for 
ECUACs.
e. Tolerance of Tested Indoor Airflow Relative to Rated Indoor Airflow 
(ECUAC and WCUAC)
    AHRI 340/360-2007 does not provide any tolerance on the tested 
indoor airflow relative to the rated airflow of the unit under test. 
AHRI 340/360-2015 has added a 3-percent tolerance for the tested 
airflow relative to the rated airflow (i.e., the tested airflow is 
permitted to be 3 percent higher or 3 percent lower than the rated 
airflow). DOE adopted a 3 percent tolerance on indoor airflow for 
testing ACUACs in the December 2015 CUAC TP final rule to limit 
variation in EER and cooling capacity, based on test data and feedback 
provided by industry commenters. 80 FR 79655, 79659-79660 (Dec. 23, 
2015).
    Issue CUAC-12: DOE seeks comment or data showing whether variations 
in indoor airflow impact the measured efficiency or capacity of ECUACs 
and WCUACs more or less than ACUACs and whether the 3-percent tolerance 
provided in AHRI 340/360-2015 (and adopted for ACUACs in DOE's 
regulations) is appropriate for these other equipment categories.
f. Vertical Separation of Indoor and Outdoor Units
    AHRI 340/360-2007 does not limit the vertical separation of indoor 
and outdoor units when testing split systems. However, AHRI 340/360-
2015 adds a requirement that the maximum allowable vertical separation 
of the indoor and outdoor units be 10 feet, presumably because 
separation greater than 10 feet can adversely affect measured 
performance. If test facilities use indoor and outdoor environmental 
chambers that are stacked vertically, the limitation on vertical 
separation may make it impractical or impossible to test split systems.
    Issue CUAC-13: DOE seeks comment regarding whether a maximum of 10 
feet of vertical separation of indoor and outdoor units would limit the 
ability of existing facilities to test split-system ACUACs, ECUACs, or 
WCUACs. DOE also seeks comment on the impact that vertical separation 
of split systems has on efficiency and capacity.
g. Outdoor Entering Air Wet-Bulb Temperature (ECUAC)
    AHRI 340/360-2007 provides the same outdoor entering air conditions 
(i.e., 95.0 [deg]F dry bulb and 75.0 14; [deg]F wet bulb) for the 
standard rating condition (Table 3 of AHRI 340/360-2007) and the 100-
percent-capacity test point used to calculate IEER (Table 6 of AHRI 
340/360-2007) for ECUACs. While the outdoor entering air dry-bulb 
temperature is unchanged in AHRI 340/360-2015, the outdoor entering air 
wet-bulb temperature for the 100-percent-capacity test point used to 
calculate IEER was changed from 75.0 [deg]F to 74.5 [deg]F (Table 6 of 
AHRI 340/360-2015). This change suggests that two full-load tests may 
be required: One at the standard rating conditions for measuring the 
rated capacity and EER, and another at the 100-percent-capacity test 
point for the IEER test. Table 6 of AHRI 340/360-2015 also lists only 
entering air wet-bulb temperatures for ECUACs, with no corresponding 
dry-bulb temperatures.
    Issue CUAC-14: DOE seeks comment regarding the slightly different 
air wet-bulb test conditions of AHRI 340/360-2015 for standard rating 
conditions as compared with the 100-percent-capacity test point for the 
IEER test, and whether the requirement should be 75.0 [deg]F for both 
purposes.
    Issue CUAC-15: DOE seeks comment on whether the air-cooled entering 
air dry-bulb temperatures in Table 6 of AHRI 340/360-2015 apply to 
evaporatively-cooled units. If any manufacturers have developed IEER 
ratings for ECUACs using AHRI 340/360-2015, DOE requests information 
about what outdoor entering air dry-bulb temperatures were used during 
the 100-percent and part-load tests.
h. Single-Zone Variable-Air-Volume and Multi-Zone Variable-Air-Volume
    AHRI 340/360-2015 established different approaches for setting 
indoor air flow for the part-load test conditions for single-zone 
variable-air-volume (SZVAV) and multi-zone variable-air-

[[Page 34443]]

volume (MZVAV) systems (see section 6.1.3.3). The test standard defines 
MZVAV as units ``designed to vary the indoor air volume and 
refrigeration capacity/staging at a controlled discharge air 
temperature and static pressure as a means of providing space 
temperature control to independent multiple spaces with independent 
thermostats.'' (AHRI 340/360-2015 section 3.14) It defines SZVAV as 
units with a ``control system designed to vary the indoor air volume 
and refrigeration capacity/staging as a means to provide zone control 
to a single or common zones, controlled by a single space thermostat 
input.'' The SZVAV definition further explains that, ``the capacity, as 
well as the supply air flow shall be controlled either through 
modulation, discrete steps or combinations of modulation and step 
control based on the defined control logic.'' (AHRI 340/360-2015 
section 3.25)
    Part of the focus of each definition is the number of zones and 
number of thermostats involved in a system served by a given variable-
air-volume unit. However, the zones served and thermostats connected 
are part of the installation of a unit and not inherent attributes of a 
unit's characteristics. Another part of the definition addresses the 
variation of indoor air flow and capacity. For MZVAV, the air flow and 
capacity can be varied to provide a controlled discharge temperature 
and a controlled static pressure, which suggests, but does not clearly 
state, that such units have variable-capacity compressors, and that 
their indoor fan controls allow fully variable control of fan speed. In 
contrast, the SZVAV definition seems to allow modulation, steps, or a 
combination of steps and modulation for both fan and compressor 
capacity control. Based on these definitions, it seems that a unit with 
a variable-capacity compressor system and a variable-speed fan could 
meet both definitions. Also, it would appear that any unit with a 
variable-capacity compressor system that has SZVAV characteristics 
could be converted to a MZVAV system by changing the indoor fan motor 
controller or perhaps simply changing its settings.
    Issue CUAC-16: DOE requests comment on whether a CUAC model that 
could be both SZVAV and MZVAV should be tested both ways, representing 
two separate basic models. If tested as one basic model, DOE requests 
information regarding how to determine which of the two test methods 
would apply. How frequently would such a model be installed in the 
field as a SZVAV as opposed to a MZVAV? DOE also requests comment on 
whether status as a proportionally controlled unit (see AHRI 340/360-
2015 section 3.20) would be considered to be the appropriate indication 
of whether a CUAC can be used as a MZVAV unit, or whether some other 
characteristics regarding variable capacity control would have to be 
satisfied. Finally, for models that can be both SZVAV and MZVAV, how 
much do the efficiency ratings for the two configurations differ?
3. Additional Test Method Issues
    In this section, DOE explores several additional issues related to 
the test procedures for CUACs. Most issues are relevant to only ECUACs, 
but a few are also relevant to WCUACs and/or ACUACs, as shown in Table 
II.3.

                                 Table II.3--Additional CUAC Test Method Issues
----------------------------------------------------------------------------------------------------------------
                            Topic                                   ACUAC            ECUAC            WCUAC
----------------------------------------------------------------------------------------------------------------
Length of Refrigerant Line Exposed to Outdoor Conditions.....               X                X                X
Atmospheric Pressure Measurement.............................               X                X                X
Consistency Among Test Procedures for Small and Large          ...............               X                X
 Equipment...................................................
Make-up Water Temperature....................................  ...............               X   ...............
Secondary Measurement Method for Capacity....................  ...............               X   ...............
Piping Evaporator Condensate to Condenser Pump...............  ...............               X   ...............
Purge Water Settings.........................................  ...............               X   ...............
Condenser Spray Pumps........................................  ...............               X   ...............
Additional Steps to Verify Proper Operation..................  ...............               X   ...............
----------------------------------------------------------------------------------------------------------------

a. Length of Refrigerant Line Exposed to Outdoor Conditions
    AHRI 340/360-2007, AHRI 340/360-2015, AHRI 210/240-2008, and AHRI 
210/240-2015-Draft all require at least 25 feet of interconnecting 
refrigerant line when testing split-systems. However, both versions of 
AHRI 340/360 require that at least 5 feet of the interconnecting 
refrigerant line must be exposed to outdoor test chamber conditions, 
while both versions of AHRI 210/240 require at least 10 feet be so 
exposed. DOE has estimated an upper bound of the capacity loss to be 
approximately 1 percent of the capacity of the unit for 10 feet of 
refrigerant line located in the outdoor chamber and approximately 0.5 
percent for 5 feet.
    Issue CUAC-17: DOE seeks comment or data regarding the typical 
length of refrigerant line that is exposed to outdoor conditions on 
split-system ACUAC, ECUAC or WCUAC installations and whether this 
length varies depending on the capacity of the unit. DOE also seeks 
comment or data on any measurements or calculations that have been made 
of the losses associated with refrigerant lines located in the outdoor 
chamber and whether the impact is larger or smaller than DOE's estimate 
of approximately 1 percent of capacity per 10 feet of refrigerant line 
located in the outdoor chamber.
b. Atmospheric Pressure Measurement
    The accuracy of atmospheric pressure measurements required by 
section 5.2.2 of ASHRAE 37-2009 (which is referenced by AHRI 340/360-
2015) is 2.5 percent. This level of uncertainty can result 
in error when calculating the indoor entering and leaving air 
enthalpies and resulting cooling capacity. Under certain circumstances, 
atmospheric pressure measurements at the extremes of this tolerance 
result in capacity measurement errors of 1-2 percent.
    Issue CUAC-18: DOE seeks comment on the typical accuracy of the 
atmospheric pressure sensors used by existing test laboratories.
c. Consistency Among Test Procedures for Small and Large ECUAC and 
WCUAC Equipment Classes
    The current test procedure and referenced industry standard for 
ECUACs and WCUACs that have cooling capacities less than 65,000 Btu/h 
(AHRI 210/240-2008) reference the same test method (ASHRAE 37-2005) and 
contain the same efficiency metrics as those for units with capacities 
greater than or equal to 65,000 Btu/h (AHRI 340/360-2007). However, 
there are some differences that have been identified in this section. 
DOE is considering whether the

[[Page 34444]]

consistency of test procedures could be improved by referencing a 
single industry standard for all cooling capacities of ECUACs and 
WCUACs. The updated industry standard for rating units with a capacity 
greater than or equal to 65,000 Btu/h (AHRI 340/360-2015) has 
significant changes that affect the testing of ECUACs and WCUACs. 
However, the industry standard for rating units with a cooling capacity 
less than 65,000 Btu/h is in the process of being updated and could 
potentially be finalized with better consistency with AHRI 340/360 for 
testing of this equipment.
    Issue CUAC-19: DOE requests comment on whether there are 
differences between ECUACs and WCUACs that have cooling capacities less 
than 65,000 Btu/h and those that have cooling capacities greater than 
or equal to 65,000 Btu/h that justify the incorporation by reference of 
different industry test standards for the different cooling capacity 
ranges. If not, DOE seeks feedback on whether referencing a single 
industry standard for units of all cooling capacities would be 
beneficial and/or whether there could or should be better consistency 
between the test standards for testing of this equipment. Specifically, 
DOE requests comment on whether there are actual differences in field 
installations and field use of this equipment and on the extent to 
which these differences impact performance.
d. Make-Up Water Temperature (ECUAC)
    Neither AHRI 340/360-2007 nor AHRI 340/360-2015 provide any 
requirements on the make-up water temperature for the standard rating 
condition or for the part-load IEER tests. Make-up water must be 
supplied to the sump of an ECUAC to replenish the evaporated water (or 
to spray nozzles for models without sumps). AHRI 210/240-2008 and AHRI 
210/240-2015-Draft specify 85.0[emsp14][deg]F for the full-load 
standard rating condition and 77.0[emsp14][deg]F for the part-load 
tests. Cooler makeup water temperature could increase measured cooling 
capacity and vice versa, causing variation in measurements if specific 
temperatures are not required.
    Issue CUAC-20: DOE seeks comment or data regarding the impact that 
the make-up water temperature has on the unit performance. DOE also 
seeks comment or data on whether the make-up water temperatures, 
including the temperatures for part-load conditions, specified in AHRI 
210/240-2008 and AHRI 210/240-2015-Draft are representative of 
conditions experienced by field-installed ECUACs of all cooling 
capacities.
e. Secondary Measurement Method for Capacity (ECUAC)
    ASHRAE 37-2009 requires the indoor air enthalpy method plus an 
additional secondary method for calculating the test equipment capacity 
for all units with less than 135,000 Btu/h rated capacity. The test 
standard lists applicable test methods in Table 1, but this table does 
not indicate that the outdoor air enthalpy method is applicable for any 
configuration of evaporatively-cooled equipment. Therefore, the 
secondary method for ECUACs is limited to use of the refrigerant 
enthalpy method or compressor calibration method for split systems and 
only the compressor calibration method for single-package equipment. 
DOE recognizes that the refrigerant enthalpy method and compressor 
calibration method can, in some circumstances, add burden to the 
testing procedure, so DOE examined the potential use of the outdoor air 
enthalpy method as a secondary method for ECUACs. During testing, DOE 
observed that the part-load test conditions produce an environment 
where condensation is likely in the outdoor unit supply duct, because 
the outdoor air dry bulb temperature cooling the duct walls can be 
lower than the dew point of the warm moist air leaving the outdoor 
unit. This condensation would be unaccounted for by the outdoor air 
enthalpy method, resulting in a calculated capacity less than the 
actual capacity. To consider another approach, DOE notes that it 
modified the CAC/HP test method to require a secondary capacity 
measurement only for full-load operation for cooling and heating, 
rather than for all tests in a January 5, 2017 final rule. 82 FR 1426, 
1441. While this change was for central air conditioners and heat 
pumps, limiting the secondary method test to a single set of 
conditions, such as the full-load cooling (and heating, if applicable) 
test conditions, would eliminate or reduce the potential for 
condensation in the outdoor supply duct when testing ECUACs.
    Issue CUAC-21: DOE seeks comment or test data on the difficulty of 
getting a match of primary and secondary capacity measurements when 
testing ECUACs with rated capacities less than 135,000 Btu/h and 
whether the difficulty level is higher, lower, or the same when testing 
the unit at full-load conditions as compared to part-load conditions. 
DOE also seeks comment and data on how often the primary capacity 
measurement results in an exceeded allowable percent difference between 
the primary and secondary capacity measurements.
    Issue CUAC-22: DOE seeks comment on whether single-package ECUACs 
with a rated cooling capacity less than 135,000 Btu/h are currently 
sold.
    Issue CUAC-23: DOE seeks comment on whether manufacturers would see 
a benefit in allowing the outdoor air enthalpy method as a secondary 
capacity measurement for ECUACs. If so, DOE is interested in feedback 
on methods to mitigate the risk of condensation in the outdoor unit 
supply duct and the outdoor supply wet-bulb sample station. DOE also 
asks if other alternative approaches could be considered for mitigating 
the potential test burden associated with the secondary test methods 
that ASHRAE 37-2009 specifies for evaporatively-cooled equipment.
f. Piping Evaporator Condensate to Condenser Pump (ECUAC)
    Some split-system ECUACs provide the option for piping evaporator 
condensate to the condenser sump. This reduces the make-up water use of 
the unit and may provide some performance improvement. Neither DOE's 
current test procedures nor the industry ECUAC test standards address 
this potential variation, which could result in differences in test 
results depending on whether this feature was employed in a test.
    Issue CUAC-24: DOE seeks comment on whether ECUACs that allow 
piping of evaporator condensate to the condenser sump present any 
complications (e.g., maintaining proper slope in the piping from the 
evaporator to the outdoor unit and test repeatability issues) when 
testing in a laboratory. DOE also seeks comment or data indicating what 
kind of impact piping the evaporator condensate to the condenser sump 
has on the efficiency and/or capacity of ECUACs.
g. Purge Water Settings (ECUAC)
    Some ECUACs require the sump water to be continuously or 
periodically purged in order to reduce mineral and scale build-up on 
the condenser heat exchanger. AHRI 340/360-2015 provides guidance to 
set up and configure the unit per the manufacturer's installation 
instructions, which would include setting the purge rate if specified.
    Issue CUAC-25: DOE seeks comment on how the purge water rate should 
be set for laboratory testing if the manufacturer's installation 
instructions do not contain information on this topic.

[[Page 34445]]

h. Condenser Spray Pumps (ECUAC)
    The rate that water is sprayed on the condenser coil may have an 
impact on the performance of an ECUAC. For units with sumps, this rate 
may be affected by the pump set-up, and, for units without sumps, the 
incoming water pressure may have an impact. Neither DOE's current test 
procedures nor the industry ECUAC test standards address these 
potential variations.
    Issue CUAC-26: DOE requests comment on whether the pump flow can be 
adjusted on any ECUACs on the market that have circulation pumps. DOE 
also requests comment on whether ECUACs without a sump exist and, if 
so, whether there are requirements on the incoming water pressure to 
ensure proper operation of the spray nozzles. DOE also requests 
comments and/or data regarding the sensitivity of performance test 
results to these adjustments.
i. Additional Steps To Verify Proper Operation (ECUAC)
    Some ECUACs may use spray nozzles with very small diameter openings 
that may become easily clogged, thereby reducing the effectiveness of 
the heat exchanger.
    Issue CUAC-27: DOE requests comment on whether there are any 
additional steps that should be taken to verify proper operation of 
ECUACs during testing, such as ensuring nozzles are not blocked.
    Issue CUAC-28: DOE requests comment on any additional issues 
associated with adopting AHRI 340/360-2015 for ACUACs, ECUACs, and 
WCUACs.

D. Test Procedure for Variable Refrigerant Flow Multi-Split Air 
Conditioners and Heat Pumps

    DOE's commercial equipment regulations include test procedures and 
energy conservation standards that apply to air-cooled VRF multi-split 
air conditioners, air-cooled VRF multi-split heat pumps, and water-
source VRF multi-split heat pumps, all with cooling capacity less than 
760,000 Btu/h, except air-cooled, single-phase VRF multi-split air 
conditioners and heat pumps with cooling capacity less than 65,000 Btu/
h (which are covered by DOE's consumer product regulations for central 
air conditioners \12\). 10 CFR 431.96 and 431.97.
---------------------------------------------------------------------------

    \12\ See 10 CFR 430.32(c) and Appendix M and M1 to Subpart B of 
Part 430.
---------------------------------------------------------------------------

    DOE's test procedure for (commercial) VRF multi-split systems is 
codified at 10 CFR 431.96 and was established in the May 2012 final 
rule. 77 FR 28928 (May 16, 2012). DOE's current regulations require 
that manufacturers test VRF multi-split systems using AHRI 1230-2010 
with addendum 1, except for sections 5.1.2 and 6.6. DOE's current test 
procedure also requires that manufacturers adhere to certain additional 
requirements listed in 10 CFR 431.96(c)-(f). Although ASHRAE 90.1-2016 
did not update its test procedure reference for VRF (AHRI 1230-2010 
with addendum 1), DOE is reviewing its test procedure in response to 
the seven-year-lookback statutory review requirement (see 42 U.S.C. 
6314(a)(1)(A)), and in advance of its review of energy conservation 
standards for VRF in response to changes in ASHRAE 90.1-2016.
    As part of its seven-year-lookback review, DOE is examining updated 
industry test standards, including Addendum 2 to AHRI 1230-2010 
(approved June 2014) and a draft version of AHRI 1230 provided by AHRI 
for the docket that will supersede AHRI 1230-2010 (with Addendum 1 and 
2) once published (``AHRI 1230-Draft,'' No. 1). DOE reviewed the AHRI 
1230-Draft and discusses in the following sections specific issues 
regarding the draft and other items related to the VRF test procedure.
1. Energy Efficiency Descriptors
    DOE currently prescribes energy conservation standards for air-
cooled VRF multi-split systems with cooling capacity greater than or 
equal to 65,000 Btu/h and water-source VRF multi-split systems in terms 
of the EER metric for cooling-mode operation and in terms of the 
coefficient of performance (COP) metric for heating-mode operation.\13\ 
DOE is considering whether to add or replace the existing cooling-mode 
efficiency descriptor (i.e., EER) with a new cooling-mode energy-
efficiency descriptor that better captures part-load performance, such 
as IEER.
---------------------------------------------------------------------------

    \13\ DOE also prescribes energy conservation standards for 
three-phase air-cooled VRF multi-split systems with cooling capacity 
less than 65,000 Btu/h in terms of the SEER metric for cooling-mode 
operation and in terms of the heating seasonal performance factor 
(HSPF) metric for heating-mode operation.
---------------------------------------------------------------------------

    IEER factors in the efficiency of operating at part-load conditions 
of 75-percent, 50-percent, and 25-percent of capacity, as well as the 
efficiency at full-load. The IEER metric provides a more representative 
measure of energy consumption in actual operation by weighting the 
full-load and part-load efficiencies with the average amount of time 
equipment spends operating at each load point. ASHRAE 90.1 has 
specified an IEER metric for commercial air conditioning and heat pump 
equipment since the 2008 Supplement to Standard 90.1-2007, effective 
January 1, 2010.14 15 ASHRAE Standard 90.1-2013 included 
minimum efficiency levels for both the EER and IEER of air-cooled VRF 
multi-split systems and for the EER of water-source VRF multi-split 
systems. ASHRAE Standard 90.1-2016 added IEER levels for water-source 
VRF multi-split systems, including units with cooling capacity less 
than 65,000 Btu/h. DOE notes that in addition to ASHRAE 90.1, both the 
ENERGY STAR and Consortium for Energy Efficiency (CEE) programs use the 
IEER metric for VRF systems.16 17
---------------------------------------------------------------------------

    \14\ ASHRAE Standard 90.1 first specified a part-load 
performance metric in the 2007 edition, which used integrated part 
load value (IPLV).
    \15\ ASHRAE, ASHRAE Addenda (2008 Supplement) (Available at: 
http://www.ashrae.org/File%20Library/docLib/Public/20090317_90_1_2007_supplement.pdf).
    \16\ ENERGY STAR Program Requirements, Product Specifications 
for Light Commercial HVAC (Available at: https://www.energystar.gov/sites/default/files/specs//private/LC_HVAC_V2.2.pdf).
    \17\ Consortium for Energy Efficiency, CEE Commercial Unitary AC 
and HP Specification (Available at: http://www.cee1.org/files/CEE_CommHVAC_UnitarySpec2012.pdf).
---------------------------------------------------------------------------

    On January 15, 2016, DOE published a direct final rule for energy 
conservation standards for small, large, and very large air-cooled 
commercial package air conditioners and heat pumps (CUACs and CUHPs), 
which amended the energy conservation standards for CUACs and CUHPs and 
changed the cooling efficiency metric from EER to IEER. 81 FR 2420. 
Except possibly for ventilation, VRF multi-split systems serve the same 
primary functions as CUACs and CUHPs (i.e., space heating and cooling 
commercial buildings) and are used in a similarly wide range of 
climatic conditions.
    Because the vast majority of cooling and heating loads do not 
demand operation at full-load, the full-season metric IEER may capture 
the efficiency of VRF multi-split systems operating in the field more 
realistically than does the full-load metric EER. DOE believes that the 
publication of IEER ratings for most units on the market (as in AHRI's 
Directory of Certified Product Performance for VRF multi-split 
systems), as well as the inclusion of minimum efficiency levels and 
test procedures for IEER of VRF multi-split systems in ASHRAE Standard 
90.1-2016 and AHRI 1230-2010, respectively, demonstrate that IEER is an 
industry-accepted metric for measuring efficiency of VRF multi-split 
systems. For these reasons, DOE is considering replacing the current 
EER metric for VRF multi-split systems with

[[Page 34446]]

the full-season IEER metric, or adding IEER in addition to EER. DOE's 
ultimate decision will be impacted by the separate energy conservation 
standards rulemaking considering the efficiency levels for VRF in 
ASHRAE 90.1-2016.
    Issue VRF-1: DOE requests comment on issues DOE should consider 
regarding potentially using IEER as an efficiency metric for energy 
conservation standards for air-cooled VRF multi-split systems with a 
cooling capacity greater than or equal to 65,000 Btu/h and all water-
source VRF multi-split systems, so as to capture efficiency in part-
load operation.
2. Representativeness and Repeatability
    Operation of VRF multi-split systems is inherently variable, and 
DOE notes that the control systems of VRF multi-split systems can be 
significantly more sophisticated than control systems in other 
commercial HVAC systems. In order to achieve steady-state operation, it 
is generally necessary for a manufacturer's representative that is 
knowledgeable about the control system to be present during testing in 
order to override the typical dynamic control and to set each 
individual component at a fixed position or speed. It may be possible 
to achieve ``full-load'' capacity and/or part-load operation in 
different ways, all of which may be consistent with the test procedure 
and manufacturer's installation instructions.
    Issue VRF-2: DOE seeks comment on the settings required to be 
reported in order for third-party laboratories to reproduce unit 
performance in a rating test.
    Section 6.3.4 of AHRI 1230-Draft requires that for air-cooled VRF 
multi-split systems with a cooling capacity less than 65,000 Btu/h, at 
least one indoor unit must be turned off for tests conducted at minimum 
compressor speed. DOE also established a similar requirement for CACs 
in the June 2016 CAC TP final rule. 81 FR 36992, 37038 (June 8, 2016). 
However, AHRI 1230-Draft does not include a corresponding requirement 
for equipment with a cooling capacity greater than or equal to 65,000 
Btu/h or for water-source VRF multi-split systems. This requirement for 
equipment less than 65,000 Btu/h considers the wide range of loads that 
can occur in the field. However, DOE expects that load diversity would 
also be an issue for larger-capacity VRF multi-split systems used in 
commercial applications.
    Issue VRF-3: DOE requests information and data on the field 
operating states of indoor units of VRF multi-split systems when 
operating at low compressor speeds (i.e., near 25-percent load). 
Specifically, are there field data available that show operating states 
of VRF multi-split systems at different load levels? Such data might 
show what happens with indoor fan speeds and expansion devices of 
indoor units at low load percentages, including whether any indoor fans 
shut off, or whether any refrigerant flow control devices shut off 
refrigerant flow, and how this might be affected by the user-accessible 
control positions set for the indoor units. DOE is also interested in 
whether indoor unit operation at low compressor speeds is different in 
field application for VRF multi-split systems with cooling capacities 
less than 65,000 Btu/h than those with capacities greater than or equal 
to 65,000 Btu/h, and whether these trends follow at intermediate 
compressor speeds as well. Further, DOE requests data that would show 
the trends of total system capacity, total indoor air flow, and 
sensible heat ratio as a function of compressor speed (e.g., percentage 
of full-speed revolutions per minute) for laboratory rating tests of 
typical VRF multi-split systems conducted either with one or no indoor 
unit shut off at the lowest load point.
3. Test Method
a. Transient Testing: Oil Recovery Mode
    AHRI 1230-Draft refers to ASHRAE 37-2009 for provisions for 
transient tests, which are required when defrost interferes with 
steady-state operation sufficiently frequently to prevent completion of 
a steady-state test (see, for example, sections 8.8.2.5.1 and 8.8.2.5.2 
of that test standard). Specific instructions are provided for how to 
determine an average heating capacity for the transient test, with 
different instructions depending on the number and completion of 
defrost cycles. Tables 2a and 2b of ASHRAE 37-2009 specify the test 
tolerances to be used when conducting a transient heating capacity 
test.
    VRF multi-split systems may periodically operate in an oil recovery 
mode in order to return oil from the refrigeration loop to the 
compressor. Section 5.1.3 of AHRI 1230-Draft requires that if a 
manufacturer indicates that a VRF multi-split system is designed to 
recover oil more frequently than every two hours of continuous 
operation, the oil recovery mode shall be activated during testing, and 
the additional power shall be included in the efficiency calculations. 
However, there is no specific instruction in the AHRI 1230-Draft that 
indicates how the additional power should be incorporated into the 
efficiency metric. DOE expects that maintenance of steady-state 
conditions may be affected during oil recovery mode and that, as a 
result, some type of transient test procedure may be appropriate when 
oil recovery mode happens during testing. However, AHRI 1230-Draft does 
not specify use of the transient test for this case, and the ASHRAE 37-
2009 description of the transient test does not mention oil recovery. 
DOE notes that VRF multi-split systems vary in the way they activate 
oil recovery mode; some may initiate oil recovery mode at a set time 
interval, and others may instead initiate oil recovery mode only when 
the system detects that the oil level in the compressor has reached a 
certain minimum level. DOE understands that unit performance may vary 
with the oil level. Consequently, DOE is considering requiring all 
measurements to be made within a certain time after the last oil 
recovery to ensure repeatability between tests.
    Issue VRF-4: DOE requests comment on the impact of oil recovery 
mode, including power input and heating/cooling provided to space 
during oil recovery mode. DOE also requests comment on whether any VRF 
multi-split systems operate in oil recovery mode more frequently than 
every two hours of continuous operation. For such systems, DOE requests 
comment on whether the test method should be modified to address the 
transient operation occurring during and after oil recovery, and how 
this should be done. In addition, DOE requests comment on the 
performance variation associated with oil level and whether all 
measurements should be made within a certain time after the last oil 
recovery. Lastly, DOE requests comment on how the energy use of oil 
recovery mode might be addressed in the test procedure without imposing 
excessive test burden.
b. Airflow Setting and Minimum External Static Pressure
    DOE notes AHRI 1230-Draft contains one set of instructions for 
setting the indoor air flow rates for systems with capacities less than 
65,000 Btu/h (section 6.3.3.1) and another set for systems with 
capacities larger than 65,000 Btu/h (section 6.4.1). It is not clear 
why alternate approaches are required for different systems because the 
indoor units generally do not differ by system capacity.
    Issue VRF-5: DOE requests comment on whether there should be a 
consistent approach for setting indoor airflow across all capacity 
ranges of VRF multi-split systems.

[[Page 34447]]

c. Condenser Head Pressure Controls
    Condenser head pressure controls regulate the flow of refrigerant 
through the condenser and/or adjust operation of condenser fans to 
prevent condenser pressures from dropping too low during low-ambient 
operation. When employed, these controls ensure that the refrigerant 
pressure is high enough to maintain adequate flow through refrigerant 
expansion devices such as thermostatic expansion valves. In the 
December 2015 CUAC test procedure final rule, DOE required that CUACs 
and CUHPs equipped with head pressure controls have these controls 
activated during testing. 80 FR 79655, 79660 (Dec. 23, 2015). For VRF 
multi-split systems equipped with heat recovery, it is unclear whether 
the head pressure would be elevated when one of the indoor units calls 
for heating during cooling-based operation. It is also not clear how 
the head pressure differs during cool outdoor conditions between units 
with and without heat recovery function.
    Issue VRF-6: DOE requests comment on the appropriateness of 
requiring head pressure control activation during testing of VRF multi-
split systems. In addition, DOE requests comment on any methods to 
control VRF multi-split systems during testing to ensure stable 
operation with head pressure controls activated. Further, DOE requests 
comment on any methods that could be added to the test procedure for 
calculation of system efficiency of VRF multi-split systems if head 
pressure controls prevent stable operation at low-ambient, part-load 
conditions.
d. Air Volume Rate for Non-Ducted Indoor Units
    DOE notes the following issues associated with testing multi-split 
systems with free discharge air flow from the indoor unit (i.e., 
airflow provided directly from the indoor unit to the conditioned space 
without the use of ducts). In testing, if a common duct is used for the 
combined discharge airflow of multiple individual units, the airflow 
for each individual unit cannot be verified. Second, even if the ESP is 
set to zero--which is intended to replicate operation without ducting--
based on a measurement of downstream pressure in a discharge duct, this 
does not always guarantee that flow is identical to free discharge 
conditions, due to sensitivity of such in-duct pressure measurements to 
the air movement in the duct. Finally, specification of unusually high 
air flows for testing of free discharge in indoor units may boost 
measured performance inconsistent with field operation. Section 
6.3.3.1.1.3 of AHRI 1230-Draft added an upper limit on air flow per 
capacity for non-ducted units for systems with capacity less than 
65,000 Btu/h--the rated air volume for each indoor unit must not exceed 
55 scfm per 1,000 Btu/h.\18\
---------------------------------------------------------------------------

    \18\ DOE notes that test methods associated with the indoor 
units of systems with capacity <65,000 Btu/h are relevant for 
testing of systems with capacity >=65,000 Btu/h because the 
capacities of the indoor units are comparable.
---------------------------------------------------------------------------

    Issue VRF-7: DOE requests comment on how to confirm air flow for 
each indoor unit individually when there is a common duct for each unit 
and when there is potential deviation from free-discharge operation if 
a discharge duct is connected. DOE also requests comment on whether 
there should be an upper limit of air flow per capacity for non-ducted 
units, such as the 55 scfm per 1,000 Btu/h limit in the AHRI 1230-
Draft.
e. Secondary Test Method
    In AHRI 1230-Draft, ASHRAE 37-2009 is referenced as the test 
procedure for both air-cooled and water-cooled units across all 
capacities. Section 7.2.1 in ASHRAE 37-2009 requires a secondary test 
method in addition to the primary method (i.e., indoor air enthalpy 
method) for units having a total cooling capacity less than 135,000 
Btu/h. ASHRAE 37-2009 provides multiple options for the secondary test 
method. For units with a cooling capacity larger than 135,000 Btu/h, 
section 7.2.2 of ASHRAE 37-2009 only requires a single method, but 
provides multiple test method options.
    Section 11.1.1.7 of AHRI 1230-Draft indicates the redundant 
measurement verification method as an alternative to refrigerant 
enthalpy method or outdoor enthalpy method when they cannot be 
performed. However, the draft does not provide guidance on how to 
determine whether the refrigerant enthalpy method or outdoor enthalpy 
method can or cannot be performed. DOE is considering whether there are 
other alternatives to the refrigerant enthalpy method or outdoor 
enthalpy method (other than the duplicate measurement method), such as 
the cooling condensate and indirect airflow measurement method.
    Issue VRF-8: DOE requests comment on the methods generally used for 
measurement of capacity when testing VRF multi-split systems and 
whether the selection of methods differs between cooling and heating 
tests. DOE requests comment on how to determine whether the refrigerant 
enthalpy method or outdoor air enthalpy method (for units having a 
total cooling capacity less than 135,000 Btu/h) can or cannot be 
performed. DOE also requests comment on how to standardize the 
selection of test methods for measuring the capacity of VRF multi-split 
systems. Finally, DOE requests comment on whether there are issues with 
achieving heat balance in part-load tests for VRF multi-split systems, 
similar to those cited for variable speed CAC/HP, and if so, whether 
there is sufficient assurance of proper measurement for all test points 
of VRF multi-split systems if the heat balance is verified only for 
full capacity.
f. Heat Recovery
    VRF multi-split systems with heat recovery include a heat recovery 
unit (sometimes referred to as a branch circuit controller) that 
controls refrigerant flow between indoor units, allowing for 
simultaneous cooling and heating operation. However, DOE believes that 
VRF multi-split systems with the heat recovery capability may be able 
to operate without the heat recovery unit attached, although in such 
case, simultaneous heating and cooling would not be possible. It is not 
clear in AHRI 1230-Draft whether VRF multi-split systems capable of 
heat recovery must be tested with the heat recovery unit attached in 
tests for determining EER, IEER, and COP. DOE seeks clarification on 
industry practice for testing VRF multi-split systems with the heat 
recovery feature because attachment of the heat recovery unit may 
affect test results.
    Issue VRF-9: DOE seeks comment on whether VRF multi-split systems 
with the heat recovery feature can be operated without the heat 
recovery unit attached, and if so, whether such systems are typically 
tested for determining EER, IEER, and COP with the heat recovery unit 
attached. Additionally, DOE seeks data showing the difference in test 
results between having the heat recovery unit attached or not.
4. Representations
a. Tested Combination
    AHRI specified requirements for tested combinations for systems 
with capacities more than 65,000 Btu/h in section 6.2.2 of the AHRI 
1230-Draft. The AHRI requirement specifies selecting standard 4-way 
ceiling cassette indoor units with the smallest coil volume per nominal 
capacity for non-ducted indoor units and selecting mid-static units for 
ducted indoor units. DOE is aware that there is a range of ductless 
indoor unit styles, which may have a range of efficiency 
characteristics. In

[[Page 34448]]

addition, ducted systems may serve a range of external static 
pressures.
    A report by the Cadeo Group \19\ indicates that 4-way ceiling 
cassettes are the most prevalent non-ducted indoor units. On the other 
hand, while DOE notes that ducted units can be classified by the amount 
of static pressure they produce as either low-static, mid-static, or 
conventional-static units, DOE has no data indicating which ducted unit 
style or static pressure classification is the most prevalent.
---------------------------------------------------------------------------

    \19\ Cadeo Report. See docket: EERE-2017-BT-TP-0018. No. 2. The 
report presents market share by VRF multi-split system equipment 
class, based on confidential sales data given in interviews with 
several major manufacturers of VRF multi-split equipment and DOE's 
CCMS database.
---------------------------------------------------------------------------

    Issue VRF-10: DOE requests comment and data on variation of system 
efficiency related to indoor unit styles (both for ducted and non-
ducted indoor units). For example, for a system tested with non-ducted 
units, what is the potential range of EER and/or IEER comparing the 
most-efficient indoor units with the most energy-intensive indoor 
units? DOE requests comment on its assumption that 4-way ceiling 
cassettes are the most prevalent non-ducted indoor unit style. DOE also 
requests data on the most prevalent style and static pressure 
classification (low-static, mid-static, or conventional-static) of 
ducted units.
b. Determination of Represented Values
    DOE recognizes that non-ducted indoor units and ducted indoor units 
operate at different levels of ESP and have different limitations on 
ESP. The ESP affects the power consumed by the indoor fan, and, 
therefore, also affects the measured efficiency of a VRF multi-split 
system. DOE is considering requiring separate ratings for different ESP 
levels to account for differences between ducted indoor units, non-
ducted indoor units, and possibly other distinctions in indoor units.
    Issue VRF-11: DOE requests comment on how many distinctly 
identifiable ESP levels are generally represented in a family of VRF 
multi-split systems and what ESP levels are typical for VRF multi-split 
systems. DOE also requests data that demonstrate how different ESP 
levels affect measured efficiency for the system, both in terms of EER 
and IEER.
    Issue VRF-12: DOE requests comment on what specific topics 
pertaining to the test procedure for VRF multi-split air conditioners 
and heat pumps, in addition to the topics discussed previously, are not 
fully or appropriately addressed in the docketed AHRI-1230-Draft.

E. Other Test Procedure Topics

    In addition to the issues identified earlier in this document, DOE 
welcomes comment on any other aspect of the existing test procedures 
for commercial package air conditioning and heating equipment that is 
the subject of this notice not already addressed by the specific areas 
identified in this document. DOE particularly seeks information that 
would improve the representativeness of the test procedures, as well as 
information that would help DOE create a procedure that would limit 
manufacturer test burden through streamlining or simplifying testing 
requirements. Comments regarding repeatability and reproducibility are 
also welcome.
    DOE also requests feedback on any potential amendments to the 
existing test procedures that could be considered to address impacts on 
manufacturers, including small businesses. Regarding the Federal test 
methods, DOE seeks comment on the degree to which the DOE test 
procedures should consider and be harmonized with the most recent 
relevant industry standards for the commercial package air conditioning 
and heating equipment that is the subject of this notice, and whether 
there are any changes to the Federal test methods that would provide 
additional benefits to the public.
    Additionally, DOE requests comment on whether the existing test 
procedures limit a manufacturer's ability to provide additional 
features to consumers on the commercial package air conditioning and 
heating equipment that is the subject of this notice. DOE particularly 
seeks information on how the test procedures could be amended to reduce 
the cost of new or additional features and make it more likely that 
such features are included on the equipment.

III. Submission of Comments

    DOE invites all interested parties to submit in writing by August 
24, 2017, comments, data, and information on matters addressed in this 
notice and on other matters relevant to DOE's consideration of amended 
test procedures for VRF multi-split systems, CRAC and DOAS equipment, 
and water-cooled, evaporatively-cooled, and air-cooled commercial 
unitary air conditioners (WCUACs, ECUACs, and ACUACs). These comments 
and information will aid in the development of a test procedure NOPR 
for the subject VRF multi-split systems, and CRAC, DOAS, WCUAC, ECUAC, 
and ACUAC equipment, if DOE determines that amended test procedures may 
be appropriate for these products.
    Instructions: All submissions received must include the agency name 
and docket number and/or RIN for this rulemaking. No telefacsimilies 
(faxes) will be accepted.
    Docket: The docket is available for review at https://www.regulations.gov, including Federal Register notices, comments, and 
other supporting documents/materials. All documents in the docket are 
listed in the https://www.regulations.gov index. However, not all 
documents listed in the index may be publicly available, such as 
information that is exempt from public disclosure.
    A link to the docket Web page can be found at: https://www.regulations.gov/docket?D=EERE-2017-BT-TP-0018. This Web page 
contains a link to the docket for this notice on the https://www.regulations.gov Web site. The https://www.regulations.gov Web page 
contains instructions on how to access all documents, including public 
comments, in the docket.
    For information on how to submit a comment, review other public 
comments and the docket, or participate in the public meeting, contact 
the Appliance Standards Program at (202) 586-6636 or by email: 
[email protected]. DOE considers public 
participation to be a very important part of the process for developing 
test procedures and energy conservation standards. DOE actively 
encourages the participation and interaction of the public during the 
comment period at each stage of the rulemaking process. Interactions 
with and between members of the public provide a balanced discussion of 
the issues and assist DOE in the rulemaking process. Anyone who wishes 
to be added to the DOE mailing list to receive future notices and 
information about this rulemaking should contact Appliance and 
Equipment Standards Program staff at (202) 586-6636 or by email at 
[email protected].
    Submitting comments via https://www.regulations.gov. The https://www.regulations.gov Web page will require you to provide your name and 
contact information. Your contact information will be viewable to DOE 
Building Technologies staff only. Your contact information will not be 
publicly viewable except for your first and last names, organization 
name (if any), and submitter representative name (if any). If your 
comment is not processed properly because of technical difficulties, 
DOE will use this information to contact you. If DOE cannot read your 
comment due to

[[Page 34449]]

technical difficulties and cannot contact you for clarification, DOE 
may not be able to consider your comment.
    However, your contact information will be publicly viewable if you 
include it in the comment itself or in any documents attached to your 
comment. Any information that you do not want to be publicly viewable 
should not be included in your comment, nor in any document attached to 
your comment. Otherwise, persons viewing comments will see only first 
and last names, organization names, correspondence containing comments, 
and any documents submitted with the comments.
    Do not submit to https://www.regulations.gov information for which 
disclosure is restricted by statute, such as trade secrets and 
commercial or financial information (hereinafter referred to as 
Confidential Business Information (CBI)). Comments submitted through 
https://www.regulations.gov cannot be claimed as CBI. Comments received 
through the Web site will waive any CBI claims for the information 
submitted. For information on submitting CBI, see the Confidential 
Business Information section.
    DOE processes submissions made through https://www.regulations.gov 
before posting. Normally, comments will be posted within a few days of 
being submitted. However, if large volumes of comments are being 
processed simultaneously, your comment may not be viewable for up to 
several weeks. Please keep the comment tracking number that https://www.regulations.gov provides after you have successfully uploaded your 
comment.
    Submitting comments via email, hand delivery/courier, or postal 
mail. Comments and documents submitted via email, hand delivery/
courier, or postal mail also will be posted to https://www.regulations.gov. If you do not want your personal contact 
information to be publicly viewable, do not include it in your comment 
or any accompanying documents. Instead, provide your contact 
information in a cover letter. Include your first and last names, email 
address, telephone number, and optional mailing address. The cover 
letter will not be publicly viewable as long as it does not include any 
comments.
    Include contact information each time you submit comments, data, 
documents, and other information to DOE. If you submit via mail or hand 
delivery/courier, please provide all items on a CD, if feasible, in 
which case it is not necessary to submit printed copies.
    Comments, data, and other information submitted to DOE 
electronically should be provided in PDF (preferred), Microsoft Word or 
Excel, WordPerfect, or text (ASCII) file format. Provide documents that 
are not secured, that are written in English, and that are free of any 
defects or viruses. Documents should not contain special characters or 
any form of encryption and, if possible, they should carry the 
electronic signature of the author.
    Campaign form letters. Please submit campaign form letters by the 
originating organization in batches of between 50 to 500 form letters 
per PDF or as one form letter with a list of supporters' names compiled 
into one or more PDFs. This reduces comment processing and posting 
time.
    Confidential Business Information. According to 10 CFR 1004.11, any 
person submitting information that he or she believes to be 
confidential and exempt by law from public disclosure should submit via 
email, postal mail, or hand delivery/courier two well-marked copies: 
One copy of the document marked ``confidential'' including all the 
information believed to be confidential, and one copy of the document 
marked ``non-confidential'' with the information believed to be 
confidential deleted. Submit these documents via email or on a CD, if 
feasible. DOE will make its own determination about the confidential 
status of the information and treat it according to its determination.
    Factors of interest to DOE when evaluating requests to treat 
submitted information as confidential include: (1) A description of the 
items, (2) whether and why such items are customarily treated as 
confidential within the industry, (3) whether the information is 
generally known by or available from other sources, (4) whether the 
information has previously been made available to others without 
obligation concerning its confidentiality, (5) an explanation of the 
competitive injury to the submitting person which would result from 
public disclosure, (6) when such information might lose its 
confidential character due to the passage of time, and (7) why 
disclosure of the information would be contrary to the public interest.
    It is DOE's policy that all comments may be included in the public 
docket, without change and as received, including any personal 
information provided in the comments (except information deemed to be 
exempt from public disclosure).
    DOE considers public participation to be a very important part of 
the process for developing test procedures and energy conservation 
standards. DOE actively encourages the participation and interaction of 
the public during the comment period in each stage of the rulemaking 
process. Interactions with and between members of the public provide a 
balanced discussion of the issues and assist DOE in the rulemaking 
process. Anyone who wishes to be added to the DOE mailing list to 
receive future notices and information about this rulemaking should 
contact Appliance and Equipment Standards Program staff at (202) 586-
6636 or via email at [email protected].

     Issued in Washington, DC, on July 11, 2017.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and 
Renewable Energy.
[FR Doc. 2017-15580 Filed 7-24-17; 8:45 am]
BILLING CODE 6450-01-P



                                                                                                                                                                                                      34427

                                                      Proposed Rules                                                                                                 Federal Register
                                                                                                                                                                     Vol. 82, No. 141

                                                                                                                                                                     Tuesday, July 25, 2017



                                                      This section of the FEDERAL REGISTER                     refrigerant flow multi-split air                      Independence Avenue SW.,
                                                      contains notices to the public of the proposed           conditioners and heat pumps (VRF                      Washington, DC 20585–0121. If
                                                      issuance of rules and regulations. The                   multi-split systems) but excluding                    possible, please submit all items on a
                                                      purpose of these notices is to give interested           single-phase systems with a rated                     compact disc (CD), in which case it is
                                                      persons an opportunity to participate in the             cooling capacity less than 65,000 Btu/h,              not necessary to include printed copies.
                                                      rule making prior to the adoption of the final
                                                                                                               which are covered as consumer                           • Hand Delivery/Courier: Appliance
                                                      rules.
                                                                                                               products. To inform interested parties                and Equipment Standards Program, U.S.
                                                                                                               and to facilitate this process, DOE has               Department of Energy, Building
                                                      DEPARTMENT OF ENERGY                                     gathered data and has identified several              Technologies Office, 950 L’Enfant Plaza,
                                                                                                               issues that might warrant modifications               SW., 6th Floor, Washington, DC 20024.
                                                      10 CFR Parts 429 and 431                                 to the currently applicable Federal test              Telephone: (202) 586–6636. If possible,
                                                                                                               procedures, topics on which DOE is                    please submit all items on a CD, in
                                                      [EERE–2017–BT–TP–0018]
                                                                                                               particularly interested in receiving                  which case it is not necessary to include
                                                      RIN 1904–AD93                                            comment. In overview, the issues                      printed copies.
                                                                                                               outlined in this document mainly                        No telefacsimilies (faxes) will be
                                                      Energy Conservation Program for                          concern incorporation by reference of                 accepted. For detailed instructions on
                                                      Certain Commercial and Industrial                        the most recent version of the relevant               submitting comments and additional
                                                      Equipment: Test Procedure for Certain                    industry standard(s); efficiency metrics              information on the rulemaking process,
                                                      Categories of Commercial Air                             and calculations; clarification of test               see section III of this document (Public
                                                      Conditioning and Heating Equipment                       methods; and any additional topics that               Participation).
                                                      AGENCY:  Office of Energy Efficiency and                 may inform DOE’s decisions in a future                  Docket: The docket for this activity,
                                                      Renewable Energy, Department of                          test procedure rulemaking, including                  which includes Federal Register
                                                      Energy (DOE).                                            methods to reduce regulatory burden                   notices, comments, and other
                                                                                                               while ensuring the procedures’                        supporting document/materials, is
                                                      ACTION: Request for information (RFI).
                                                                                                               accuracy. These topics (and others                    available for review at
                                                      SUMMARY:   In response to statutory                      identified by commenters) are ones                    www.regulations.gov. All documents in
                                                      requirements to review its test                          which may be addressed in proposed                    the docket are listed in the
                                                      procedures in response to any updates                    test procedure amendments in a                        www.regulations.gov index. However,
                                                      of the relevant industry test procedures,                subsequent notice of proposed                         not all documents listed in the index
                                                      as referenced in the American Society of                 rulemaking (NOPR). DOE welcomes                       may be publicly available, such as
                                                      Heating, Refrigerating and Air-                          written comments and data from the                    information that is exempt from public
                                                      Conditioning Engineers (ASHRAE)                          public on any subject related to the test             disclosure.
                                                      Standard 90.1 (ASHRAE Standard 90.1),                    procedures for this equipment,                          The docket Web page can be found at:
                                                      the U.S. Department of Energy (DOE) is                   including topics not specifically raised              https://www.regulations.gov/docket?D
                                                      initiating a data collection process to                  in this RFI.                                          =EERE-2017-BT-TP-0018. The docket
                                                      consider amendments to DOE’s test                        DATES: Written comments, data, and                    Web page will contain simple
                                                      procedures for commercial package air                    information are requested and will be                 instructions on how to access all
                                                      conditioning and heating equipment                       accepted on or before August 24, 2017.                documents, including public comments,
                                                      with test procedure updates included in                                                                        in the docket. See section III of this
                                                                                                               ADDRESSES: Interested persons are
                                                      ASHRAE Standard 90.1–2016—                                                                                     document, Public Participation, for
                                                                                                               encouraged to submit comments using
                                                      specifically, those evaporatively-cooled                                                                       information on how to submit
                                                                                                               the Federal eRulemaking Portal at
                                                      commercial unitary air conditioners                                                                            comments through
                                                                                                               https://www.regulations.gov. Follow the
                                                      (ECUACs), water-cooled commercial                                                                              www.regulations.gov.
                                                                                                               instructions for submitting comments.
                                                      unitary air conditioners (WCUACs), and                   Alternatively, interested persons may                 FOR FURTHER INFORMATION CONTACT: Ms.
                                                      air-cooled commercial unitary air                        submit comments, identified by docket                 Catherine Rivest, U.S. Department of
                                                      conditioners (ACUACs) which have a                       number EERE–2017–BT–TP–0018, by                       Energy, Office of Energy Efficiency and
                                                      rated cooling capacity greater than or                   any of the following methods:                         Renewable Energy, Building
                                                      equal to 65,000 Btu/h and less than                         • Federal eRulemaking Portal:                      Technologies Office, EE–5B, 1000
                                                      760,000 Btu/h; and all classes of                        www.regulations.gov. Follow the                       Independence Avenue SW.,
                                                      computer room air conditioners                           instructions for submitting comments.                 Washington, DC 20585–0121.
                                                      (CRACs); as well as to consider adopting                    • Email: CommACHeatingEquipCat                     Telephone: (202) 586–7335. Email:
                                                      a new test procedure for dedicated                       2017TP0018@ee.doe.gov. Include EERE–                  ApplianceStandardsQuestions@
                                                      outdoor air systems (DOASes),                            2017–BT–TP–0018 in the subject line of                ee.doe.gov.
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      equipment covered by ASHRAE                              the message.                                            Mr. Eric Stas, U.S. Department of
                                                      Standard 90.1 for the first time. In                        • Postal Mail: Appliance and                       Energy, Office of the General Counsel,
                                                      response to other statutory requirements                 Equipment Standards Program, U.S.                     GC–33, 1000 Independence Avenue
                                                      for DOE to review its test procedures at                 Department of Energy, Building                        SW., Washington, DC 20585. Telephone:
                                                      least once every seven years, DOE is                     Technologies Office, Mailstop EE–5B,                  (202) 586–9507. Email: Eric.Stas@
                                                      also reviewing its test procedures for                   Test Procedure RFI for Commercial                     hq.doe.gov.
                                                      ECUACs and WCUACs with a rated                           Package Air Conditioning and Heating                    For further information on how to
                                                      cooling capacity less than 65,000 Btu/h,                 Equipment, Docket No. EERE–2017–BT–                   submit a comment, or review other
                                                      as well as all classes of variable                       TP–0018 and/or RIN 1904–AD93, 1000                    public comments and the docket,


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00001   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34428                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      contact the Appliance and Equipment                         g. Purge Water Settings (ECUAC)                    Act include definitions (42 U.S.C. 6311),
                                                      Standards Program staff at (202) 586–                       h. Condenser Spray Pumps (ECUAC)                   energy conservation standards (42
                                                      6636 or by email: ApplianceStandards                        i. Additional Steps To Verify Proper               U.S.C. 6313), test procedures (42 U.S.C.
                                                                                                                     Operation (ECUAC)                               6314), labeling provisions (42 U.S.C.
                                                      Questions@ee.doe.gov.
                                                                                                                  D. Test Procedure for Variable Refrigerant
                                                      SUPPLEMENTARY INFORMATION:                                     Flow Multi-Split Air Conditioners and
                                                                                                                                                                     6315), and the authority to require
                                                                                                                     Heat Pumps                                      information and reports from
                                                      Table of Contents                                                                                              manufacturers (42 U.S.C. 6316).
                                                                                                                  1. Energy Efficiency Descriptors
                                                      I. Authority and Background                                 2. Representativeness and Repeatability               Federal energy efficiency
                                                      II. Discussion                                              3. Test Method                                     requirements for covered equipment
                                                         A. Test Procedure for Computer Room Air                  a. Transient Testing: Oil Recovery Mode            established under EPCA generally
                                                            Conditioners                                          b. Airflow Setting and Minimum External            supersede State laws and regulations
                                                         1. Scope                                                    Static Pressure                                 concerning energy conservation testing,
                                                         a. Computer Room Cooling Application                     c. Condenser Head Pressure Controls                labeling, and standards. (See 42 U.S.C.
                                                         b. Configurations                                        d. Air Volume Rate for Non-Ducted Indoor
                                                         2. Energy Efficiency Descriptor
                                                                                                                                                                     6316(a) and (b); 42 U.S.C. 6297) DOE
                                                                                                                     Units                                           may, however, grant waivers of Federal
                                                         a. Integrated Efficiency Metrics                         e. Secondary Test Method
                                                         b. Part-Load Operation Due to Unit                       f. Heat Recovery
                                                                                                                                                                     preemption for particular State laws or
                                                            Oversizing                                            4. Representations                                 regulations, in accordance with the
                                                         c. Operation Modes Other Than Standard                   a. Tested Combination                              procedures and other provisions of
                                                            Cooling Mode                                          b. Determination of Represented Values             EPCA. (42 U.S.C. 6316(b)(2)(D))
                                                         3. Industry Test Standards                               E. Other Test Procedure Topics                        The Federal testing requirements
                                                         a. Standard Models and Application                    III. Submission of Comments                           consist of test procedures that
                                                            Classes in AHRI 1360–2016                                                                                manufacturers of covered equipment
                                                         b. ASHRAE 37 and Secondary Method                     I. Authority and Background                           must use as the basis for: (1) Certifying
                                                         c. Minimum External Static Pressure                      Title III, part C 1 of the Energy Policy           to DOE that their equipment complies
                                                         d. Setting Indoor Airflow
                                                                                                               and Conservation Act of 1975 (EPCA or                 with the applicable energy conservation
                                                         e. Refrigerant Charging Instruction
                                                         B. Test Procedure for Dedicated Outdoor               the Act), Public Law 94–163 (42 U.S.C.                standards adopted pursuant to EPCA
                                                            Air Systems                                        6311–6317, as codified), added by                     (see 42 U.S.C. 6316(b); 42 U.S.C. 6296),
                                                         1. Definition                                         Public Law 95–619, title IV, section                  and (2) making representations about
                                                         a. Air Intake Source and Dehumidification             441(a), established the Energy                        the efficiency of that equipment (42
                                                            Capability                                         Conservation Program for Certain                      U.S.C. 6314(d)). Similarly, DOE must
                                                         b. Reheat                                             Industrial Equipment, which includes                  use these test procedures to determine
                                                         2. Energy Efficiency Descriptors                      provisions covering the types of                      whether the equipment complies with
                                                         a. Dehumidification Metric                            commercial heating and air                            relevant standards promulgated under
                                                         b. Heating Metric
                                                                                                               conditioning equipment that are the                   EPCA.
                                                         3. Test Method
                                                         a. Airflow                                            subject of this notice.2 This covered                    Under 42 U.S.C. 6314, EPCA sets forth
                                                         b. Liquid Flow                                        equipment includes small, large, and                  the general criteria and procedures DOE
                                                         c. Test Conditions                                    very large commercial package air                     is required to follow when prescribing
                                                         d. Tolerances                                         conditioning and heating equipment,                   or amending test procedures for covered
                                                         e. Capacity Measurement                               which specifically includes variable                  equipment. EPCA requires that any
                                                         f. Test Set-Up                                        refrigerant flow multi-split air                      prescribed or amended test procedures
                                                         C. Test Procedure for Air-Cooled, Water-              conditioners and heat pumps (VRF                      must be reasonably designed to produce
                                                            Cooled, and Evaporatively-Cooled                   multi-split systems),3 computer room air              test results which reflect energy
                                                            Equipment                                                                                                efficiency, energy use or estimated
                                                                                                               conditioners (CRACs), dedicated
                                                         1. Energy Efficiency Descriptor                                                                             annual operating cost of a covered
                                                         2. Addressing Changes to AHRI 340/360                 outdoor air systems (DOASes),
                                                         a. Head Pressure Controls                             evaporatively-cooled commercial                       equipment during a representative
                                                         b. Refrigerant Charging Requirements                  unitary air conditioners (ECUACs) less                average use cycle or period of use and
                                                         c. Adjustment for Different Atmospheric               than 760,000 Btu/h, water-cooled                      requires that the test procedure not be
                                                            Pressure Conditions                                commercial unitary air conditioners                   unduly burdensome to conduct. (42
                                                         d. Measurement of Condenser Air Inlet                 (WCUACs) less than 760,000 Btu/h, and                 U.S.C. 6314(a)(2))
                                                            Temperature (ACUAC and ECUAC)                      air-cooled commercial unitary air                        EPCA requires that the test
                                                         e. Tolerance of Tested Indoor Airflow                 conditioners (ACUACs) greater than or                 procedures for commercial package air
                                                            Relative to Rated Indoor Airflow                                                                         conditioning and heating equipment be
                                                                                                               equal to 65,000 Btu/h and less than
                                                            (ECUAC and WCUAC)                                                                                        those generally accepted industry
                                                         f. Vertical Separation of Indoor and                  760,000 Btu/h, all of which are
                                                                                                               addressed in this document. (42 U.S.C.                testing procedures or rating procedures
                                                            Outdoor Units
                                                                                                               6311(1)(B)–(D))                                       developed or recognized by the Air-
                                                         g. Outdoor Entering Air Wet-Bulb
                                                            Temperature (ECUAC)                                   Under EPCA, the energy conservation                Conditioning, Heating, and Refrigeration
                                                         h. Single-Zone Variable-Air-Volume and                program consists essentially of four                  Institute (AHRI) or by the American
                                                            Multi-Zone Variable-Air-Volume                     parts: (1) Testing, (2) labeling, (3)                 Society of Heating, Refrigerating and
                                                         3. Additional Test Method Issues                      Federal energy conservation standards,                Air-Conditioning Engineers (ASHRAE),
                                                         a. Length of Refrigerant Line Exposed to                                                                    as referenced in ASHRAE Standard
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                                                                               and (4) certification and enforcement
                                                            Outdoor Conditions                                 procedures. Relevant provisions of the                90.1, ‘‘Energy Standard for Buildings
                                                         b. Atmospheric Pressure Measurement                                                                         Except Low-Rise Residential Buildings’’
                                                         c. Consistency Among Test Procedures for                1 For editorial reasons, upon codification in the   (ASHRAE Standard 90.1), and that if
                                                            Small and Large ECUAC and WCUAC                    U.S. Code, part C was redesignated part A–1.          such an industry test procedure is
                                                            Equipment Classes
                                                         d. Make-Up Water Temperature (ECUAC)
                                                                                                                 2 All references to EPCA in this document refer
                                                                                                                                                                     amended, DOE must update its test
                                                                                                               to the statute as amended through the Energy          procedure to be consistent with the
                                                         e. Secondary Measurement Method for                   Efficiency Improvement Act of 2015, Public Law
                                                            Capacity (ECUAC)                                   114–11 (April 30, 2015).                              amended industry test procedure,
                                                         f. Piping Evaporator Condensate to                      3 Not including single-phase VRF less than 65,000   unless DOE determines, by rule
                                                            Condenser Pump (ECUAC)                             Btu/h.                                                published in the Federal Register and


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00002   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                                      Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                                                                           34429

                                                      supported by clear and convincing                                         EPCA also requires that DOE conduct                                     test procedure, DOE must determine the
                                                      evidence, that the amended test                                        an evaluation of test procedures at least                                  extent to which the proposed test
                                                      procedure would not meet the                                           once every seven years for each class of                                   procedure would alter the equipment’s
                                                      requirements in 42 U.S.C. 6314(a)(2)                                   covered equipment to determine if an                                       measured energy efficiency. If DOE
                                                      and (3) related to representative use and                              amended test procedure would more                                          determines that the amended test
                                                      test burden. (42 U.S.C. 6314(a)(4))                                    accurately or fully comply with the                                        procedure would alter the measured
                                                         ASHRAE Standard 90.1 was updated                                    requirements in 42 U.S.C. 6314(a)(2)                                       efficiency of the covered equipment,
                                                      on October 26, 2016,4 and this update                                  and (3). (42 U.S.C. 6314(a)(1)(A)) After                                   DOE must amend the applicable energy
                                                      made changes to the test procedure                                     this evaluation, DOE must either                                           conservation standard accordingly. (42
                                                      references in ASHRAE Standard 90.1–                                    prescribe amended test procedures or                                       U.S.C. 6314(a)(4)(C); 42 U.S.C. 6293(e))
                                                      2013 for CRACs, as well as ACUACs,                                     publish a notice in the Federal Register
                                                      ECUACs, and WCUACs with cooling                                        regarding its determination not to                                            Although ASHRAE Standard 90.1–
                                                      capacity ≥65,000 Btu/h and <760,000                                    amend test procedures. (42 U.S.C.                                          2016 did not include revisions to the
                                                      Btu/h.5 Additionally, ASHRAE                                           6314(a)(1)(A)(i) and (ii)) In either case,                                 test procedures for VRF equipment or
                                                      Standard 90.1–2016 added efficiency                                    if DOE determines that a test procedure                                    ECUACs and WCUACs with cooling
                                                      levels and a test procedure for DOAS.                                  amendment is warranted, it must                                            capacity <65,000 Btu/h, DOE is
                                                      These changes on the part of ASHRAE                                    publish proposed test procedures and                                       including such equipment in this RFI
                                                      trigger DOE’s obligation to review these                               offer the public an opportunity to                                         under DOE’s 7-year lookback authority.
                                                      test procedures pursuant to the                                        present oral and written comments on                                       The test procedures under review in this
                                                      requirements of EPCA.                                                  them. (42 U.S.C. 6314(b)) To amend a                                       RFI are shown in Table I.1.
                                                                               TABLE I.1—COMMERCIAL AIR CONDITIONING AND HEATING EQUIPMENT INCLUDED IN THE RFI
                                                                                                                             Review test procedure due to                                                                                               7-Year review
                                                                Equipment included in RFI                                   amendments to industry test or                                     Last test procedure (final rule)                         due (final rule)
                                                                                                                                  rating procedure?

                                                      CRAC .......................................................   Yes ..........................................................    77 FR 28928 (May 16, 2012) .................                     May 16, 2019.
                                                      DOAS .......................................................   Yes ..........................................................    N/A ..........................................................   N/A.
                                                      ECUAC .....................................................    Yes (≥65,000 Btu/h only*) .......................                 77 FR 28928 (May 16, 2012) .................                     May 16, 2019.
                                                      WCUAC ....................................................     Yes (≥65,000 Btu/h only*) .......................                 77 FR 28928 (May 16, 2012) .................                     May 16, 2019.
                                                      ACUAC ≥ 65,000 Btu/h** .........................               Yes ..........................................................    80 FR 79655 (Dec. 23, 2015) .................                    Dec. 23, 2022.
                                                      VRF (except single-phase <65,000 Btu/                          No ............................................................   77 FR 28928 (May 16, 2012) .................                     May 16, 2019.
                                                       h***).
                                                        * DOE is considering ECUAC and WCUAC with cooling capacity less than 65,000 Btu/h in this rulemaking notice under its 7-year lookback au-
                                                      thority.
                                                        ** DOE will be considering ACUAC with cooling capacity less than 65,000 Btu/h under its 7-year lookback authority in a separate test proce-
                                                      dure rulemaking.
                                                        *** Single-phase VRF with rated cooling capacity less than 65,000 Btu/h are covered under DOE’s consumer product regulations for central air
                                                      conditioners.


                                                        Upon completion of this proceeding,                                  comment and information on the                                             Regulatory Costs,’’ Executive Branch
                                                      DOE expects to satisfy for all the                                     specific topics discussed below.                                           agencies such as DOE are directed to
                                                      equipment categories listed in Table I.1,                                                                                                         manage the costs associated with the
                                                                                                                             II. Discussion
                                                      both the requirements of EPCA                                                                                                                     imposition of expenditures required to
                                                      pertaining to DOE action prompted by                                      This RFI discusses each category of                                     comply with Federal regulations. See 82
                                                      amendments to industry test or rating                                  equipment under consideration in                                           FR 9339 (Feb. 3, 2017). Pursuant to that
                                                      procedures, as well as EPCA’s 7-year                                   separate sections set forth below. DOE                                     Executive Order, DOE encourages the
                                                      review requirements. In support of its                                 seeks input to aid in the development of                                   public to provide input on measures
                                                      test procedures, DOE conducts in-depth                                 the technical and economic analyses                                        DOE could take to lower the cost of its
                                                      technical analyses of publicly-available                               regarding whether amended test                                             regulations applicable to the
                                                      test standards and other relevant                                      procedures for each category of                                            commercial equipment addressed in
                                                      information. DOE continually seeks data                                equipment may be warranted.                                                this notice consistent with the
                                                      and public input to improve its testing                                Specifically, DOE is requesting                                            requirements of EPCA.
                                                      methodologies to more accurately reflect                               comment on any opportunities to                                               Within each section, DOE raises
                                                      customer use and to produce repeatable                                 streamline and simplify testing                                            relevant issues regarding scope,
                                                      results. In general, DOE is requesting                                 requirements for each category of                                          efficiency metric, and test method, with
                                                      comment and supporting data regarding                                  equipment discussed in this notice.                                        a focus on changes identified by review
                                                      representative and repeatable methods                                     Additionally, DOE welcomes                                              of the updated test procedures in
                                                      for measuring the energy use of the                                    comments on other issues relevant to                                       ASHRAE Standard 90.1–2016. As
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      equipment that is the subject of this RFI.                             the conduct of this rulemaking that may                                    required by statute, DOE is considering
                                                      As such, DOE is interested in feedback                                 not specifically be identified in this                                     amendments to the current test
                                                      on any aspect of the test procedures for                               document. In particular, DOE notes that                                    procedures (and in the case of DOAS,
                                                      the identified equipment, but it is                                    under Executive Order 13771,                                               adoption of a new test procedure) to be
                                                      especially interested in receiving                                     ‘‘Reducing Regulation and Controlling                                      consistent with those specified in
                                                        4 There is no publication date printed on                            found at https://www.ashrae.org/news/2016/ashrae-                          reaffirmation of the existing test procedure, and as
                                                      ASHRAE Standard 90.1–2016, but ASHRAE issued                           ies-publish-2016-energy-efficiency-standard.                               such, does not constitute a change requiring DOE
                                                                                                                               5 For water-source heat pumps, ASHRAE
                                                      a press release on October 26, 2016, which can be                                                                                                 action.
                                                                                                                             Standard 90.1–2016 included reference to a



                                                 VerDate Sep<11>2014        17:17 Jul 24, 2017      Jkt 241001       PO 00000      Frm 00003       Fmt 4702       Sfmt 4702       E:\FR\FM\25JYP1.SGM            25JYP1


                                                      34430                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      ASHRAE 90.1–2016, where possible.                        In March 2012, DOE published a                        extent of the use of such equipment for
                                                      Further, DOE requests comment on the                     supplemental notice of proposed                       computer room cooling.
                                                      benefits and burdens of adopting the                     rulemaking (SNOPR) refining its                          Issue CRAC–2: DOE seeks comment
                                                      industry test procedures referenced in                   proposed definition of ‘‘computer room                and data on whether a specific sensible
                                                      ASHRAE 90.1–2016, without                                air conditioner.’’ 77 FR 16769, 16772–                heat ratio could be selected that would
                                                      modification.                                            16773 (March 22, 2012). In response to                effectively and consistently distinguish
                                                                                                               this SNOPR, several stakeholders                      CRACs from other classes of commercial
                                                      A. Test Procedure for Computer Room                      commented about differences in                        package air conditioners. DOE also
                                                      Air Conditioners                                         performance features between CRACs                    seeks comment on any other design
                                                         DOE’s test procedure for CRACs, set                   and CUACs. Carrier commented that                     differences or performance features that
                                                      forth at 10 CFR 431.96, currently                        CRACs are designed to handle different                would help resolve this issue.
                                                      incorporates by reference ASHRAE 127–                    load characteristics, most notably by                 b. Configurations
                                                      2007, ‘‘Method of Testing for Rating                     focusing on sensible load and not latent
                                                      Computer and Data Processing Room                        cooling. (EERE–2011–BT–STD–0029,                         The following sections discuss
                                                      Unitary Air Conditioners’’, (omit section                Carrier, No. 28 at p. 1) Panasonic                    configurations of CRACs that DOE has
                                                      5.11), with additional provisions                        commented that CRACs have a different                 identified on the market and for which
                                                      indicated in 10 CFR 431.96(c) and (e).                   operating range and that they operate                 DOE is considering potential
                                                      The energy efficiency metric is sensible                 with tighter tolerances on temperature                modifications to its current test
                                                      coefficient of performance (SCOP) for all                and relative humidity than do CUACs.                  procedure.
                                                      CRAC equipment categories. ASHRAE                        (EERE–2011–BT–STD–0029, Panasonic,                    i. Airflow Direction and Mounting
                                                      90.1–2016 updated its test procedure                     No. 20 at pp. 68–69) Despite these                    Location
                                                      reference for CRACs from ASHRAE                          comments, DOE was unable to
                                                                                                               determine any specific requirements on                   DOE’s minimum efficiency standards
                                                      127–2007 to AHRI 1360–2016,                                                                                    for CRACs in 10 CFR 431.97 apply to
                                                      ‘‘Performance Rating of Computer and                     sensible load that would consistently
                                                                                                               differentiate CRACs from CUACs and                    down-flow and up-flow units, which is
                                                      Data Processing Room Air                                                                                       terminology typically applied to floor-
                                                      Conditioners’’, which in turn references                 allow it to incorporate performance
                                                                                                               characteristics into the CRAC definition.             mounted units. However, DOE’s test
                                                      ASHRAE 127–2012. This update on the                                                                            procedure for CRACs in 10 CFR 431.96
                                                      part of ASHRAE triggered DOE to                          Therefore, on May 16, 2012, DOE
                                                                                                               adopted the current definition for                    is not limited to floor-mounted units.
                                                      review its test procedure for CRACs. In                                                                        On January 15, 2015, DOE published a
                                                      addition, DOE is aware that the                          ‘‘computer room air conditioner’’ that
                                                                                                               distinguishes them from CUACs based                   final guidance document (‘‘January 2015
                                                      ASHRAE 127 committee is working on                                                                             Guidance Document’’) to clarify the
                                                      an updated version of that standard, and                 on application differences. 77 FR 28928,
                                                                                                               28947–28948 (May 16, 2012; ‘‘May 2012                 coverage of horizontal free-discharge
                                                      DOE may consider the updated version                                                                           CRACs under DOE’s regulations for
                                                      when it is available.                                    final rule’’).
                                                                                                                  A review of 1000 CRAC models in                    CRACs set forth in 10 CFR part 431.7 In
                                                         In order to ensure that potential                                                                           the January 2015 Guidance Document,
                                                                                                               DOE’s Compliance Certification
                                                      adoption of AHRI 1360–2016 as the                                                                              DOE clarified that while horizontal free-
                                                                                                               Management System (CCMS) shows that
                                                      DOE test procedure for CRACs would                                                                             discharge CRACs are not subject to the
                                                                                                               all of these models have a sensible heat
                                                      satisfy statutory requirements, the                                                                            energy conservation standards for
                                                                                                               ratio (SHR) above 80 percent. In
                                                      following sections consider issues                       contrast, commercial air conditioners                 CRACs, the 2012 test procedure final
                                                      related to the reduced scope of AHRI                     used for comfort cooling generally have               rule did not have an exception for any
                                                      1360–2016 relative to ASHRAE 127–                        SHRs between 65 percent and 80                        specific airflow direction (i.e., down-
                                                      2007, as well as updates in the industry                 percent. DOE notes that the indoor air                flow, up-flow or horizontal-flow) or
                                                      test standards to the test method and                    test condition for CUACs has a higher                 mounting type (i.e., floor-mount,
                                                      rating conditions. DOE also explores                     relative humidity than the test condition             ceiling-mount).8 Therefore, any
                                                      other CRAC-related issues including                      for CRACs. Therefore, the SHR for any                 manufacturer making representations of
                                                      definitions and the efficiency metric.                   air conditioner will be higher when                   the energy consumption of CRACs
                                                      1. Scope                                                 tested using the CRAC test condition                  (including ceiling-mounted ducted or
                                                                                                               than when using the CUAC test                         free-discharge units or horizontal free-
                                                      a. Computer Room Cooling Application                                                                           discharge units and all other equipment
                                                                                                               conditions. However, DOE is
                                                         The definition for ‘‘computer room air                considering whether a specific SHR                    that meets the CRAC definition) must
                                                      conditioner’’ in DOE’s regulations does                  (e.g., 80 percent at the test condition of            base these representations on tests
                                                      not include physical design differences,                 CRACs) would be sufficient to                         conducted according to the current DOE
                                                      component characteristics, or                            differentiate CRACs from other CUACs.                 test procedure. A manufacturer may
                                                      performance features that distinguish                       Issue CRAC–1: DOE requests                         request a test procedure waiver for a
                                                      CRACs from other commercial package                      comment on the extent to which models
                                                                                                                                                                       7 The January 2015 Guidance document can be
                                                      air conditioning and heating equipment                   of commercial package air conditioners                found as Document Number 2 in Docket Number
                                                      (e.g., CUACs) used for comfort cooling.6                 are marketed and/or installed for use in              EERE–2014–BT–GUID–0022.
                                                                                                               both comfort cooling and computer                       8 On October 7, 2015, DOE published a draft
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                        6 DOE defines ‘‘computer room air conditioner’’
                                                                                                               room cooling applications. DOE also                   guidance document (‘‘October 2015 Guidance
                                                      as a basic model of commercial package air-              seeks comment on whether there are                    Document’’) seeking comment concerning the
                                                      conditioning and heating equipment (packaged or                                                                coverage of ceiling-mount ducted and free-
                                                      split) that is: used in computer rooms, data             models rated for energy efficiency ratio              discharge CRACs. (The October 2015 Guidance
                                                      processing rooms, or other information technology        (EER) or seasonal energy efficiency ratio             document can be found as Document Number 3 in
                                                      cooling applications; rated for sensible coefficient     (SEER) and not SCOP that are used for                 Docket Number EERE–2014–BT–GUID–0022.) DOE
                                                      of performance (SCOP) and tested in accordance           computer room cooling—if so, DOE                      has not yet finalized this guidance with respect to
                                                      with 10 CFR 431.96, and is not a covered consumer                                                              ceiling-mounted ducted and free-discharge CRACs.
                                                      product under 42 U.S.C. 6291(1)–(2) and 6292. A          requests comment and data on the                      The draft guidance also took the position that such
                                                      computer room air conditioner may be provided                                                                  CRACs were not subject to standards, but the test
                                                      with, or have as available options, an integrated        the supplied air, and reheating function. 10 CFR      procedure did not have an exception for any
                                                      humidifier, temperature, and/or humidity control of      431.92.                                               specific airflow direction.



                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00004   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                          34431

                                                      basic model if it contains design                        portable unit marketed for computer                      Issue CRAC–7: DOE requests
                                                      features that prevent testing according                  room cooling that is rated with SCOP                  comment on whether there are other
                                                      to the DOE test procedure, or such                       and is not a covered consumer product                 configurations of commercial package
                                                      testing may generate results that are                    under 42 U.S.C. 6291(1)–(2) and 6292 to               air conditioners that are marketed for
                                                      unrepresentative of the true energy                      meet its definition of ‘‘computer room                computer room cooling applications and
                                                      consumption of the basic model. 10 CFR                   air conditioner.’’ DOE is considering                 that meet DOE’s definition for CRAC,
                                                      431.401. To date, DOE has not received                   amendments to its test procedure for                  beyond floor-mounted units (i.e., up-
                                                      any such waiver requests.                                computer room air conditioners to better              flow, down-flow, and horizontal
                                                         DOE notes that the scope of AHRI                      reflect usage in the field of portable                discharge), ceiling-mounted units,
                                                      Standard 1360–2016 (AHRI 1360–2016),                     units used for computer room cooling                  portable units, indoor single package
                                                      ‘‘2016 Standard for Performance Rating                   that are not covered consumer products,               units, rooftop units, and certain SPVUs.
                                                      of Computer and Data Processing Room                     as applicable.
                                                      Air Conditioners’’, the test procedure                                                                         2. Energy Efficiency Descriptor
                                                                                                                 Issue CRAC–4: DOE requests
                                                      referenced in ASHRAE 90.1–2016,                          comments on whether any specific                         When ASHRAE 90.1–2016 amended
                                                      excludes ceiling-mounted units, only                     provisions should be considered to                    its energy efficiency levels, it also
                                                      covering floor-mounted units. As stated                  address how to test portable units used               updated its test procedure from
                                                      in the October 2015 Guidance                             in computer room cooling applications,                ASHRAE 127–2007 to AHRI 1360–2016.
                                                      Document, ASHRAE 127–2007 can be                         such as whether they are typically                    AHRI 1360–2016 defines standard rating
                                                      used to test ceiling-mounted units. DOE                  ducted and, if so, what a representative              configurations and conditions and
                                                      understands that the ASHRAE 127                          minimum external static pressure (ESP)                provides additional requirements for
                                                      committee is considering additional                                                                            testing CRACs, but does not include a
                                                                                                               and return air temperature would be.
                                                      provisions that would apply specifically                                                                       method of test. Instead, AHRI 1360–
                                                      to ceiling-mounted equipment, but a                      iii. Single Package Non-Floor-Mounted                 2016 references ASHRAE 127–2012 as
                                                      revised ASHRAE 127 standard is not yet                   Air Conditioners                                      the method of test. This test procedure
                                                      available. For those CRACs not                                                                                 change also updated the ASHRAE 90.1
                                                                                                                  DOE identified several manufacturers
                                                      addressed by AHRI 1360–2016, DOE                                                                               efficiency metric for CRACs from SCOP
                                                                                                               that produce single package non-floor-
                                                      may consider continuing to reference                                                                           to net sensible coefficient of
                                                                                                               mounted air conditioners (other than
                                                      ASHRAE 127–2007 or updating to a                                                                               performance (NSenCOP). DOE’s current
                                                                                                               portable units) that are marketed
                                                      revised version of ASHRAE 127 when                                                                             efficiency metric for CRACs is SCOP. As
                                                                                                               specifically for cooling computer rooms,
                                                      published, if appropriate.                                                                                     compared with SCOP, the new metric
                                                                                                               telecommunication rooms, and data
                                                         Issue CRAC–3: DOE requests                                                                                  NSenCOP specifies different operating
                                                                                                               centers. DOE identified such air
                                                      comment on the appropriate test                                                                                conditions for water-cooled and glycol-
                                                                                                               conditioners designed for both interior               cooled models and adjusts the efficiency
                                                      procedure for ceiling-mounted CRACs,
                                                                                                               and exterior installation. Of the exterior-           to account for the energy use associated
                                                      considering that AHRI 1360–2016 does
                                                                                                               mount units DOE identified, some meet                 with the water or glycol pump. These
                                                      not address them, and the test burden
                                                                                                               DOE’s definition for ‘‘single package                 changes presumably result in a more
                                                      associated with any such procedure.
                                                                                                               vertical air conditioner’’ (one type of               accurate representation of the energy
                                                      ii. Three-Phase Portable Units                           single-package vertical unit (SPVU)),                 use associated with the equipment.
                                                         Several manufacturers market                          while others are rooftop units. All of                Because ASHRAE 90.1 changed the
                                                      portable units for commercial use in                     these identified models appear to meet                metric to NSenCOP, EPCA requires that
                                                      data centers and computer rooms. On                      DOE’s definition for computer room air                DOE must consider updating to
                                                      June 1, 2016, under its authority for                    conditioners. Therefore, DOE is                       NSenCOP as well. For completeness,
                                                      regulating consumer products, DOE                        considering whether amendments are                    DOE reviews other issues related to
                                                      published a final rule that established a                needed in its test procedure for CRACs                efficiency metrics for CRACs in this
                                                      test procedure for portable air                          to better reflect the in-field energy use             section, including: (1) Integrated
                                                      conditioners. 81 FR 35242. In addition,                  and installation practices of single-                 efficiency metrics; (2) part-load
                                                      DOE issued a final rule to establish                     package non-floor-mounted air                         operation due to unit oversizing; and (3)
                                                      energy conservation standards for                        conditioners used for computer room                   operation modes other than standard
                                                      portable air conditioners. In a final                    cooling.                                              cooling mode. If DOE ultimately decides
                                                      determination published on April 18,                        Issue CRAC–5: DOE seeks information                to change its metric from SCOP to
                                                      2016, DOE established a definition for                   on the extent to which single-package                 NSenCOP, DOE would need to develop
                                                      ‘‘portable air conditioner’’ that excludes               non-floor-mounted air conditioners are                a crosswalk analysis to translate DOE’s
                                                      units that use three-phase power as a                    used in computer room applications.                   existing standards—which are in terms
                                                      means of differentiating the portable air                   Issue CRAC–6: DOE seeks comment                    of SCOP—to the NSenCOP metric.
                                                      conditioners that are consumer products                  on whether special test procedure
                                                      (and thus determined to be covered                       provisions should be developed for                    a. Integrated Efficiency Metrics
                                                      products) from those that could                          different kinds of single package non-                   ASHRAE 127–2007 includes the
                                                      normally not be used in residential                      floor-mounted air conditioners that are               integrated efficiency metric, adjusted
                                                      applications. 81 FR 22514, 22519–                        used for computer room cooling,                       sensible coefficient of performance
                                                      22520. DOE identified several models of                  including: (1) Whether such units are                 (ASCOP), which is calculated based on
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      portable units that are marketed for                     typically installed with supply/return                the SCOPs at four different rating
                                                      commercial computer room cooling                         air ducting; and (2) whether the test set-            conditions (A, B, C, and D), representing
                                                      applications and use three-phase power                   up described in ANSI/ASHRAE 37–                       different ambient conditions, with
                                                      instead of single-phase power. This                      2009, ‘‘Methods of Testing for Rating                 weightings for the SCOP at each rating
                                                      equipment does not meet DOE’s                            Electrically Driven Unitary Air-                      condition based on the climate at a
                                                      definition for ‘‘portable air conditioner’’              Conditioning and Heat Pump                            specific location. ASHRAE 127–2012
                                                      and is not subject to DOE’s current test                 Equipment,’’ (ASHRAE 37–2009) is                      and AHRI 1360–2016 include an
                                                      procedures or standards for portable air                 appropriate and if any additional test                updated integrated efficiency metric,
                                                      conditioners. DOE considers any                          set-up provisions would be needed.                    integrated net sensible coefficient of


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00005   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34432                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      performance iNSenCOP, instead of                           Issue CRAC–9: DOE requests                          conditions and additional requirements
                                                      ASCOP. There are differences between                     information on the range of typical field             for testing CRACs, but does not include
                                                      ASCOP and iNSenCOP, similar to those                     load levels for CRACs at conditions                   a method of test. Instead, AHRI 1360–
                                                      between SCOP and NSenCOP, but both                       close to or at the maximum ambient                    2016 references ASHRAE 127–2012 to
                                                      are weighted averages of sensible-                       outdoor air temperature conditions                    conduct the test. Consequently, DOE
                                                      capacity-based efficiencies measured for                 specified in the DOE test procedure for               will consider adopting both industry
                                                      operation at different ambient                           various unit capacities. DOE seeks input              test standards. In the following sections,
                                                      conditions.                                              on typical rules of thumb for oversizing              DOE discusses specific test procedure-
                                                         The ASCOP and iNSenCOP test                           and whether the issues of oversizing of               related issues and questions regarding
                                                      methods in ASHRAE 127–2007,                              this equipment should be addressed in                 ASHRAE 127–2012 and AHRI 1360–
                                                      ASHRAE 127–2012, and AHRI 1360–                          the efficiency metric.                                2016.
                                                      2016 require units to maintain a
                                                      constant sensible cooling capacity at                    c. Operation Modes Other Than                         a. Standard Models and Application
                                                      lower ambient temperatures. However,                     Standard Cooling Mode                                 Classes in AHRI 1360–2016
                                                      it is not clear how the lower-ambient                       Many CRACs operate in air                             Indoor floor-mounted CRACs can be
                                                      tests are to be conducted. As the                        circulation mode. DOE understands that                installed in different configurations,
                                                      ambient temperature decreases, the                       redundant units are usually installed in              which vary by direction of airflow and
                                                      maximum cooling capacity of a CRAC                       the computer room, and some of the                    connections (e.g., raised floor plenum,
                                                      will inherently increase. ASHRAE 127–                    redundant units can be controlled to                  ducted, free air). Instead of specifying
                                                      2012 does not provide guidance                           operate in air circulation mode for better            test conditions for all possible
                                                      regarding how the unit should be                         air movement. In this mode, the direct                combinations, AHRI 1360–2016
                                                      controlled in order to deliver the same                  expansion refrigerant system is shut                  includes the concept of ‘‘standard
                                                      amount of sensible cooling as its                        down, and only evaporator blowers and                 models’’ that characterize common
                                                      capacity increases for the lower-ambient                 controls are on. DOE is considering                   configurations and specify standard
                                                      tests.                                                   whether the energy consumption of air                 rating conditions (e.g., external static
                                                         Issue CRAC–8: DOE requests                            circulation mode should be considered                 pressure, return air temperature) for
                                                      comment on whether DOE should                            in the CRAC energy efficiency metric.                 each style of indoor floor-mounted
                                                      consider adopting an integrated                             Issue CRAC–10: DOE seeks comment                   CRAC. Table C.1 of Appendix C of AHRI
                                                      efficiency metric (e.g., iNSenCOP). Also                 on the conditions under which CRACs                   1360–2016 defines four different
                                                      if so, DOE requests comment on how the                   will operate in air circulation mode (i.e.,           standard models: (1) Down-flow (with
                                                      requirement to maintain a constant                       operating the indoor fan without                      raised floor plenum discharge and free
                                                      sensible cooling capacity associated                     actively cooling) in the field, whether               air return); (2) horizontal-flow (with free
                                                      with the iNSenCOP test procedure                         each CRAC switches automatically                      air discharge and free air return); (3) up-
                                                      should be implemented during testing.                    between standard cooling mode and air                 flow ducted (with ducted discharge and
                                                                                                               circulation mode, and if so, the time                 free air return); and (4) up-flow non-
                                                      b. Part-Load Operation Due to Unit                       percentage that CRACs operate in such                 ducted (with free air discharge and free
                                                      Oversizing                                               circulation mode. DOE also seeks                      air return). AHRI 1360–2016 also
                                                         CRACs typically operate at part-load                  comment on what fan setting(s) is used                specifies which of the four standard
                                                      (i.e., less than designed full cooling                   for air circulation mode and whether                  model test set-ups and standard rating
                                                      capacity) in the field. Reasons for this                 DOE should consider this energy use in                conditions apply for down-flow,
                                                      may include, but are not limited to,                     the CRAC efficiency metric.                           horizontal-flow, and up-flow CRACs.
                                                      redundancy in installed units to prevent                                                                       For example, down-flow units are tested
                                                      server shutdown if a CRAC unit stops                     3. Industry Test Standards
                                                                                                                                                                     with a raised floor plenum discharge
                                                      working, and server room designers                          In its test procedure for CRACs, DOE               and a free air return.
                                                      building in extra cooling capacity to                    currently incorporates by reference                      DOE notes that for up-flow CRACs,
                                                      accommodate additional server racks in                   ASHRAE 127–2007 (omitting section                     AHRI 1360–2016 includes two standard
                                                      the future. At part-load, single-speed                   5.11). 10 CFR 431.96. As mentioned                    models with associated standard rating
                                                      systems cycle on and off to match the                    previously, ASHRAE published an                       conditions, one for ducted discharge
                                                      cooling requirement, while variable                      updated version of this test standard in              connections and one for free air
                                                      speed systems might operate at a                         2012, ASHRAE 127–2012. ASHRAE                         discharge. However, connection
                                                      different speed, but both control                        127–2012 includes several                             variations are characteristics of
                                                      strategies change performance as                         modifications from ASHRAE 127–2007,                   installations. A given up-flow unit
                                                      compared to full-load operation. While                   which are discussed in the following                  could be installed either with or without
                                                      the DOE test procedure measures                          sections. DOE is aware that ASHRAE is                 a duct. DOE’s research has not revealed
                                                      performance at full-load, DOE estimated                  working to update ASHRAE 127–2012,                    that up-flow CRACs have physical
                                                      in its May 2012 final rule analysis that                 and DOE may consider the newer                        characteristics that clearly distinguish
                                                      CRAC units operate on average at a                       version of the test standard if it is                 them as ducted or non-ducted models.
                                                      sensible load of 65 percent of the full-                 published during the course of this                   Hence, it is not clear which of the AHRI
                                                      load sensible capacity. (EERE–2011–                      rulemaking. As discussed previously,                  1360–2016 up-flow standard model
                                                      BT–STD–0029–0021, pp. 4–15, 4–16).                       DOE is also aware that the referenced                 requirements would be used for testing.
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      This may indicate a difference between                   industry test procedure in ASHRAE                        Issue CRAC–11: DOE requests
                                                      DOE test procedure operating                             Standard 90.1–2016 has changed to                     comment on what equipment
                                                      requirements and typical field                           AHRI 1360–2016. The scope of AHRI                     characteristics can be used to determine
                                                      operation. Therefore, DOE is                             1360–2016 covers only floor-mounted                   whether up-flow CRACs should be
                                                      considering whether this practice of                     computer and data processing room air                 tested as ducted or non-ducted models.
                                                      oversizing should be factored into a                     conditioners, including up-flow, down-                DOE also requests comments on
                                                      CRAC efficiency metric to the extent                     flow, and horizontal-flow units. AHRI                 whether up-flow units can be sold for
                                                      that it would better represent an average                1360–2016 defines standard                            both up-flow ducted and up-flow non-
                                                      use cycle.                                               configurations and provides rating                    ducted applications and whether such


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00006   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                                Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                         34433

                                                      models are currently tested using both                   electric energy use of CRACs. DOE is                     For CRACs with cooling capacity less
                                                      ducted and non-ducted standard rating                    considering updating the DOE test                     than 135,000 Btu/h, DOE is considering
                                                      conditions.                                              procedure to clarify that the test method             whether its test procedure should
                                                         DOE also notes that, in addition to the               is based on ASHRAE 37–2009, except as                 require a secondary test method and
                                                      four standard models of floor-mounted                    modified or adjusted by ASHRAE 127–                   how agreement between the primary
                                                      CRACs, Table C.1 of AHRI 1360–2016                       2012 or AHRI 1360–2016.                               and secondary methods should be
                                                      also includes many additional                               Issue CRAC–14: DOE seeks comment                   evaluated. DOE is also considering
                                                      combinations of connections, referred to                 on whether the test method of ASHRAE                  whether the primary and secondary
                                                      as application configurations, but does                  37–2009 is appropriate for measuring                  tests should be based on total cooling
                                                      not provide standard rating conditions                   capacity, sensible capacity, and electric             capacity or sensible cooling capacity.
                                                      for these configurations.                                energy use for all configurations of                  Basing these tests on sensible cooling
                                                         Issue CRAC–12: DOE requests                           CRACs (including configurations for                   capacity may be more appropriate
                                                      confirmation that, although floor-                       which DOE does not currently prescribe                because it is the basis of the CRAC
                                                      mounted CRACs may be sold to be                          energy conservation standards).                       efficiency metric in both ASHRAE
                                                      installed in multiple configurations, all                   Table 2b in section 8 of ASHRAE 37–                Standard 90.1 and the current Federal
                                                      models are capable of being tested as                    2009 includes test operating tolerances               standard.
                                                      one of the four standard models                          (maximum allowable observed range)                       Issue CRAC–16: DOE seeks comment
                                                      identified in Table C.1 of AHRI 1360–                    and condition tolerances (maximum                     on whether a secondary test is
                                                      2016.                                                    variation of the average from a specified             appropriate for testing CRACs, for what
                                                         AHRI 1360–2016 does not include                       test condition) for several parameters,               range of cooling capacity such a
                                                      standard models or standard rating                       including air and fluid temperatures, in              requirement should apply for CRACs,
                                                      conditions for ceiling-mount or non-                     order to reduce the uncertainty of the                how the requirement should be applied
                                                      floor mount CRACs. The current DOE                       measurement of cooling capacity,                      (given that most secondary test methods
                                                      test procedure, which incorporates by                    heating capacity, and/or energy use of                measure total rather than sensible
                                                      reference ASHRAE 127–2007, specifies                     air conditioners or heat pumps.                       capacity), and what level of agreement
                                                      different test operating conditions (e.g.,               However, this section of ASHRAE 37–                   (in percent) should be required. DOE is
                                                      different external static pressure) than                 2009 is not explicitly referenced by the              also interested in detailed information
                                                      AHRI 1360–2016.                                          CRAC industry test standards. Section                 on whether there would be a significant
                                                         Issue CRAC–13: DOE requests                           5.1 of ASHRAE 127–2007 and section                    additional test burden resulting from a
                                                      comment on whether the test                              5.2.1 of ASHRAE 127–2012 only                         secondary test—and if so, the nature
                                                      requirements of ASHRAE 127–2007 are                      include an operation tolerance for the                and extent of that burden.
                                                      representative of average use cycles for                 room temperature, and no versions of                     Many CRACs have compressors
                                                      ceiling-mount and other non-floor-                       ASHRAE 127 or AHRI 1360 include any                   housed in their indoor units. ASHRAE
                                                      mounted CRACs. If not, DOE requests                      other tolerances. DOE considers the                   37–2009 specifies modification of the
                                                      comment on which, if any, of the test                    tolerances of Table 2b of ASHRAE 37–                  indoor enthalpy method as depicted in
                                                      requirements of AHRI 1360–2016 would                     2009 to be relevant for CRACs and                     its Figure 3, Calorimeter air enthalpy
                                                      more appropriately represent average                     important to reduce variability of key                test method arrangement, for capturing
                                                      use cycles for such CRACs.                               CRAC performance measurements.                        the impact of compressor heat on the
                                                                                                                  Issue CRAC–15: DOE requests                        capacity measurement. However, none
                                                      b. ASHRAE 37 and Secondary Method
                                                                                                               comment on whether any operating or                   of the industry test standards explicitly
                                                         ASHRAE 127–2007 references ANSI/                      condition tolerances included in Table                call for using this test set-up for CRAC
                                                      ASHRAE 37–2005, ‘‘Methods of Testing                     2b in section 8 of ASHRAE 37–2009 are                 indoor units to take into consideration
                                                      for Rating Unitary Air-Conditioning and                  not appropriate for CRACs. If any are                 the cooling capacity reduction
                                                      Heat Pump Equipment’’ (ASHRAE 37–                        not appropriate, DOE requests an                      associated with compressor heat.
                                                      2005), while 127–2012 and AHRI 1360–                     explanation as to why and suggestions                    Issue CRAC–17: DOE requests
                                                      2016 reference the updated version,                      on how the tolerances should be                       comment on whether it is appropriate to
                                                      ASHRAE 37–2009. ASHRAE 37–2005                           changed.                                              incorporate the impact of compressor
                                                      and the updated ASHRAE 37–2009                              Section 7.2.1 of ASHRAE 37–2009                    heat in sensible capacity measurements
                                                      describe test methods for measuring                      requires that when testing equipment                  for CRACs with compressors housed in
                                                      cooling capacity, heating capacity, and                  with a total cooling capacity less than               their indoor units. DOE requests that the
                                                      electrical energy use of air conditioners                135,000 Btu/h, simultaneous capacity                  comments provide an explanation as to
                                                      and heat pumps. However, it is not clear                 tests using the indoor air enthalpy                   why it is or is not appropriate, and
                                                      whether the industry test standards for                  method and one other applicable                       whether the answer depends on the
                                                      CRACs reference specific provisions or                   method must be conducted.                             specific CRAC configuration.
                                                      all of the provisions of ASHRAE 37–                      Specifically, these other test methods
                                                      2005 or ASHRAE 37–2009.9 No                              include the outdoor air enthalpy                      c. Minimum External Static Pressure
                                                      alternate methods for determining                        method, the compressor calibration                       ASHRAE 127–2007, ASHRAE 127–
                                                      cooling capacity are included in                         method, the refrigerant enthalpy                      2012, and AHRI 1360–2016 all contain
                                                      ASHRAE 127 or AHRI 1360. Therefore,                      method, and the outdoor liquid coil                   different minimum external static
                                                      DOE expects that manufacturers do use                    method. Table 1 in section 7 of                       pressure (ESP) levels and categories, as
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      the test methods of ASHRAE 37–2005 or                    ASHRAE 37–2009 specifies which of                     indicated in Table II.1. In ASHRAE 127–
                                                      ASHRAE 37–2009 to determine cooling                      these test methods are applicable for                 2012, the minimum ESP levels are the
                                                      capacity, sensible cooling capacity, and                 each equipment configuration and                      same as for ASHRAE 127–2007, but
                                                                                                               method of heat rejection in cooling                   ASHRAE 127–2012 defines ‘‘ducted
                                                         9 For example, in ASHRAE 127–2007, the                mode. Section 10.1.2 of ASHRAE 37–                    systems’’ as ‘‘air conditioners intended
                                                      reference to ASHRAE 37–2005 is located under a           2009 requires that the total cooling                  to be connected to supply and/or return
                                                      subsection 5.1.4.5.2 titled, ‘‘Raised Floor Plenum
                                                      Systems’’ which is located under section 5.1.4.5
                                                                                                               capacity calculated from the two                      ductwork’’ instead of ‘‘to supply and
                                                      titled ‘‘External Resistance, Ducted Connected,          simultaneously conducted methods                      return ductwork,’’ as specified in
                                                      Floor Plenum and Free Air Discharge.’’                   agree within 6.0 percent.                             ASHRAE 127–2007.


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00007   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34434                       Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                                                                     TABLE II.1—EXTERNAL STATIC PRESSURE REQUIREMENTS
                                                                                                                                                                                                                                                 Minimum ESP
                                                                       Test standard                                                                              CRAC Category                                                                    (in. w.c.)

                                                      ASHRAE 127–2007 and ASHRAE 127–                          Ducted:
                                                       2012.                                                        Net Sensible Capacity < 20 kW ............................................................................                            0.8
                                                                                                                    Net Sensible Capacity ≥ 20 kW ............................................................................                            1.0
                                                                                                               Free Discharge .............................................................................................................               0.0
                                                      AHRI 1360–2016 ......................................    Up-flow Ducted:
                                                                                                               Net Sensible Capacity <65 kBtu/h ...............................................................................                           0.3
                                                                                                               Net Sensible Capacity ≥65 kBtu/h and <240 kBtu/h ...................................................                                       0.4
                                                                                                               Net Sensible Capacity ≥240 kBtu/h and <769 kBtu/h .................................................                                        0.5
                                                                                                               Horizontal and Up-flow Non-ducted .............................................................................                            0.0
                                                                                                               Down-flow .....................................................................................................................            0.2



                                                         DOE is considering the test                                  inlet and free-discharge mode. However,                                      For ACUACs with capacity ≥65,000
                                                      procedures and the ESP levels of AHRI                           this might not be representative of field                                  Btu/h, DOE established a requirement
                                                      1360–2016, but seeks input on the                               operation. The condenser fan for a                                         that the full-load indoor airflow rate
                                                      significant difference in the ESP values                        CRAC with a ducted condenser has to                                        must be within ±3 percent of the
                                                      of the different test standards.                                overcome the additional pressure drop                                      certified airflow. 80 FR 79655, 79671
                                                      Additionally, AHRI 1360–2016 does not                           of the ducts; thus, imposing a minimum                                     (Dec. 23, 2015; ‘‘December 2015 CUAC
                                                      include minimum ESP requirements for                            ESP requirement for testing may better                                     TP final rule’’). Tolerance for ESP in this
                                                      ceiling-mounted units. AHRI–1360–                               reflect field operating conditions than                                    test is ¥0.00/+0.05 in. w.c. In contrast,
                                                      2016 also made very significant changes                         testing the unit with free air inlet and                                   for consumer central air conditioners
                                                      to the ESPs for up-flow ducted and                              discharge. However, this could require                                     and heat pumps (CAC/HPs), the method
                                                      down-flow configurations compared to                            attaching an apparatus to allow                                            for setting indoor air volume rate for
                                                      ASHRAE 127–2012. DOE received no                                adjustment of ESP, which would add to                                      ducted units without variable-speed
                                                      data or information from ASHRAE                                 test burden. Alternatively, if a well-                                     constant-air-volume-rate indoor fans is a
                                                      indicating the rationale for the changes                        defined air duct set-up for indoor                                         multi-step process that addresses the
                                                      or why lower static pressures are more                          condensers could be developed (e.g.,                                       discrete-step fan speed control of these
                                                      representative of field performance.                            specific length and cross-sectional                                        units. In this method, (a) the air volume
                                                      Thus, DOE is particularly interested in                         dimensions for the inlet and/or outlet                                     rate during testing may not be higher
                                                      any information regarding the static                            air duct), a standardized airflow                                          than the certified air volume rate, but
                                                      pressures that are likely representative                        resistance could be imposed without                                        may be 10 percent less, and (b) the ESP
                                                      of all CRACs.                                                   requiring a similar connection and                                         during testing may not be lower than the
                                                         Issue CRAC–18: DOE requests                                  adjustment of the airflow and                                              minimum specified ESP, but may be
                                                      comment on whether the ESP levels                               measurement apparatus as used for                                          higher than the minimum if this is
                                                      required by AHRI 1360–2016 are                                  measurement of indoor airflow, which                                       required to avoid having the air volume
                                                      representative of field operation for                           could significantly reduce test burden.                                    rate overshoot its certified value. 81 FR
                                                      floor-mounted CRACs.                                                                                                                       36992, 37026 (June 8, 2016; ‘‘June 2016
                                                         Issue CRAC–19: DOE requests                                     Issue CRAC–21: DOE seeks comment
                                                                                                                      on how to set up the condenser air flow                                    CAC TP final rule’’).
                                                      information on whether the ESP levels                                                                                                        Issue CRAC–22: DOE seeks
                                                      required by ASHRAE 127–2012 are                                 when testing CRACs manufactured with
                                                                                                                                                                                                 information on how certified airflow is
                                                      representative of field operation for                           condenser air inlet and outlet
                                                                                                                                                                                                 achieved in laboratory testing of CRACs,
                                                      ceiling-mounted CRACs and for other                             connections and high-static condenser                                      both with indoor blowers that are
                                                      non-floor-mounted CRAC                                          fans, which indicate that such units can                                   continuously variable and for indoor
                                                      configurations, and if not, what a                              be installed indoors with the condenser                                    blowers that are adjustable in discrete
                                                      representative minimum ESP would be.                            air ducted to and from the outdoors.                                       steps. DOE also seeks comments on
                                                         DOE’s review of CRAC installation                            Additionally, DOE requests comment on                                      whether the tolerances for setting
                                                      manuals suggests that some up-flow                              whether some CRACs can be installed                                        airflow of commercial CUACs or of
                                                      units are installed with a plenum box                           with or without condenser ducting, and                                     CAC/HPs are appropriate for CRACs,
                                                      that redirects the airflow from the                             if so, how often these units are typically                                 and what tolerances would be
                                                      upwards direction to the front or rear.                         installed with condenser ducting. DOE                                      appropriate for airflow and ESP.
                                                         Issue CRAC–20: DOE requests                                  also seeks comment on whether certain
                                                      comment on the percentage of up-flow                            CRAC configurations are more likely to                                     e. Refrigerant Charging Instruction
                                                      CRAC installations in which a plenum                            be installed with condenser ducting.                                          Neither the ASHRAE nor the AHRI
                                                      box that redirects air from the upward                          d. Setting Indoor Airflow                                                  testing standards for CRACs include
                                                      direction to the front or rear would be                                                                                                    specific instructions for refrigerant
                                                      attached, and whether non-ducted units                            DOE currently requires manufacturers                                     charging. The June 2016 CAC TP final
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      are tested with or without this plenum.                         to certify the indoor airflow for CRACs.                                   rule provides a comprehensive
                                                         DOE identified several models of air-                        However, DOE’s test procedure and                                          approach for charging intended to
                                                      cooled CRACs that have an indoor                                industry test standards do not impose                                      improve test reproducibility. The
                                                      condenser and, therefore, may require                           tolerances on achieving the certified                                      approach indicates which set of
                                                      ducting of condenser air. Neither AHRI                          airflow and/or the minimum ESP during                                      installation instructions to use for
                                                      1360–2016 nor ASHRAE 127–2013                                   testing. The performance of any air                                        charging, explains what to do if there
                                                      address the possibility of condenser                            conditioner can be significantly affected                                  are no instructions, indicates that target
                                                      ducting, and accordingly, would call for                        by operation with indoor airflow that is                                   values of parameters are the centers of
                                                      testing such CRACs like others in free-                         very different from the intended airflow.                                  the ranges allowed by installation


                                                 VerDate Sep<11>2014     17:17 Jul 24, 2017   Jkt 241001      PO 00000      Frm 00008       Fmt 4702       Sfmt 4702      E:\FR\FM\25JYP1.SGM             25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                           34435

                                                      instructions, and specifies tolerances for               a small portion of the total airflow for              1. Definition
                                                      the measured values. 81 FR 36992,                        typical commercial air conditioners,                    As stated previously, DOE is
                                                      37030–37031. An approach that details                    usually less than 50 percent. When                    considering how to define ‘‘dedicated
                                                      methods such as these could improve                      operating in humid conditions, the                    outdoor air system.’’ Both AHRI 920–
                                                      the CRAC test method.                                    dehumidification load is a much larger                2015 and ASHRAE 198–2013 include
                                                        Issue CRAC–23: DOE requests                            percentage of total cooling load for a                definitions for DOAS. DOE may adopt
                                                      comments on what refrigerant charging                    DOAS than for a typical commercial air                one of these definitions, but it may also
                                                      requirements should be considered to                     conditioner. Additionally, compared to                adjust the definition to assure that it is
                                                      establish reproducible test results for                  a typical commercial air conditioner,                 clear and complete. The following
                                                      CRACs, and whether the approach                          the amount of total cooling (both
                                                      developed for CAC/HP products may be                                                                           sections address different aspects of the
                                                                                                               sensible and latent) is much greater per              definitions provided in the industry test
                                                      appropriate. Also, DOE seeks comments                    pound of air for a DOAS at design
                                                      on the typical operating conditions at                                                                         standards.
                                                                                                               conditions (i.e., the warmest/most
                                                      which the unit is charged in the field                   humid expected summer conditions),                    a. Air Intake Source and
                                                      and/or what conditions should be used                    and a DOAS is designed to                             Dehumidification Capability
                                                      to set refrigerant charge for testing                    accommodate greater variation in                         Both AHRI 920–2015 and ASHRAE
                                                      purposes.                                                entering air temperature and humidity.
                                                        Issue CRAC–24: DOE requests                                                                                  198–2013 define a DOAS as a product
                                                                                                               DOASes are typically installed in                     that dehumidifies 100-percent outdoor
                                                      comments on any other issues related to                  addition to a primary cooling system
                                                      the adoption of AHRI 1360–2016 as the                                                                          air to a low dew point. However, section
                                                                                                               (e.g., CUAC, VRF, chilled water system,               6.6 of ASHRAE 198–2013 provides
                                                      test procedure for CRACs.                                water-source heat pumps)—the DOAS                     requirements for dampers not used for
                                                      B. Test Procedure for Dedicated Outdoor                  conditions the outdoor ventilation air,               introducing outdoor air, suggesting that
                                                      Air Systems                                              while the primary system provides                     some DOAS units take in some
                                                                                                               cooling to balance building shell and                 percentage of return air. Accordingly,
                                                        DOASes appear to meet the EPCA
                                                                                                               interior loads and solar heat gain. DOE               DOE has identified models from
                                                      definition for ‘‘commercial package air
                                                                                                               is considering whether there is a need                multiple manufacturers that are
                                                      conditioning and heating equipment,’’ 10
                                                                                                               for definitions of ‘‘commercial central               advertised as DOASes, but which
                                                      and could be considered as a category
                                                                                                               air conditioners and central air                      incorporate a damper-controlled return
                                                      of that covered equipment. (42 U.S.C.
                                                                                                               conditioning heat pumps’’ and                         air inlet that allows return air to be
                                                      6311(8)(A)) However, DOE has
                                                                                                               ‘‘dedicated outdoor air systems’’ to                  mixed with outdoor air.
                                                      tentatively concluded that if DOASes
                                                                                                               clarify this distinction. If DOE                         CUACs also often incorporate a
                                                      are a category of ‘‘commercial package
                                                                                                               determines this necessary, it would do                damper to mix return air and outdoor
                                                      air conditioning and heating
                                                                                                               so through a future rulemaking                        air. Additionally, CUACs also can
                                                      equipment,’’ there are no existing DOE
                                                                                                               proceeding.                                           dehumidify 100-percent outdoor air,
                                                      test procedures or energy conservation
                                                      standards for that category of                              ASHRAE 90.1–2016 created separate                  although generally not to a dew point as
                                                      commercial package air conditioning                      equipment classes for DOAS units and                  low as DOASes. Hence, DOE is
                                                      and heating equipment. Specifically,                     set minimum efficiency levels using the               concerned that the dehumidification
                                                      DOE does not believe that DOAS are                       integrated seasonal moisture removal                  capability and/or the range of
                                                      among the commercial ‘‘central air                       efficiency (ISMRE) metric for all DOAS                percentage of return air flow may have
                                                      conditioners and central air                             classes and the integrated seasonal                   to be quantified to distinguish DOASes
                                                      conditioning heat pumps’’ for which                      coefficient of performance (ISCOP)                    and CUACs.
                                                      EPCA originally established standards                    metric for air-source heat pump and                      Issue DOAS–1: DOE requests
                                                      (42 U.S.C. 6313(a)(1)–(2), (7)–(9)), and                 water-source heat pump DOAS classes.                  information on the range of the
                                                      for which the current test procedure and                 Both metrics are measured in                          maximum percentage of return air
                                                      standards are codified in Table 1 to 10                  accordance with AHRI Standard 920–                    intake relative to total air flow of DOAS
                                                      CFR 431.96 and Tables 1–4 of 10 CFR                      2015, ‘‘Performance Rating of DX-                     models in order to determine whether
                                                      431.97 (as air conditioners and heat                     Dedicated Outdoor Air System Units’’                  the maximum return air percentage is an
                                                      pumps).                                                  (AHRI 920–2015). AHRI 920–2015                        important DOAS distinguishing feature.
                                                        Neither EPCA nor DOE defines                           references ASHRAE Standard 198–2013,                     Issue DOAS–2: DOE requests
                                                      commercial ‘‘central air conditioners                    ‘‘Method of Test for Rating DX-                       comment on the differences in
                                                      and central air conditioning heat                        Dedicated Outdoor Air Systems for                     dehumidification capabilities of CUACs
                                                      pumps.’’ DOASes operate similarly to                     Moisture Removal Capacity and                         and DOASes when operating with 100-
                                                      commercial central air conditioners and                  Moisture Removal Efficiency’’ (ASHRAE                 percent outdoor air. Specifically, DOE
                                                      central air conditioning heat pumps, in                  198–2013), as the method of test for                  seeks comment on whether a difference
                                                      that they provide space conditioning                     DOAS units.                                           can be quantified to be a clear
                                                      using a refrigeration cycle consisting of                   DOE must adopt the industry                        differentiating feature of DOASes—for
                                                      a compressor, condenser, expansion                       standard designated by ASHRAE 90.1                    example, can a specific dew point
                                                      valve, and evaporator. However,                          unless it is not consistent with EPCA                 criterion for a given set of outdoor air
                                                                                                               requirements. Accordingly, DOE is                     conditions be established that can be
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      DOASes are designed to provide 100
                                                      percent outdoor air to the conditioned                   considering the test methods of AHRI                  achieved by any DOAS, but that no
                                                      space, while outdoor air makes up only                   920–2015 and ASHRAE 198–2013, but                     conventional CUAC can achieve?
                                                                                                               may consider modifications of these test
                                                        10 Under the statute, ‘‘commercial package air         methods if necessary to fulfill the EPCA              b. Reheat
                                                      conditioning and heating equipment’’ means air-          requirements. In the following sections,                DOE is interested in determining how
                                                      cooled, water-cooled, evaporatively-cooled, or           DOE reviews potential definitions and                 the ability to reheat dehumidified air
                                                      water-source (not including ground-water-source)
                                                      electrically operated, unitary central air
                                                                                                               efficiency metrics for DOAS, as well as               should be incorporated into the
                                                      conditioners and central air conditioning heat           questions regarding the test method in                definition of a DOAS. The AHRI 920–
                                                      pumps for commercial application.                        the industry standards.                               2015 definition requires that a DOAS


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00009   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34436                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      include reheat ‘‘capable of controlling                  920–2015 appears to be missing the                    measurement that is representative of an
                                                      the supply dry-bulb temperature of the                   supply air volume flow rate as a factor.              average use cycle for the tested
                                                      dehumidified air to the designed supply                     Issue DOAS–4: DOE requests                         equipment. (42 U.S.C. 6314(a)(2))
                                                      air temperature,’’ whereas the ASHRAE                    information to clarify the calculation                Section 6.4 of AHRI 920–2015 indicates
                                                      198–2013 definition indicates only that                  procedure for ISMRE. Specifically, DOE                that the weighting factors for the COPs
                                                      DOASes may have this functionality.                      requests input on which                               are derived from bin hour data to
                                                      The ASHRAE 198–2013 definition                           dehumidification test MRE should be                   represent a full year of operation.
                                                      indicates that the DOAS might also have                  used (and why), how and when the                         Issue DOAS–7: DOE seeks information
                                                      a supplemental heat system ‘‘for use                     supplementary heat penalty is applied,                about analysis of climate data relevant
                                                      when outdoor air requires heating                        and the basis for the supplementary heat              to the development of the ISCOP test
                                                      beyond the capability of the                             equation.                                             conditions and weighting factors in
                                                      refrigeration system and/or other heat                      While the primary functions of                     order to allow confirmation that the
                                                      transfer apparatus.’’ Supplemental                       DOASes are to provide ventilation and                 metric provides a measurement that is
                                                      heating is also mentioned in the note                    to dehumidify the outdoor air, the units              representative of an average use cycle
                                                      below the AHRI 920–2015 definition.                      also provide sensible cooling to the                  for DOAS heat pump equipment.
                                                         Issue DOAS–3: DOE requests                            supplied air stream. However, the                        ‘‘Integrated seasonal coefficient of
                                                      comment on whether and how reheating                     sensible cooling provided by the unit is              performance,’’ as defined in AHRI 920–
                                                      functionality should be included in the                  not accounted for as part of the MRE or               2015, is an energy efficiency metric for
                                                      DOAS definition. If reheat should be                     ISMRE efficiency metric. DOE is aware                 water-source heat pumps. However,
                                                      required for a unit to be considered a                   that the total sensible cooling provided              DOE notes that ASHRAE 90.1–2016
                                                      DOAS, DOE requests comment on                            may be significantly less than the latent             includes ISCOP minimum efficiency
                                                      whether a minimum reheat capacity                        cooling associated with removal of                    levels for air-source heat pumps
                                                      should be specified in the definition.                   moisture—for example, conditions C                    (heating mode) in Table 6.8.1–16 in
                                                      DOE also requests information to clarify                 and D of Tables 2 and 3 of AHRI 1360–                 addition to water-source heat pumps.
                                                      the difference between a reheat system                   2016 specify inlet air conditions already             ASHRAE 198–2013 section 10.9 claims
                                                      and a supplementary heat system in a                     cooler than the target 70 °F supply                   that its equations for calculating COP
                                                      DOAS—for example, if reheat is                           temperature—but sensible cooling may                  are for water-source heat pumps,
                                                      required for a DOAS, can it be a                         be important enough to consider for the               although the COP definition in ASHRAE
                                                      supplementary reheat system (i.e., one                   warmer test conditions.                               198–2013 does not exclude air-source
                                                      that uses a heat source other than warm                     Issue DOAS–5: DOE requests                         heat pumps, and the equations should
                                                      refrigerant or heat recovered from the                   comment on whether the DOAS                           apply equally well for air-source heat
                                                      return air)?                                             efficiency metric should also account                 pumps. Finally, DOE notes that tests
                                                                                                               for sensible cooling provided for                     conducted at 35 °F dry bulb temperature
                                                      2. Energy Efficiency Descriptors                         ventilation air during the cooling/                   for consumer central air conditioning
                                                      a. Dehumidification Metric                               dehumidification season.                              heat pumps (which are air-source)
                                                                                                                  The ISMRE metric is based on testing               consider the impacts of defrosting of the
                                                         ISMRE is a seasonal efficiency metric                 at four different operating conditions,               outdoor coil in the energy use
                                                      calculated based on moisture removal                     involving specification of both dry bulb              measurement (see section 3.9 of 10 CFR
                                                      efficiency (MRE) at four different                       and wet bulb outdoor temperature. A                   part 430, subpart B, appendix M), while
                                                      dehumidification rating conditions. The                  weighted average of the MRE                           defrost is not discussed at all in
                                                      weighted values are derived from bin                     measurements determined for the four                  ASHRAE 198–2013. Defrost has a real
                                                      hour data (i.e., temperature/humidity                    conditions is calculated to obtain                    impact on efficiency because of energy
                                                      data for a selection of representative                   ISMRE. DOE test procedures must                       use associated with defrost and because
                                                      cities indicating the number of hours of                 provide a measurement that is                         a system cannot continue to provide
                                                      occurrence of each ‘‘bin’’ representing a                representative of an average use cycle                heating during defrost operation,
                                                      defined range of temperature and                         for the tested equipment. (42 U.S.C.                  thereby reducing time-averaged
                                                      humidity) to represent seasonal                          6314(a)(2)) Among the considerations                  capacity. Hence, consideration of
                                                      operation. MRE is calculated as                          that might be relevant in defining the                defrost could provide a more field-
                                                      moisture removal capacity (MRC)                          test conditions and weighting factors is              representative measurement of
                                                      divided by the total energy input, as                    the fact that ventilation air must be                 performance.
                                                      described in ASHRAE 198–2013 section                     delivered to occupied spaces during                      Issue DOAS–8: DOE seeks input on
                                                      10.6.                                                    occupied hours, which would put more                  the calculation procedure for the COP of
                                                         DOE is seeking clarification on the                   emphasis on daytime hours for                         air-source heat pump DOASes,
                                                      calculation procedure for ISMRE.                         development of the metric.                            including whether testing for test
                                                      ASHRAE 198–2013 indicates measuring                         Issue DOAS–6: DOE seeks information                condition E of AHRI 920–2015 Table 2
                                                      MRE twice for each test condition, once                  about analysis of climate data relevant               (35 °F dry bulb/29 °F wet bulb) should
                                                      with reheat on and once with reheat off.                 to the development of the ISMRE test                  consider energy use associated with
                                                      AHRI 920–2015 does not specify which                     conditions and weighting factors in                   defrost.
                                                      of these values of MRE is used in the                    order to confirm that the metric                         The COP equation of ASHRAE 198–
                                                      calculation of ISMRE. AHRI 920–2015                      provides a measurement that is                        2013 section 10.9 uses the term qhp to
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      section 6.1.3.1 calls for a supplemental                 representative of an average use cycle                represent the heating capacity in the
                                                      heat penalty if the supply air                           for DOAS equipment.                                   COP calculation. This term does not
                                                      temperature is less than 70 °F, but the                                                                        appear in the nomenclature section, but
                                                      incorporation of this penalty into the                   b. Heating Metric                                     the subscript ‘‘hp’’ suggests that this
                                                      MRE equation is not clearly described.                      ISCOP is a seasonal energy efficiency              includes only heat provided by the heat
                                                      It is also not clear whether the ASHRAE                  descriptor calculated as the weighted                 pumping function of the DOAS unit.
                                                      198–2013 test method considers this                      average of heating COP determined for                 However, the equation defining qhp is
                                                      penalty. Finally, the equation for the                   two different heating rating conditions.              based on supply air temperature,
                                                      supplemental heat penalty in AHRI                        DOE test procedures must provide a                    suggesting that any of the possible


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00010   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                           34437

                                                      additional methods for providing heat                    how to set up for testing a unit with                 EATR measurement would represent an
                                                      (e.g., supplemental heat, heat recovery)                 multiple indoor fan speed options.                    unnecessary addition to test burden.
                                                      may contribute to qhp and thereby boost                    Issue DOAS–10: DOE requests input                     Issue DOAS–13: DOE seeks comments
                                                      COP by increasing the numerator of the                   on the appropriate selection of the
                                                                                                                                                                     on whether EATR should be included in
                                                      COP equation. The COP equation                           supply airflow rate for testing units that
                                                                                                                                                                     DOE’s test procedure for DOAS, and, if
                                                      includes only electric power input in                    can operate with a range of airflow rates.
                                                                                                               DOE requests information regarding                    so, how it should be used in
                                                      the denominator and does not include
                                                                                                               how manufacturers select the airflow                  determining DOAS ratings. DOE
                                                      energy use that might be associated with
                                                                                                               rate for testing and any data                         requests information on the range of
                                                      fuel-fired supplemental heat. In
                                                      addition, the supplemental heat penalty                  demonstrating the variation of DOAS                   return air leakage typical for energy
                                                      of AHRI 920–2015 section 6.1.3.1,                        unit performance over a range of                      recovery wheels used in DOASes.
                                                      which the section states applies to the                  installed airflow rates.                              b. Liquid Flow
                                                      heating test conditions as well as the                     Issue DOAS–11: DOE requests
                                                      dehumidification test conditions, seems                  comment on whether it would be                        i. Water Flow Rate for Water-Source
                                                      to penalize the COP calculation                          appropriate to develop a test that                    DOASes
                                                      excessively, because it does not indicate                includes part-load (reduced ventilation
                                                                                                               air) test points to quantify the efficiency              Neither AHRI 920–2015 nor ASHRAE
                                                      that the additional heating should be                                                                          198–2013 provides requirements for
                                                      added to the qhp of the COP equation.                    benefit of demand-controlled ventilation
                                                                                                               for DOASes that are capable of operating              outlet water temperature or water flow
                                                         Issue DOAS–9: DOE seeks input on                                                                            rate for water-cooled units. Instead,
                                                      the calculation for COP and how the                      with this control.
                                                                                                                                                                     AHRI 920–2015 specifies a standard
                                                      supplemental heat penalty is included.                   ii. Return Airflow                                    rating test water entering temperature in
                                                      DOE also seeks input on how the                             For testing DOAS units with energy                 Table 2 and requires in section 6.1.4.3
                                                      heating capacity and power/fuel                          recovery,11 Tables 2 and 3 in AHRI 920–               that the manufacturer specify a water
                                                      consumption of various supplemental                      2015 provide return airflow temperature               flow rate, unless it is controlled
                                                      heating sources are accounted for as part                conditions and indicate that they apply               automatically by the device. However,
                                                      of the COP equation and how DOAS                         to units with energy recovery at                      ANSI/AHRI 340/360–2007 with
                                                      manufacturers incorporate the impacts                    balanced airflow (i.e., tested with                   addenda 1 and 2, ‘‘Standard for
                                                      of these sources in their ISCOP                          supply airflow equal to exhaust airflow).             Performance Rating of Commercial and
                                                      calculations.                                            It is unclear what airflow streams                    Industrial Unitary Air-Conditioning and
                                                      3. Test Method                                           should be balanced, how to determine if               Heat Pump Equipment’’ (AHRI 340/
                                                                                                               they are balanced, and within what                    360–2007) and ANSI/AHRI 210/240–
                                                      a. Airflow
                                                                                                               tolerances they should be balanced.                   2008 with addenda 1 and 2, ‘‘Standard
                                                      i. Supply Airflow                                        DOE is considering clarifying the return              for Performance Rating of Unitary Air-
                                                                                                               airflow set-up procedures.                            Conditioning & Air-Source Heat Pump
                                                        Section 5.2.2 of AHRI 920–2015                            Issue DOAS–12: DOE requests
                                                      specifies instructions regarding supply                                                                        Equipment’’ (AHRI 210/240–2008),
                                                                                                               comment regarding how manufacturers                   which cover performance rating for
                                                      airflow rate. Section 5.2.2.1 of that                    who have tested heat recovery DOAS set
                                                      industry standard requires either use of                                                                       water-cooled commercial air-
                                                                                                               up return airflow for testing DOAS units              conditioning equipment, employ a
                                                      the supply airflow that occurs at the                    with energy recovery as prescribed by
                                                      minimum external static pressure of                                                                            different method. Both of these
                                                                                                               the AHRI 920–2015 test standard.
                                                      Table 4 or a manufacturer-specified                                                                            standards specify water inlet and outlet
                                                                                                               Further, DOE requests comment on
                                                      lower leaving airflow rate that occurs                                                                         temperatures for the standard rating
                                                                                                               whether balanced airflow is
                                                      with higher external static pressure.                    representative of field installation, and             conditions, rather than relying on
                                                      Section 5.2.2.3 of that industry standard                what ESP levels should be set up for the              manufacturers to determine water flow
                                                      further requires that the manufacturer                   return airflow.                                       rate. Further, both standards specify that
                                                      specify a single airflow for all tests.                                                                        the full-load water flow rate determined
                                                      However, many DOAS systems can                           iii. Exhaust Air Transfer Ratio                       for the standard rating conditions
                                                      operate over a range of airflow rates, and                  Exhaust air transfer ratio (EATR) is an            should also be used for IEER part-load
                                                      DOE expects that their indoor fans can                   indicator of the amount of air that leaks             rating conditions. DOE believes that
                                                      be set up with a range of speeds to                      from the return air side of the energy                these approaches to testing reflect the
                                                      accommodate the airflow range and the                    recovery wheel to the supply air side.                typical design temperature differential
                                                      variation in duct length in field                        Such leakage could increase the                       for cooling towers serving water-cooled
                                                      installations. Further, some DOAS                        apparent dehumidification provided by                 equipment, and a very common
                                                      systems are employed for demand                          a DOAS unit because the return air is                 approach for control of condenser water
                                                      ventilation use, for which reduced                       less humid than the outdoor air into                  pumps, and hence it is not clear why
                                                      airflow will likely be required for a                    which the return air could leak—thus,                 the same approach would not be
                                                      significant portion of the unit’s use.                   high leakage could boost the ISMRE                    adopted for water-cooled DOAS.
                                                      Such systems also are likely to have                     rating without providing any real
                                                      variable-speed indoor fans, whose speed                                                                           Issue DOAS–14: DOE requests
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                                                                               benefit. However, DOE recognizes that
                                                      settings for the test may also have to be                                                                      information on how condenser water
                                                                                                               such leakage may be low enough in
                                                      defined clearly. The performance of the                                                                        flow rates are set in the field and how
                                                                                                               most energy recovery wheels that the
                                                      DOAS may vary significantly from the                                                                           they are controlled at part load. DOE
                                                      low end to the high end of the rated                       11 DOAS units with energy recovery take in and      also requests comment on whether the
                                                      installation airflow range. DOE is                       discharge exhaust air, using a device such as an      provisions of section 6.1.4.3 of AHRI
                                                      concerned that the selected airflow rate                 energy recovery wheel that can transfer heat and      920–2015 provide sufficient guidance
                                                                                                               moisture from the exhaust air to the outdoor air,     regarding how to set up water flow for
                                                      may not provide a representative                         thereby preconditioning the outdoor air and
                                                      indication of field use, and that there                  reducing the load required to cool, dehumidify, or    DOASes with automatic water flow
                                                      may not be sufficient clarity regarding                  heat the air to the desired supply conditions.        control systems.


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00011   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34438                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      ii. Energy Consumption of Pumps and                      equipment classes certainly do reflect                iii. Water-Cooled Condensing and
                                                      Fans for Water-Source Condensers                         this advantage, with the ISMRE levels                 Ground-Source Equipment
                                                         AHRI 920–2015 offers Equation 1 for                   being 4.9 for water-cooled DOAS using                    Tables 2 and 3 in AHRI 920–2015
                                                      calculating the total pump effect (PE),                  cooling tower water and 6.0 for those                 include two categories for water-cooled
                                                      an estimate of the energy consumption                    using chilled water. Although the 6.0                 DOASes and three categories for heat
                                                      of non-integral water pumps (i.e.,                       ISMRE level for chilled-water-cooled                  pump DOASes. The test standard
                                                      pumps that are not part of the DOAS                      operation appears to be much more                     specifies a different set of inlet water/
                                                      unit and whose power consumption                         efficient, it does not include the energy             fluid temperatures for each category.
                                                      would, therefore, not already be part of                 use associated with the chiller system                The different categories and their
                                                      the measured power). Section 6.1.3 of                    required to deliver the chilled water at              associated rating conditions could
                                                      AHRI 920–2015 implies that this                          the specified 45 °F.                                  require some DOASes to be tested
                                                      calculation applies solely to water                         Issue DOAS–17: DOE requests                        separately as different basic models. For
                                                      pumps serving refrigerant-to-liquid heat                 comment on whether energy                             example, water-cooled DOASes that can
                                                      recovery devices—no indication is given                  contributions should be considered for                be operated with either chilled water or
                                                      whether the equation also applies for                    the chiller system of a water-cooled                  condenser water would have to be
                                                      pumps serving water-source or water-                     DOAS that is rated for use with chilled               tested and rated in both configurations.
                                                      cooled condensers—although it is                         water for condenser cooling. If so, DOE               Similarly, ASHRAE 90.1–2016 includes
                                                      possible that the term ‘‘refrigerant-to-                 requests comment on the appropriate                   three rating subcategories for water-
                                                      liquid heat recovery device’’ refers to                  representative value for the chiller                  source heat pump DOASes—ground-
                                                      the condenser of a water-source heat                     system energy contribution.                           source, closed loop; ground-water-
                                                      pump DOAS. Further, neither AHRI                                                                               source; and water-source. The EPCA
                                                      920–2015 nor ASHRAE 198–2013                             c. Test Conditions                                    definition for ‘‘commercial package air
                                                      mention accounting for the energy                                                                              conditioning and heating equipment’’
                                                                                                               i. Supply Air Conditions
                                                      consumption of heat recovery fans for                                                                          does not include ground-water-source
                                                      water loops or water-cooled condensers.                    AHRI 920–2015 includes a                            products (42 U.S.C. 6311(8)(A)), but
                                                      In contrast, AHRI 340/360–2007, which                    requirement of minimum supply air                     ground-source and water-source heat
                                                      is used for rating water-cooled CUACs,                   temperature of 70.0 °F for all standard               pumps would be covered by DOE with
                                                      provides in section 6.1 a power                          rating conditions and a maximum dew-                  two different rating conditions. DOE is
                                                      consumption allowance for both the                       point temperature of 55.0 °F for                      considering whether such dual rating
                                                      cooling tower fan and the circulating                    standard rating conditions for                        and certification is appropriate.
                                                      water pump.                                              dehumidification. ASHRAE 198–2013                        Issue DOAS–20: DOE requests
                                                         Issue DOAS–15: DOE requests                           requires a supply air temperature of                  comment on whether condenser cooling
                                                      confirmation that the ‘‘refrigerant-to-                  75.2 °F or as close to this value as the              by cooling tower water versus chilled
                                                      liquid heat recovery device’’ cited in                   controls will allow during testing.                   water demarcates two distinct
                                                      section 6.1.3 of AHRI 920–2015 is                                                                              equipment categories, or whether a
                                                      intended to include heat exchangers                        Issue DOAS–18: DOE requests                         single piece of equipment could operate
                                                      used for rejection of refrigerant circuit                comment or clarification related to the               in both applications. Likewise, DOE
                                                      heat during the dehumidification cycle,                  difference in target supply air                       requests comments on whether ground-
                                                      and comment on whether Equation 1 of                     temperature requirements between                      source closed-loop DOASes represent
                                                      this section for estimating the energy                   AHRI 920–2015 and ASHRAE 198–                         equipment that is distinct from water-
                                                      usage of water pumps is appropriate for                  2013. DOE requests comments as to the                 source models. For each of these pairs
                                                      DOASes with water-cooled condensers.                     appropriate supply air temperature for                of categories, if they do only represent
                                                         Issue DOAS–16: DOE requests                           use in the DOE test procedure for                     different test conditions for the same
                                                      comment on accounting for the energy                     DOAS.                                                 equipment, DOE requests input on
                                                      consumption for heat-rejection fans                      ii. Cooling Tower and Closed-Loop                     whether testing and rating equipment
                                                      employed in water-cooled or water-loop                                                                         for two applications is preferable, or
                                                                                                               Water-Source Differences
                                                      DOASes.                                                                                                        whether a single set of test conditions
                                                                                                                 The water entering temperature test                 and rating would be sufficient.
                                                      iii. Energy Consumption for the Chiller
                                                                                                               conditions in AHRI 920–2015 Table 2                      Section 2 of ASHRAE 198–2013
                                                      System for Liquid-Cooled DOAS Using
                                                                                                               for testing water-cooled DOAS differ                  specifically excludes DOASes with
                                                      Chilled Water for Condenser Cooling
                                                                                                               from the water-source heat pump inlet                 water coils that are supplied by a chiller
                                                        One of the options for testing water-                  temperature conditions specified in                   located outside of the unit. However,
                                                      cooled DOAS is to provide condenser                      Table 3 for water-source heat pump                    AHRI 920–2015 Table 2 includes
                                                      cooling water at 45 °F, replicating                      DOAS tested using the ‘‘water source’’                operating conditions for which a water-
                                                      operation in which condenser cooling is                  test conditions. Water-source water                   cooled condenser is supplied with
                                                      provided by a chilled water system.                                                                            chilled water, and ASHRAE 90.1–2016
                                                                                                               loops generally provide heat rejection
                                                      When operating in this fashion, the                                                                            established standard levels for DOASes
                                                                                                               using cooling towers. Hence, it is
                                                      chilled water system must expend                                                                               that operate with chilled water as the
                                                                                                               unclear that there is much value in
                                                      additional energy to maintain the 45 °F                                                                        condenser cooling fluid.
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                                                                               having incremental differences for the
                                                      supply water condition—it is not clear                                                                            Issue DOAS–21: DOE seeks
                                                                                                               dehumidification test conditions for
                                                      that this energy is considered in the                                                                          confirmation that the ASHRAE 198–
                                                      ISMRE metric. Without this energy use                    these types of equipment.
                                                                                                                                                                     2013 chiller exclusion applies to cooling
                                                      contribution, the ratings for such                         Issue DOAS–19: DOE requests                         coils rather than condenser coils.
                                                      equipment would appear to be have an                     comment on the need for different
                                                      unfair advantage in comparison to the                    dehumidification test conditions for a                d. Tolerances
                                                      ratings for DOAS rated using cooling                     water-cooled DOAS as compared to a                       Rating test tolerances for DOASes are
                                                      tower water. The minimum efficiency                      water-source heat pump DOAS using                     listed in Table 1 of ASHRAE 198–2013.
                                                      levels in ASHRAE 90.1–2016 for both                      the closed water loop test conditions.                This table specifies tolerances for


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00012   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                           34439

                                                      airflow rate and outdoor and return air                  that makes use of a secondary method                  it always clear how to set them to zero
                                                      dry-bulb and wet-bulb temperatures, but                  to check the primary method                           purge? Also, DOE requests feedback on
                                                      does not list any tolerances for supply                  worthwhile to ensure accuracy. DOE is                 whether it is appropriate to set purge to
                                                      airflow temperature. However,                            considering whether secondary                         zero or whether it would be more
                                                      tolerances for supply temperature are                    measurements should be required for                   appropriate to set purge to its highest
                                                      included in other relevant test                          DOAS testing in order to ensure                       setting or to some standard setting?
                                                      procedures, such as in Table 2b of                       accuracy of measurements. Section 7 of                   Issue DOAS–26: DOE requests any
                                                      ASHRAE 37–2009. DOE is considering                       ASHRAE 37–2009 describes several                      additional comments related to the
                                                      adding operating tolerances for supply                   different test methods applicable to                  adoption of AHRI 920–2015 as the test
                                                      airflow dry-bulb and wet-bulb                            testing of unitary air-conditioning and               procedure for DOAS.
                                                      temperatures to the test procedure.                      heat pump equipment. The cooling
                                                         In addition, the operating and                        condensate method may be particularly                 C. Test Procedure for Air-Cooled, Water-
                                                      condition tolerances listed for airflow                  relevant as a secondary test method for               Cooled, and Evaporatively-Cooled
                                                      rate are 5 percent in Table 1 of ASHRAE                  measuring the dehumidification                        Equipment
                                                      198–2013, which is looser than the                       performance of a DOAS.                                   DOE’s test procedures for ACUACs,
                                                      airflow rate tolerance adopted for                         Issue DOAS–23: DOE requests                         ECUACs, and WCUACs are codified at
                                                      CUACs. In fact, DOE proposed to apply                    comment on the need for a secondary                   10 CFR 431.96. Table 1 at 10 CFR 431.96
                                                      ± 5 percent condition tolerance on                       test method requirement for DOAS                      incorporates by reference AHRI 340/
                                                      cooling full-load indoor airflow rate for                testing. DOE seeks input regarding                    360–2007 for WCUACs and ECUACs
                                                      CUACs (see 80 FR 46870, 46873 (August                    potentially applicable secondary test                 with cooling capacity ≥65,000 Btu/h,
                                                      6, 2015; ‘‘August 2015 CUAC TP                           methods for the dehumidification and                  excluding section 6.3. For ACUACs with
                                                      NOPR’’)), but received several                           heating tests, and whether a secondary                cooling capacity ≥65,000 Btu/h, Table 1
                                                      comments suggesting that a 5-percent                     test method requirement and/or the                    refers to appendix A to subpart F of part
                                                      tolerance would result in too much                       secondary method allowed by the test                  431, which references sections 3, 4, and
                                                      variation in the measurement of EER                      procedure should depend on cooling (or                6 of AHRI 340/360–2007, excluding
                                                      and cooling capacity. Therefore, DOE                     dehumidification) capacity or airflow                 section 6.3. Paragraphs (c) and (e) of 10
                                                      adopted a 3-percent tolerance in the                     rate. DOE is also interested in detailed              CFR 431.96 and appendix A to subpart
                                                      December 2015 CUAC TP final rule, as                     information on the test burden that                   F of part 431 contain additional test
                                                      suggested by stakeholder comments. 80                    would be associated with a secondary                  procedure provisions for WCUACs/
                                                      FR 79655, 79659–79660 (Dec. 23, 2015).                   test method.                                          ECUACs and ACUACs, respectively.
                                                      DOE has concerns that the 5-percent                                                                            ASHRAE 90.1–2016 updated its test
                                                                                                               f. Test Set-Up
                                                      condition tolerance on airflow in                                                                              procedure reference for this equipment
                                                      ASHRAE 198–2013 may result in too                           Figures 1 and 2 of ASHRAE 198–2013
                                                                                                               show the typical test set-up for DOASes               to AHRI 340/360–2015, ‘‘Performance
                                                      much test variability for DOASes.                                                                              Rating of Commercial and Industrial
                                                         Issue DOAS–22: DOE requests                           with and without energy recovery. The
                                                                                                               figures show airflow and condition                    Unitary Air-conditioning and Heat
                                                      comment on whether to adopt the
                                                                                                               measuring devices at both the inlet and               Pump Equipment’’ (AHRI 340/360–
                                                      operating condition tolerances for
                                                      supply air temperature listed in Table                   the outlet of each airstream, but it is not           2015), which has triggered the
                                                      2b of ASHRAE 37–2009 for DOAS                            clear in the test standard that both                  requirement for DOE to review its test
                                                      testing. DOE also seeks input regarding                  airflow measurement devices are                       procedures for this equipment.
                                                      whether a 5-percent airflow tolerance is                 required. DOE notes that typically only                  At 10 CFR 431.95 and Table 1 of 10
                                                      acceptable. Further, DOE requests any                    one airflow measuring device, which                   CFR 431.96, DOE incorporates by
                                                      information or data regarding tolerances                 measures airflow downstream of the                    reference AHRI 210/240–2008 for
                                                      for any other test operating parameters.                 unit, is installed in air-conditioner and             testing of ACUACs, WCUACs, and
                                                      Specifically, DOE requests comment on                    heat pump testing. ASHRAE 198–2013                    ECUACs with cooling capacity <65,000
                                                      whether there are any parameters whose                   provides no description of the use of                 Btu/h, excluding section 6.5. While
                                                      tolerances should be tightened or                        two sets of airflow measurements per                  ASHRAE 90.1–2016 did not update its
                                                      relaxed to ensure limited variation and                  airstream, for example, for a tolerance               test procedure reference for this
                                                      high certainty for the ISMRE and ISCOP                   check of the airflow calculation or                   equipment, AHRI has made public a
                                                      results with appropriate test burden.                    determination of leakage between air                  draft update of AHRI 210/240 (AHRI
                                                                                                               streams when testing a DOAS with                      210/240–2015–Draft) that was submitted
                                                      e. Capacity Measurement                                                                                        to the docket for the test procedure for
                                                                                                               energy recovery.
                                                         The air enthalpy method, as specified                    Issue DOAS–24: DOE requests                        CAC/HPs on August 14, 2015 (Docket
                                                      in section 6.1 of ASHRAE 198–2013, is                    comments on whether it is beneficial or               No. EERE–2009–BT–TP–0004). For this
                                                      the only capacity measurement method                     necessary to use two airflow measuring                reason, and to comply with the statutory
                                                      required in the test procedure. There is                 devices per airstream when testing                    requirement to review test procedures at
                                                      no mention of a secondary test method                    DOAS equipment.                                       least once every seven years (42 U.S.C.
                                                      for capacity measurement verification in                    Section 6.6 of ASHRAE 198–2013,                    6314(a)(1)(A)), DOE is reviewing its test
                                                      AHRI 920–2015 or ASHRAE 198–2013.                        which deals with Unit Preparation,                    procedures for ECUACs and WCUACs
                                                      In contrast, secondary capacity                          describes that any energy recovery                    with cooling capacity less than 65,000
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      measurements are generally required for                  devices that include a purge or other                 Btu/h in this RFI. DOE will consider
                                                      testing of air conditioners with capacity                function that transfers air from supply               ACUACs with a cooling capacity less
                                                      less than 135,000 Btu/h (see, e.g.,                      or exhaust shall be disabled to set at                than 65,000 Btu/h in a separate RFI.
                                                      ASHRAE 37–2009 section 7.2.1).                           zero position.                                           The following sections explore
                                                      Measurement of air conditioning                             Issue DOAS–25: DOE seeks additional                aligning the ECUAC and WCUAC metric
                                                      capacity is based on the measurements                    information on the purge function                     with that of ACUAC, review updates in
                                                      of air flow rate, temperature, and                       mentioned in section 6.6 of ASHRAE                    AHRI 340/360–2015 to determine if
                                                      humidity, which can have an                              198–2013. Specifically, are all purge                 adopting that industry standard would
                                                      uncertainty range associated with them                   devices adjustable to zero purge, and is              meet EPCA requirements, and explore


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00013   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34440                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      additional test procedure issues related                 of a negotiated rulemaking involving                  static pressures for testing based on the
                                                      to the subject equipment.                                that equipment. As part of this term                  rated unit capacity of ECUACs and
                                                                                                               sheet, Recommendation #3 discussed                    WCUACs. DOE is interested in ensuring
                                                      1. Energy Efficiency Descriptor
                                                                                                               the need for DOE’s test procedures and                that the external static pressures in the
                                                         DOE’s current energy efficiency                       related efficiency metrics to properly                test procedures are representative of
                                                      descriptor for ECUACs and WCUACs is                      account for the energy consumption of                 those experienced in field installations.
                                                      the energy efficiency ratio (EER). 10 CFR                fans embedded in regulated commercial                 In the December 2015 CUAC TP final
                                                      431.96. The EER metric only captures                     air-conditioning equipment.                           rule, DOE summarized stakeholder
                                                      performance at a single set of rating                       In addition, the working group agreed              comments regarding the possibility that
                                                      conditions with equipment operating at                   that in the next round of test procedure              external static pressures as measured in
                                                      full-load, and it is calculated by                       rulemakings, DOE should consider                      the field may be higher than those found
                                                      dividing the full-load cooling capacity                  revising efficiency metrics that include              in the industry test standards. 80 FR
                                                      by the equipment power input. In                         energy use of supply and condenser fans               79655, 79664 (Dec. 23, 2015). Based on
                                                      contrast, DOE adopted integrated energy                  to include the energy consumption                     this information, DOE is examining the
                                                      efficiency ratio (IEER) as an energy                     during all relevant operating modes                   external static pressures specified in the
                                                      efficiency metric for ACUACs in the                      (e.g., auxiliary heating mode, ventilation            test procedures for ECUACs and
                                                      December 2015 CUAC TP final rule. 80                     mode, and part-load operation). The                   WCUACs.
                                                      FR 79655 (Dec. 23, 2015). ASHRAE                         working group included ACUACs,                           Issue CUAC–3: DOE requests
                                                      90.1–2016 also provides minimum                          ECUACs, and WCUACs in its list of                     comment or data regarding the typical
                                                      efficiency IEER levels (in addition to                   regulated equipment for which fan                     external static pressures in field
                                                      EER levels) for ECUACs and WCUACs.                       energy use should be considered.                      installations of ECUACs and WCUACs
                                                         AHRI 340/360–2007 includes a                          (Docket No. EERE–2013–BT–STD–                         and whether these field-installed
                                                      method for testing and calculating IEER                  0006–0179 at pp. 3–4, 16)                             external static pressures typically vary
                                                      for ECUACs and WCUACs. IEER is an                           Consequently, DOE is considering                   with capacity. DOE also seeks comment
                                                      energy efficiency descriptor that is                     what changes to its ACUAC, ECUAC,                     regarding whether the field applications
                                                      calculated from test results at four sets                and WCUAC test procedures may more                    of ECUACs and WCUACs are different
                                                      of conditions including a full-load test                 accurately represent fan energy use in                from ACUACs with regards to the
                                                      at standard rating conditions and three                  field applications. DOE is aware that                 typical ducting installed on the system.
                                                      part-load tests at different outdoor                     field-installed fan energy use will vary                 Another issue related to fan energy is
                                                      conditions for ECUACs and different                      based on the use of the fan for ancillary             the default fan power for ACUACs,
                                                      entering water temperatures for                          functions (e.g., economizers, ventilation,            ECUACs, and WCUACs with a coil-only
                                                      WCUACs. IEER utilizes adjustment                         filtration, and auxiliary heat). In order to          configuration (i.e., without an integral
                                                      factors to account for cycling losses,                   properly account for fan energy use,                  supply fan). Current test procedures for
                                                      when applicable, at part-load                            DOE is requesting information on how                  ACUACs, ECUACs, and WCUACs
                                                      conditions. IEER also includes                           frequently field installations use the                specify that indoor fan power of 365
                                                      continuous indoor fan operation, during                  supply fan of the CUAC for various                    Watts (W) per 1000 standard cubic feet
                                                      times when the compressor would be                       ancillary functions.                                  per minute (scfm) be added to power
                                                      cycling to meet the required load, to                       Issue CUAC–2: DOE requests                         input for coil-only units and that the
                                                      account for fan operation during                         information, including any available                  corresponding heat addition be
                                                      ventilation mode. After the measured                     data, on how frequently CUAC supply                   subtracted from measured cooling. This
                                                      efficiencies at the four test conditions                 fans are operated when there is no                    value has been used to account for the
                                                      are adjusted for cycling losses and                      demand for heating or cooling (i.e., for              fan energy use associated with coil-only
                                                      continuous fan use, if applicable, the                   fresh air ventilation or air circulation/             units for many years, and more-efficient
                                                      results are multiplied by weighting                      filtration), and what the typical                     motors and fans may be in use for which
                                                      factors and added together to determine                  operating schedules or duty cycles are                the current 365 W/1000 scfm fan power
                                                      the IEER. The weighting factors used are                 for this function. Additionally, DOE                  value is not representative. It is also
                                                      as follows: 0.020 for the full-load test,                requests data or information regarding                possible that the value is not consistent
                                                      0.617 for the 75-percent load test, 0.238                how frequently and what forms of                      with field-typical external static
                                                      for the 50-percent load test, and 0.125                  primary and auxiliary heating are                     pressures.
                                                      for the 25-percent load test.                            installed with CUACs and whether their                   Issue CUAC–4: DOE seeks comment
                                                         Issue CUAC–1: DOE seeks comment                       operation is dependent on the supply                  or data on the prevalence of ACUACs,
                                                      or data on whether the IEER part-load                    fan of the CUAC. DOE requests data or                 ECUACs, and WCUACs that are sold in
                                                      conditions and IEER weighting factors                    information regarding how frequently                  coil-only configurations (i.e., neither
                                                      are representative of the operation of                   the systems are used with economizers,                with an integral supply fan, nor with a
                                                      field-installed ECUACs and WCUACs.                       how the economizers are integrated                    designated air mover such as a furnace
                                                      DOE also seeks comment or data                           with the systems, and what control logic              or modular blower).
                                                      regarding the typical cycling losses of                  is typically used on the economizers.                    Issue CUAC–5: DOE seeks comment
                                                      field-installed ECUACs and WCUACs.                       DOE also seeks comment and                            or data on the typical efficiency or
                                                         The Appliance Standards and                           information regarding the use of the                  typical power use and flow of fans used
                                                      Rulemaking Federal Advisory                              indoor supply fan of CUACs for any                    with coil-only ACUACs, WCUACs, and
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      Committee (ASRAC) Commercial and                         ancillary functions not mentioned                     ECUACs in field installations.
                                                      Industrial Fans and Blowers Working                      above. Please differentiate by ACUAC,
                                                      Group developed recommendations                          ECUAC, or WCUAC, as necessary.                        2. Addressing Changes to AHRI 340/360
                                                      regarding the energy conservation                           Another factor that influences fan                    As noted previously, ASHRAE 90.1–
                                                      standards, test procedures, and                          energy use is the external static pressure            2016 updated its reference from AHRI
                                                      efficiency metrics for commercial and                    that is required to overcome the air                  340/360–2007 to AHRI 340/360–2015.
                                                      industrial fans and blowers in a term                    distribution system pressure drop. Both               The updated AHRI 340/360–2015
                                                      sheet (Docket No. EERE–2013–BT–STD–                      AHRI 210/240–2008 and AHRI 340/                       includes significant changes from AHRI
                                                      0006–0179), which was the culmination                    360–2007 specify minimum external                     340/360–2007 for ACUACs, ECUACs,


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00014   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                                      Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                                                        34441

                                                      and WCUACs, and DOE seeks comment                                     other changes are only relevant to one                                relevant. In some cases, a change may
                                                      on those changes as discussed in this                                 or two of the equipment categories.                                   not be relevant to ACUACs because the
                                                      section. Several changes are relevant to                              Table II.2 illustrates to which                                       change has already been adopted in the
                                                      all three categories of equipment, while                              equipment category each change is                                     December 2015 CUAC TP final rule.

                                                                                                                       TABLE II.2—AHRI 340/360–2015 CHANGES
                                                                                                                    Topic                                                                          ACUAC                 ECUAC        WCUAC

                                                      Head Pressure Controls ..............................................................................................................              X                 X                X
                                                      Refrigerant Charging Requirements ............................................................................................                     X                 X                X
                                                      Adjustment for Different Atmospheric Pressure Conditions ........................................................                                  X                 X                X
                                                      Measurement of Condenser Air Inlet Temperature .....................................................................                               X                 X     ........................
                                                      Tolerance of Tested Airflow Relative to Rated Airflow ...............................................................                   ........................     X                X
                                                      Vertical Separation of Indoor and Outdoor Units ........................................................................                           X                 X                X
                                                      Outdoor Entering Air Wet-Bulb Temperature ..............................................................................                ........................     X     ........................
                                                      Single-Zone Variable-Air-Volume and Multi-Zone Variable-Air-Volume .....................................                                           X                 X                X



                                                      a. Head Pressure Controls                                                Issue CUAC–6: DOE seeks information                                values of parameters are the centers of
                                                         Condenser head pressure controls                                   and data regarding testing of CUACs                                   the ranges allowed by installation
                                                      regulate the flow of refrigerant through                              with head pressure control that would                                 instructions, and specifies tolerances for
                                                      the condenser and/or adjust operation of                              require the special test provisions                                   the measured values. 81 FR 36992,
                                                      condenser fans to prevent condenser                                   described in AHRI 340/360–2015.                                       37030–37031. These methods could be
                                                      pressures from dropping too low during                                Specifically, can such units be tested in                             considered as an example for the CUAC
                                                      low-ambient operation. When                                           compliance with the relaxed stability                                 test method.
                                                      employed, these controls ensure that the                              requirements of these test provisions?                                  Issue CUAC–7: DOE seeks comment
                                                      refrigerant pressure is high enough to                                Do the test results accurately represent                              on whether it would be appropriate to
                                                      maintain adequate flow through                                        field use? Is the test burden associated                              adopt an approach for charging
                                                      refrigerant expansion devices such as                                 with these tests appropriate?                                         requirements for commercial CUACs
                                                      thermostatic expansion valves. AHRI                                   b. Refrigerant Charging Requirements                                  similar or identical to the approach
                                                      340/360–2007 provides minimal                                                                                                               adopted in the June 2016 CAC TP final
                                                                                                                               AHRI 340/360–2007 does not provide                                 rule for residential products. DOE seeks
                                                      guidance on head pressure controls,
                                                                                                                            any specific guidance on setting the                                  comments regarding which parts of the
                                                      only mentioning in note 2 of Table 6
                                                                                                                            refrigerant charge of a unit.                                         approach should or should not be
                                                      that the condenser airflow should be                                     The DOE test procedures for ACUACs,
                                                      adjusted as required by the unit controls                                                                                                   adopted, and for what reasons they
                                                                                                                            ECUACs, and WCUACs state that if the
                                                      for head pressure control. AHRI 340/                                                                                                        might or might not be suitable for
                                                                                                                            manufacturer specifies a range of
                                                      360–2015 states that any head pressure                                                                                                      application to CUACs. DOE is also
                                                                                                                            superheat, sub-cooling, and/or
                                                      controls shall be left at the                                                                                                               interested in receiving data that
                                                                                                                            refrigerant pressures in the installation
                                                      manufacturer’s settings and operated in                                                                                                     demonstrate how sensitive the
                                                                                                                            or operation manual, any value within
                                                      automatic mode, but that, if this results                             that range may be used to determine                                   performance of ACUACs, ECUACs, and
                                                      in unstable operation exceeding the                                   refrigerant charge, unless the                                        WCUACs is relative to changes in the
                                                      tolerances of ASHRAE 37–2009, the                                     manufacturer clearly specifies a rating                               various charge indicators used for
                                                      time-averaged head pressure control test                              value in its installation or operation                                different charging methods, specifically
                                                      described in section F7 of appendix F of                              manual, in which case the specified                                   the method based on sub-cooling.
                                                      AHRI 340/360–2015 shall be used. This                                 value shall be used. 10 CFR 431.96(e)(1);                             c. Adjustment for Different Atmospheric
                                                      test requires measuring performance                                   section (5)(i) of appendix A to                                       Pressure Conditions
                                                      using two one-hour test periods, first                                subpart F of part 431.
                                                      after approaching the target ambient                                     AHRI 340/360–2015 states that                                         In order to address potential
                                                      condition from warmer temperatures,                                   equipment shall be charged with                                       differences in measured results
                                                      and once after approaching from lower                                 refrigerant at standard rating conditions                             conducted at different atmospheric
                                                      temperatures. During these tests, the                                 (or conditions specified by the                                       pressure conditions, AHRI 340/360–
                                                      looser tolerance requirements from                                    manufacturer in the installation                                      2015 introduced an adjustment for
                                                      Table 2b of ASHRAE 37–2009 for the                                    instructions) in accordance with the                                  indoor supply fan power and
                                                      ‘‘heat portion’’ of the heat with defrost                             manufacturer’s installation instructions                              corresponding fan heat. This adjusts the
                                                      test must be met. This issue was                                      or label applied to the equipment. In                                 fan power based on the barometric
                                                      reviewed by DOE for ACUACs in the                                     contrast with the DOE test procedure,                                 pressure at the test site, multiplying the
                                                      December 2015 CUAC TP final rule. In                                  the industry test standard calls for the                              measured supply fan power by the
                                                      that final rule, DOE clarified that head                              use of the average of ranges of sub-                                  square of the ratio of the measured air
                                                      pressure controls must be active during                               cooling or superheat specified in                                     density (density of air at measured
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      the test, but DOE did not adopt the time-                             installation manuals.                                                 supply air temperature and humidity
                                                      averaged head pressure control test                                      As discussed in section II.A.3.e, the                              and measured atmospheric pressure) to
                                                      specified in AHRI 340/360–2015,                                       June 2016 CAC TP final rule provides a                                the density of the supply air if it were
                                                      indicating that AHRI 340/360–2015 was                                 comprehensive approach for charging                                   at standard pressure (14.696 pounds per
                                                      a draft document at the time and that                                 that improves test reproducibility. The                               square inch). Consequently, the cooling
                                                      DOE would reconsider adoption of the                                  approach indicates which set of                                       capacity and efficiency are also
                                                      provisions for testing units with head                                installation instructions to use for                                  impacted by this correction.
                                                      pressure control later. 80 FR 79655,                                  charging, explains what to do if there                                   The outdoor air mass flow rate and
                                                      79660 (Dec. 23, 2015).                                                are no instructions, indicates that target                            fan power will also vary with


                                                 VerDate Sep<11>2014       17:17 Jul 24, 2017      Jkt 241001      PO 00000      Frm 00015      Fmt 4702      Sfmt 4702      E:\FR\FM\25JYP1.SGM            25JYP1


                                                      34442                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      atmospheric pressure; however, the                       requirements in AHRI 340/360–2015                     use indoor and outdoor environmental
                                                      outdoor fan speed is typically not                       may not be appropriate for ECUACs.                    chambers that are stacked vertically, the
                                                      adjustable, because most outdoor fans                      Issue CUAC–10: DOE requests                         limitation on vertical separation may
                                                      have single-speed direct-drive motors,                   comments and data on the sizes of the                 make it impractical or impossible to test
                                                      and no rated outdoor air flow rate in                    smallest and largest openings for                     split systems.
                                                      scfm is set during the test for the                      condenser inlet air on the sides of                     Issue CUAC–13: DOE seeks comment
                                                      majority of CUACs. To address the                        ECUACs. DOE seeks comment on                          regarding whether a maximum of 10 feet
                                                      potential impact of barometric pressure                  whether the air sampler tree                          of vertical separation of indoor and
                                                      on the outdoor fan air flow, AHRI 340/                   requirements in Appendix C of AHRI                    outdoor units would limit the ability of
                                                      360–2015 imposed a minimum                               340/360–2015, specifically the                        existing facilities to test split-system
                                                      atmospheric pressure of 13.7 pounds                      requirement of 10 to 20 branch tubes,                 ACUACs, ECUACs, or WCUACs. DOE
                                                      per square inch absolute (psia) for                      and the thermopile requirement of                     also seeks comment on the impact that
                                                      testing equipment.                                       having 16 thermocouples per air                       vertical separation of split systems has
                                                        Issue CUAC–8: DOE requests test data                   sampler tree, are feasible for all                    on efficiency and capacity.
                                                      that validate the supply fan power                       ECUACs. DOE also seeks information
                                                                                                                                                                     g. Outdoor Entering Air Wet-Bulb
                                                      correction used in AHRI 340/360–2015.                    regarding any alternative methods or
                                                                                                                                                                     Temperature (ECUAC)
                                                      DOE is also interested in comments on                    measurements for determining
                                                                                                               condenser inlet air uniformity that may                  AHRI 340/360–2007 provides the
                                                      whether the minimum atmospheric
                                                                                                               be more suitable for ECUACs.                          same outdoor entering air conditions
                                                      pressure of 13.7 psia will prevent any
                                                                                                                 Issue CUAC–11: DOE requests                         (i.e., 95.0 °F dry bulb and 75.0 14; °F
                                                      existing laboratories from testing
                                                                                                               comments and data regarding whether a                 wet bulb) for the standard rating
                                                      equipment, and what burden, if any, is
                                                                                                               method of measuring and specifications                condition (Table 3 of AHRI 340/360–
                                                      imposed by such a requirement. DOE
                                                                                                               for uniformity of the outdoor inlet wet               2007) and the 100-percent-capacity test
                                                      also seeks any available test data
                                                                                                               bulb temperature would benefit test                   point used to calculate IEER (Table 6 of
                                                      showing the impact that variations in
                                                                                                               reproducibility for ECUACs.                           AHRI 340/360–2007) for ECUACs.
                                                      atmospheric pressure have on the
                                                                                                                                                                     While the outdoor entering air dry-bulb
                                                      performance (i.e., capacity and                          e. Tolerance of Tested Indoor Airflow                 temperature is unchanged in AHRI 340/
                                                      component power use) of ACUACs,                          Relative to Rated Indoor Airflow                      360–2015, the outdoor entering air wet-
                                                      ECUACs, and WCUACs.                                      (ECUAC and WCUAC)                                     bulb temperature for the 100-percent-
                                                      d. Measurement of Condenser Air Inlet                       AHRI 340/360–2007 does not provide                 capacity test point used to calculate
                                                      Temperature (ACUAC and ECUAC)                            any tolerance on the tested indoor                    IEER was changed from 75.0 °F to 74.5
                                                                                                               airflow relative to the rated airflow of              °F (Table 6 of AHRI 340/360–2015).
                                                        A number of requirements have been                     the unit under test. AHRI 340/360–2015                This change suggests that two full-load
                                                      added in Appendix C of AHRI 340/360–                     has added a 3-percent tolerance for the               tests may be required: One at the
                                                      2015 to help ensure accurate and                         tested airflow relative to the rated                  standard rating conditions for
                                                      reproducible measurement of the                          airflow (i.e., the tested airflow is                  measuring the rated capacity and EER,
                                                      condenser air inlet temperature. These                   permitted to be 3 percent higher or 3                 and another at the 100-percent-capacity
                                                      requirements include specifications on                   percent lower than the rated airflow).                test point for the IEER test. Table 6 of
                                                      the acceptable number, geometry,                         DOE adopted a 3 percent tolerance on                  AHRI 340/360–2015 also lists only
                                                      placement, and construction details of                   indoor airflow for testing ACUACs in                  entering air wet-bulb temperatures for
                                                      air sampling trees; specifications on the                the December 2015 CUAC TP final rule                  ECUACs, with no corresponding dry-
                                                      required accuracy of dry bulb, wet bulb,                 to limit variation in EER and cooling                 bulb temperatures.
                                                      and thermopile measurement devices;                      capacity, based on test data and                         Issue CUAC–14: DOE seeks comment
                                                      requirements on the set-up and number                    feedback provided by industry                         regarding the slightly different air wet-
                                                      of aspirating psychrometers; and criteria                commenters. 80 FR 79655, 79659–79660                  bulb test conditions of AHRI 340/360–
                                                      for assessing acceptable air distribution                (Dec. 23, 2015).                                      2015 for standard rating conditions as
                                                      and control of air temperature.                             Issue CUAC–12: DOE seeks comment                   compared with the 100-percent-capacity
                                                        Issue CUAC–9: DOE requests                             or data showing whether variations in                 test point for the IEER test, and whether
                                                      comment on whether any manufacturers                     indoor airflow impact the measured                    the requirement should be 75.0 °F for
                                                      have evaluated the condenser inlet air                   efficiency or capacity of ECUACs and                  both purposes.
                                                      uniformity using the criteria in                         WCUACs more or less than ACUACs                          Issue CUAC–15: DOE seeks comment
                                                      Appendix C of AHRI 340/360–2015 for                      and whether the 3-percent tolerance                   on whether the air-cooled entering air
                                                      ACUACs and ECUACs and if so,                             provided in AHRI 340/360–2015 (and                    dry-bulb temperatures in Table 6 of
                                                      whether any alterations to the laboratory                adopted for ACUACs in DOE’s                           AHRI 340/360–2015 apply to
                                                      or test set-up were necessary to meet                    regulations) is appropriate for these                 evaporatively-cooled units. If any
                                                      those requirements. Also, DOE requests                   other equipment categories.                           manufacturers have developed IEER
                                                      comment on whether the requirements                                                                            ratings for ECUACs using AHRI 340/
                                                      of Appendix C are sufficient to ensure                   f. Vertical Separation of Indoor and
                                                                                                                                                                     360–2015, DOE requests information
                                                      reproducibility of results and/or any test               Outdoor Units
                                                                                                                                                                     about what outdoor entering air dry-
                                                      data that demonstrate sufficient                            AHRI 340/360–2007 does not limit                   bulb temperatures were used during the
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      reproducibility.                                         the vertical separation of indoor and                 100-percent and part-load tests.
                                                        Due to the different heat exchange                     outdoor units when testing split
                                                      process of ECUAC condensers when                         systems. However, AHRI 340/360–2015                   h. Single-Zone Variable-Air-Volume and
                                                      compared to ACUACs, ECUACs may                           adds a requirement that the maximum                   Multi-Zone Variable-Air-Volume
                                                      have lower condenser airflow and in                      allowable vertical separation of the                    AHRI 340/360–2015 established
                                                      turn, smaller openings for the condenser                 indoor and outdoor units be 10 feet,                  different approaches for setting indoor
                                                      inlet air when compared to ACUACs of                     presumably because separation greater                 air flow for the part-load test conditions
                                                      similar capacity. Consequently, the air                  than 10 feet can adversely affect                     for single-zone variable-air-volume
                                                      sampler tree and thermopile                              measured performance. If test facilities              (SZVAV) and multi-zone variable-air-


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00016   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                                      Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                                                          34443

                                                      volume (MZVAV) systems (see section                                    thermostats connected are part of the                                  that could be both SZVAV and MZVAV
                                                      6.1.3.3). The test standard defines                                    installation of a unit and not inherent                                should be tested both ways,
                                                      MZVAV as units ‘‘designed to vary the                                  attributes of a unit’s characteristics.                                representing two separate basic models.
                                                      indoor air volume and refrigeration                                    Another part of the definition addresses                               If tested as one basic model, DOE
                                                      capacity/staging at a controlled                                       the variation of indoor air flow and                                   requests information regarding how to
                                                      discharge air temperature and static                                   capacity. For MZVAV, the air flow and                                  determine which of the two test
                                                      pressure as a means of providing space                                 capacity can be varied to provide a                                    methods would apply. How frequently
                                                      temperature control to independent                                     controlled discharge temperature and a                                 would such a model be installed in the
                                                      multiple spaces with independent                                       controlled static pressure, which                                      field as a SZVAV as opposed to a
                                                      thermostats.’’ (AHRI 340/360–2015                                      suggests, but does not clearly state, that                             MZVAV? DOE also requests comment
                                                      section 3.14) It defines SZVAV as units                                such units have variable-capacity                                      on whether status as a proportionally
                                                      with a ‘‘control system designed to vary                               compressors, and that their indoor fan                                 controlled unit (see AHRI 340/360–2015
                                                      the indoor air volume and refrigeration                                controls allow fully variable control of                               section 3.20) would be considered to be
                                                      capacity/staging as a means to provide                                 fan speed. In contrast, the SZVAV                                      the appropriate indication of whether a
                                                      zone control to a single or common                                     definition seems to allow modulation,                                  CUAC can be used as a MZVAV unit, or
                                                      zones, controlled by a single space                                    steps, or a combination of steps and                                   whether some other characteristics
                                                      thermostat input.’’ The SZVAV                                          modulation for both fan and compressor                                 regarding variable capacity control
                                                      definition further explains that, ‘‘the                                capacity control. Based on these                                       would have to be satisfied. Finally, for
                                                      capacity, as well as the supply air flow                               definitions, it seems that a unit with a
                                                                                                                                                                                                    models that can be both SZVAV and
                                                      shall be controlled either through                                     variable-capacity compressor system
                                                                                                                                                                                                    MZVAV, how much do the efficiency
                                                      modulation, discrete steps or                                          and a variable-speed fan could meet
                                                                                                                                                                                                    ratings for the two configurations differ?
                                                      combinations of modulation and step                                    both definitions. Also, it would appear
                                                      control based on the defined control                                   that any unit with a variable-capacity                                 3. Additional Test Method Issues
                                                      logic.’’ (AHRI 340/360–2015 section                                    compressor system that has SZVAV
                                                      3.25)                                                                  characteristics could be converted to a                                  In this section, DOE explores several
                                                        Part of the focus of each definition is                              MZVAV system by changing the indoor                                    additional issues related to the test
                                                      the number of zones and number of                                      fan motor controller or perhaps simply                                 procedures for CUACs. Most issues are
                                                      thermostats involved in a system served                                changing its settings.                                                 relevant to only ECUACs, but a few are
                                                      by a given variable-air-volume unit.                                      Issue CUAC–16: DOE requests                                         also relevant to WCUACs and/or
                                                      However, the zones served and                                          comment on whether a CUAC model                                        ACUACs, as shown in Table II.3.

                                                                                                                TABLE II.3—ADDITIONAL CUAC TEST METHOD ISSUES
                                                                                                                     Topic                                                                           ACUAC                 ECUAC        WCUAC

                                                      Length of Refrigerant Line Exposed to Outdoor Conditions .......................................................                                     X                 X                X
                                                      Atmospheric Pressure Measurement ..........................................................................................                          X                 X                X
                                                      Consistency Among Test Procedures for Small and Large Equipment .....................................                                     ........................     X                X
                                                      Make-up Water Temperature ......................................................................................................          ........................     X     ........................
                                                      Secondary Measurement Method for Capacity ...........................................................................                     ........................     X     ........................
                                                      Piping Evaporator Condensate to Condenser Pump ..................................................................                         ........................     X     ........................
                                                      Purge Water Settings ..................................................................................................................   ........................     X     ........................
                                                      Condenser Spray Pumps ............................................................................................................        ........................     X     ........................
                                                      Additional Steps to Verify Proper Operation ...............................................................................               ........................     X     ........................



                                                      a. Length of Refrigerant Line Exposed to                               ACUAC, ECUAC or WCUAC                                                  the extremes of this tolerance result in
                                                      Outdoor Conditions                                                     installations and whether this length                                  capacity measurement errors of 1–2
                                                                                                                             varies depending on the capacity of the                                percent.
                                                         AHRI 340/360–2007, AHRI 340/360–                                                                                                             Issue CUAC–18: DOE seeks comment
                                                                                                                             unit. DOE also seeks comment or data
                                                      2015, AHRI 210/240–2008, and AHRI                                      on any measurements or calculations                                    on the typical accuracy of the
                                                      210/240–2015–Draft all require at least                                that have been made of the losses                                      atmospheric pressure sensors used by
                                                      25 feet of interconnecting refrigerant                                 associated with refrigerant lines located                              existing test laboratories.
                                                      line when testing split-systems.                                       in the outdoor chamber and whether the
                                                      However, both versions of AHRI 340/                                                                                                           c. Consistency Among Test Procedures
                                                                                                                             impact is larger or smaller than DOE’s                                 for Small and Large ECUAC and
                                                      360 require that at least 5 feet of the                                estimate of approximately 1 percent of
                                                      interconnecting refrigerant line must be                                                                                                      WCUAC Equipment Classes
                                                                                                                             capacity per 10 feet of refrigerant line
                                                      exposed to outdoor test chamber                                        located in the outdoor chamber.                                           The current test procedure and
                                                      conditions, while both versions of AHRI                                                                                                       referenced industry standard for
                                                      210/240 require at least 10 feet be so                                 b. Atmospheric Pressure Measurement                                    ECUACs and WCUACs that have
                                                      exposed. DOE has estimated an upper                                       The accuracy of atmospheric pressure                                cooling capacities less than 65,000
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      bound of the capacity loss to be                                       measurements required by section 5.2.2                                 Btu/h (AHRI 210/240–2008) reference
                                                      approximately 1 percent of the capacity                                of ASHRAE 37–2009 (which is                                            the same test method (ASHRAE 37–
                                                      of the unit for 10 feet of refrigerant line                            referenced by AHRI 340/360–2015) is                                    2005) and contain the same efficiency
                                                      located in the outdoor chamber and                                     ±2.5 percent. This level of uncertainty                                metrics as those for units with
                                                      approximately 0.5 percent for 5 feet.                                  can result in error when calculating the                               capacities greater than or equal to
                                                         Issue CUAC–17: DOE seeks comment                                    indoor entering and leaving air                                        65,000 Btu/h (AHRI 340/360–2007).
                                                      or data regarding the typical length of                                enthalpies and resulting cooling                                       However, there are some differences
                                                      refrigerant line that is exposed to                                    capacity. Under certain circumstances,                                 that have been identified in this section.
                                                      outdoor conditions on split-system                                     atmospheric pressure measurements at                                   DOE is considering whether the


                                                 VerDate Sep<11>2014        17:17 Jul 24, 2017      Jkt 241001      PO 00000      Frm 00017       Fmt 4702      Sfmt 4702     E:\FR\FM\25JYP1.SGM             25JYP1


                                                      34444                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      consistency of test procedures could be                  e. Secondary Measurement Method for                      Issue CUAC–22: DOE seeks comment
                                                      improved by referencing a single                         Capacity (ECUAC)                                      on whether single-package ECUACs
                                                      industry standard for all cooling                           ASHRAE 37–2009 requires the indoor                 with a rated cooling capacity less than
                                                      capacities of ECUACs and WCUACs.                         air enthalpy method plus an additional                135,000 Btu/h are currently sold.
                                                      The updated industry standard for                        secondary method for calculating the                     Issue CUAC–23: DOE seeks comment
                                                      rating units with a capacity greater than                test equipment capacity for all units                 on whether manufacturers would see a
                                                      or equal to 65,000 Btu/h (AHRI 340/                      with less than 135,000 Btu/h rated                    benefit in allowing the outdoor air
                                                      360–2015) has significant changes that                   capacity. The test standard lists                     enthalpy method as a secondary
                                                      affect the testing of ECUACs and                         applicable test methods in Table 1, but               capacity measurement for ECUACs. If
                                                      WCUACs. However, the industry                            this table does not indicate that the
                                                      standard for rating units with a cooling                                                                       so, DOE is interested in feedback on
                                                                                                               outdoor air enthalpy method is                        methods to mitigate the risk of
                                                      capacity less than 65,000 Btu/h is in the                applicable for any configuration of
                                                      process of being updated and could                                                                             condensation in the outdoor unit supply
                                                                                                               evaporatively-cooled equipment.                       duct and the outdoor supply wet-bulb
                                                      potentially be finalized with better                     Therefore, the secondary method for
                                                      consistency with AHRI 340/360 for                                                                              sample station. DOE also asks if other
                                                                                                               ECUACs is limited to use of the                       alternative approaches could be
                                                      testing of this equipment.                               refrigerant enthalpy method or
                                                         Issue CUAC–19: DOE requests                                                                                 considered for mitigating the potential
                                                                                                               compressor calibration method for split               test burden associated with the
                                                      comment on whether there are
                                                                                                               systems and only the compressor                       secondary test methods that ASHRAE
                                                      differences between ECUACs and
                                                                                                               calibration method for single-package                 37–2009 specifies for evaporatively-
                                                      WCUACs that have cooling capacities
                                                                                                               equipment. DOE recognizes that the                    cooled equipment.
                                                      less than 65,000 Btu/h and those that
                                                      have cooling capacities greater than or                  refrigerant enthalpy method and
                                                                                                               compressor calibration method can, in                 f. Piping Evaporator Condensate to
                                                      equal to 65,000 Btu/h that justify the                                                                         Condenser Pump (ECUAC)
                                                      incorporation by reference of different                  some circumstances, add burden to the
                                                      industry test standards for the different                testing procedure, so DOE examined the
                                                                                                               potential use of the outdoor air enthalpy                Some split-system ECUACs provide
                                                      cooling capacity ranges. If not, DOE                                                                           the option for piping evaporator
                                                      seeks feedback on whether referencing a                  method as a secondary method for
                                                                                                               ECUACs. During testing, DOE observed                  condensate to the condenser sump. This
                                                      single industry standard for units of all                                                                      reduces the make-up water use of the
                                                      cooling capacities would be beneficial                   that the part-load test conditions
                                                                                                               produce an environment where                          unit and may provide some performance
                                                      and/or whether there could or should be                                                                        improvement. Neither DOE’s current
                                                      better consistency between the test                      condensation is likely in the outdoor
                                                                                                               unit supply duct, because the outdoor                 test procedures nor the industry ECUAC
                                                      standards for testing of this equipment.                                                                       test standards address this potential
                                                      Specifically, DOE requests comment on                    air dry bulb temperature cooling the
                                                                                                               duct walls can be lower than the dew                  variation, which could result in
                                                      whether there are actual differences in                                                                        differences in test results depending on
                                                      field installations and field use of this                point of the warm moist air leaving the
                                                                                                               outdoor unit. This condensation would                 whether this feature was employed in a
                                                      equipment and on the extent to which                                                                           test.
                                                      these differences impact performance.                    be unaccounted for by the outdoor air
                                                                                                               enthalpy method, resulting in a                          Issue CUAC–24: DOE seeks comment
                                                      d. Make-Up Water Temperature                             calculated capacity less than the actual              on whether ECUACs that allow piping
                                                      (ECUAC)                                                  capacity. To consider another approach,               of evaporator condensate to the
                                                        Neither AHRI 340/360–2007 nor                          DOE notes that it modified the CAC/HP                 condenser sump present any
                                                      AHRI 340/360–2015 provide any                            test method to require a secondary                    complications (e.g., maintaining proper
                                                      requirements on the make-up water                        capacity measurement only for full-load               slope in the piping from the evaporator
                                                      temperature for the standard rating                      operation for cooling and heating, rather             to the outdoor unit and test repeatability
                                                      condition or for the part-load IEER tests.               than for all tests in a January 5, 2017               issues) when testing in a laboratory.
                                                      Make-up water must be supplied to the                    final rule. 82 FR 1426, 1441. While this              DOE also seeks comment or data
                                                      sump of an ECUAC to replenish the                        change was for central air conditioners               indicating what kind of impact piping
                                                      evaporated water (or to spray nozzles for                and heat pumps, limiting the secondary                the evaporator condensate to the
                                                      models without sumps). AHRI 210/240–                     method test to a single set of conditions,            condenser sump has on the efficiency
                                                      2008 and AHRI 210/240–2015–Draft                         such as the full-load cooling (and                    and/or capacity of ECUACs.
                                                      specify 85.0 °F for the full-load standard               heating, if applicable) test conditions,
                                                      rating condition and 77.0 °F for the part-               would eliminate or reduce the potential               g. Purge Water Settings (ECUAC)
                                                      load tests. Cooler makeup water                          for condensation in the outdoor supply
                                                                                                                                                                       Some ECUACs require the sump
                                                      temperature could increase measured                      duct when testing ECUACs.
                                                                                                                                                                     water to be continuously or periodically
                                                      cooling capacity and vice versa, causing                    Issue CUAC–21: DOE seeks comment
                                                                                                               or test data on the difficulty of getting             purged in order to reduce mineral and
                                                      variation in measurements if specific
                                                                                                               a match of primary and secondary                      scale build-up on the condenser heat
                                                      temperatures are not required.
                                                        Issue CUAC–20: DOE seeks comment                       capacity measurements when testing                    exchanger. AHRI 340/360–2015
                                                      or data regarding the impact that the                    ECUACs with rated capacities less than                provides guidance to set up and
                                                      make-up water temperature has on the                     135,000 Btu/h and whether the                         configure the unit per the
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      unit performance. DOE also seeks                         difficulty level is higher, lower, or the             manufacturer’s installation instructions,
                                                      comment or data on whether the make-                     same when testing the unit at full-load               which would include setting the purge
                                                      up water temperatures, including the                     conditions as compared to part-load                   rate if specified.
                                                      temperatures for part-load conditions,                   conditions. DOE also seeks comment                      Issue CUAC–25: DOE seeks comment
                                                      specified in AHRI 210/240–2008 and                       and data on how often the primary                     on how the purge water rate should be
                                                      AHRI 210/240–2015–Draft are                              capacity measurement results in an                    set for laboratory testing if the
                                                      representative of conditions                             exceeded allowable percent difference                 manufacturer’s installation instructions
                                                      experienced by field-installed ECUACs                    between the primary and secondary                     do not contain information on this
                                                      of all cooling capacities.                               capacity measurements.                                topic.


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00018   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                                   34445

                                                      h. Condenser Spray Pumps (ECUAC)                         16, 2012). DOE’s current regulations                   air conditioning and heat pump
                                                        The rate that water is sprayed on the                  require that manufacturers test VRF                    equipment since the 2008 Supplement
                                                      condenser coil may have an impact on                     multi-split systems using AHRI 1230–                   to Standard 90.1–2007, effective January
                                                      the performance of an ECUAC. For units                   2010 with addendum 1, except for                       1, 2010.14 15 ASHRAE Standard 90.1–
                                                      with sumps, this rate may be affected by                 sections 5.1.2 and 6.6. DOE’s current                  2013 included minimum efficiency
                                                      the pump set-up, and, for units without                  test procedure also requires that                      levels for both the EER and IEER of air-
                                                      sumps, the incoming water pressure                       manufacturers adhere to certain                        cooled VRF multi-split systems and for
                                                      may have an impact. Neither DOE’s                        additional requirements listed in 10                   the EER of water-source VRF multi-split
                                                      current test procedures nor the industry                 CFR 431.96(c)–(f). Although ASHRAE                     systems. ASHRAE Standard 90.1–2016
                                                      ECUAC test standards address these                       90.1–2016 did not update its test                      added IEER levels for water-source VRF
                                                      potential variations.                                    procedure reference for VRF (AHRI                      multi-split systems, including units
                                                        Issue CUAC–26: DOE requests                            1230–2010 with addendum 1), DOE is                     with cooling capacity less than 65,000
                                                      comment on whether the pump flow                         reviewing its test procedure in response               Btu/h. DOE notes that in addition to
                                                      can be adjusted on any ECUACs on the                     to the seven-year-lookback statutory                   ASHRAE 90.1, both the ENERGY STAR
                                                      market that have circulation pumps.                      review requirement (see 42 U.S.C.                      and Consortium for Energy Efficiency
                                                      DOE also requests comment on whether                     6314(a)(1)(A)), and in advance of its                  (CEE) programs use the IEER metric for
                                                      ECUACs without a sump exist and, if so,                  review of energy conservation standards                VRF systems.16 17
                                                      whether there are requirements on the                    for VRF in response to changes in                         On January 15, 2016, DOE published
                                                      incoming water pressure to ensure                        ASHRAE 90.1–2016.                                      a direct final rule for energy
                                                      proper operation of the spray nozzles.                     As part of its seven-year-lookback                   conservation standards for small, large,
                                                      DOE also requests comments and/or                        review, DOE is examining updated                       and very large air-cooled commercial
                                                      data regarding the sensitivity of                        industry test standards, including                     package air conditioners and heat
                                                      performance test results to these                        Addendum 2 to AHRI 1230–2010                           pumps (CUACs and CUHPs), which
                                                      adjustments.                                             (approved June 2014) and a draft                       amended the energy conservation
                                                                                                               version of AHRI 1230 provided by AHRI                  standards for CUACs and CUHPs and
                                                      i. Additional Steps To Verify Proper                     for the docket that will supersede AHRI                changed the cooling efficiency metric
                                                      Operation (ECUAC)                                        1230–2010 (with Addendum 1 and 2)                      from EER to IEER. 81 FR 2420. Except
                                                         Some ECUACs may use spray nozzles                     once published (‘‘AHRI 1230-Draft,’’                   possibly for ventilation, VRF multi-split
                                                      with very small diameter openings that                   No. 1). DOE reviewed the AHRI 1230-                    systems serve the same primary
                                                      may become easily clogged, thereby                       Draft and discusses in the following                   functions as CUACs and CUHPs (i.e.,
                                                      reducing the effectiveness of the heat                   sections specific issues regarding the                 space heating and cooling commercial
                                                      exchanger.                                               draft and other items related to the VRF               buildings) and are used in a similarly
                                                         Issue CUAC–27: DOE requests                           test procedure.                                        wide range of climatic conditions.
                                                      comment on whether there are any                                                                                   Because the vast majority of cooling
                                                                                                               1. Energy Efficiency Descriptors
                                                      additional steps that should be taken to                                                                        and heating loads do not demand
                                                      verify proper operation of ECUACs                           DOE currently prescribes energy                     operation at full-load, the full-season
                                                      during testing, such as ensuring nozzles                 conservation standards for air-cooled                  metric IEER may capture the efficiency
                                                      are not blocked.                                         VRF multi-split systems with cooling                   of VRF multi-split systems operating in
                                                         Issue CUAC–28: DOE requests                           capacity greater than or equal to 65,000               the field more realistically than does the
                                                      comment on any additional issues                         Btu/h and water-source VRF multi-split                 full-load metric EER. DOE believes that
                                                      associated with adopting AHRI 340/                       systems in terms of the EER metric for                 the publication of IEER ratings for most
                                                      360–2015 for ACUACs, ECUACs, and                         cooling-mode operation and in terms of                 units on the market (as in AHRI’s
                                                      WCUACs.                                                  the coefficient of performance (COP)                   Directory of Certified Product
                                                                                                               metric for heating-mode operation.13                   Performance for VRF multi-split
                                                      D. Test Procedure for Variable                           DOE is considering whether to add or                   systems), as well as the inclusion of
                                                      Refrigerant Flow Multi-Split Air                         replace the existing cooling-mode                      minimum efficiency levels and test
                                                      Conditioners and Heat Pumps                              efficiency descriptor (i.e., EER) with a               procedures for IEER of VRF multi-split
                                                        DOE’s commercial equipment                             new cooling-mode energy-efficiency                     systems in ASHRAE Standard 90.1–
                                                      regulations include test procedures and                  descriptor that better captures part-load              2016 and AHRI 1230–2010,
                                                      energy conservation standards that                       performance, such as IEER.                             respectively, demonstrate that IEER is
                                                      apply to air-cooled VRF multi-split air                     IEER factors in the efficiency of                   an industry-accepted metric for
                                                      conditioners, air-cooled VRF multi-split                 operating at part-load conditions of 75-               measuring efficiency of VRF multi-split
                                                      heat pumps, and water-source VRF                         percent, 50-percent, and 25-percent of                 systems. For these reasons, DOE is
                                                      multi-split heat pumps, all with cooling                 capacity, as well as the efficiency at full-           considering replacing the current EER
                                                      capacity less than 760,000 Btu/h, except                 load. The IEER metric provides a more                  metric for VRF multi-split systems with
                                                      air-cooled, single-phase VRF multi-split                 representative measure of energy
                                                      air conditioners and heat pumps with                     consumption in actual operation by                       14 ASHRAE Standard 90.1 first specified a part-

                                                      cooling capacity less than 65,000 Btu/h                  weighting the full-load and part-load                  load performance metric in the 2007 edition, which
                                                      (which are covered by DOE’s consumer                     efficiencies with the average amount of                used integrated part load value (IPLV).
                                                                                                                                                                        15 ASHRAE, ASHRAE Addenda (2008
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      product regulations for central air                      time equipment spends operating at
                                                                                                                                                                      Supplement) (Available at: http://www.ashrae.org/
                                                      conditioners 12). 10 CFR 431.96 and                      each load point. ASHRAE 90.1 has                       File%20Library/docLib/Public/20090317_90_1_
                                                      431.97.                                                  specified an IEER metric for commercial                2007_supplement.pdf).
                                                        DOE’s test procedure for (commercial)                                                                           16 ENERGY STAR Program Requirements,

                                                      VRF multi-split systems is codified at 10                  13 DOE also prescribes energy conservation           Product Specifications for Light Commercial HVAC
                                                                                                               standards for three-phase air-cooled VRF multi-split   (Available at: https://www.energystar.gov/sites/
                                                      CFR 431.96 and was established in the                                                                           default/files/specs//private/LC_HVAC_V2.2.pdf).
                                                                                                               systems with cooling capacity less than 65,000
                                                      May 2012 final rule. 77 FR 28928 (May                    Btu/h in terms of the SEER metric for cooling-mode       17 Consortium for Energy Efficiency, CEE

                                                                                                               operation and in terms of the heating seasonal         Commercial Unitary AC and HP Specification
                                                        12 See 10 CFR 430.32(c) and Appendix M and M1          performance factor (HSPF) metric for heating-mode      (Available at: http://www.cee1.org/files/CEE_
                                                      to Subpart B of Part 430.                                operation.                                             CommHVAC_UnitarySpec2012.pdf).



                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00019   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34446                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      the full-season IEER metric, or adding                   percent load). Specifically, are there                DOE expects that maintenance of
                                                      IEER in addition to EER. DOE’s ultimate                  field data available that show operating              steady-state conditions may be affected
                                                      decision will be impacted by the                         states of VRF multi-split systems at                  during oil recovery mode and that, as a
                                                      separate energy conservation standards                   different load levels? Such data might                result, some type of transient test
                                                      rulemaking considering the efficiency                    show what happens with indoor fan                     procedure may be appropriate when oil
                                                      levels for VRF in ASHRAE 90.1–2016.                      speeds and expansion devices of indoor                recovery mode happens during testing.
                                                         Issue VRF–1: DOE requests comment                     units at low load percentages, including              However, AHRI 1230-Draft does not
                                                      on issues DOE should consider                            whether any indoor fans shut off, or                  specify use of the transient test for this
                                                      regarding potentially using IEER as an                   whether any refrigerant flow control                  case, and the ASHRAE 37–2009
                                                      efficiency metric for energy                             devices shut off refrigerant flow, and                description of the transient test does not
                                                      conservation standards for air-cooled                    how this might be affected by the user-               mention oil recovery. DOE notes that
                                                      VRF multi-split systems with a cooling                   accessible control positions set for the              VRF multi-split systems vary in the way
                                                      capacity greater than or equal to 65,000                 indoor units. DOE is also interested in               they activate oil recovery mode; some
                                                      Btu/h and all water-source VRF multi-                    whether indoor unit operation at low                  may initiate oil recovery mode at a set
                                                      split systems, so as to capture efficiency               compressor speeds is different in field               time interval, and others may instead
                                                      in part-load operation.                                  application for VRF multi-split systems               initiate oil recovery mode only when
                                                      2. Representativeness and Repeatability                  with cooling capacities less than 65,000              the system detects that the oil level in
                                                                                                               Btu/h than those with capacities greater              the compressor has reached a certain
                                                         Operation of VRF multi-split systems                  than or equal to 65,000 Btu/h, and
                                                      is inherently variable, and DOE notes                                                                          minimum level. DOE understands that
                                                                                                               whether these trends follow at                        unit performance may vary with the oil
                                                      that the control systems of VRF multi-                   intermediate compressor speeds as well.
                                                      split systems can be significantly more                                                                        level. Consequently, DOE is considering
                                                                                                               Further, DOE requests data that would                 requiring all measurements to be made
                                                      sophisticated than control systems in
                                                                                                               show the trends of total system capacity,             within a certain time after the last oil
                                                      other commercial HVAC systems. In
                                                                                                               total indoor air flow, and sensible heat              recovery to ensure repeatability between
                                                      order to achieve steady-state operation,
                                                                                                               ratio as a function of compressor speed               tests.
                                                      it is generally necessary for a
                                                                                                               (e.g., percentage of full-speed
                                                      manufacturer’s representative that is                                                                            Issue VRF–4: DOE requests comment
                                                                                                               revolutions per minute) for laboratory
                                                      knowledgeable about the control system                                                                         on the impact of oil recovery mode,
                                                                                                               rating tests of typical VRF multi-split
                                                      to be present during testing in order to                                                                       including power input and heating/
                                                                                                               systems conducted either with one or no
                                                      override the typical dynamic control                                                                           cooling provided to space during oil
                                                                                                               indoor unit shut off at the lowest load
                                                      and to set each individual component at                                                                        recovery mode. DOE also requests
                                                                                                               point.
                                                      a fixed position or speed. It may be                                                                           comment on whether any VRF multi-
                                                      possible to achieve ‘‘full-load’’ capacity               3. Test Method                                        split systems operate in oil recovery
                                                      and/or part-load operation in different                                                                        mode more frequently than every two
                                                                                                               a. Transient Testing: Oil Recovery Mode
                                                      ways, all of which may be consistent                                                                           hours of continuous operation. For such
                                                      with the test procedure and                                 AHRI 1230-Draft refers to ASHRAE                   systems, DOE requests comment on
                                                      manufacturer’s installation instructions.                37–2009 for provisions for transient                  whether the test method should be
                                                         Issue VRF–2: DOE seeks comment on                     tests, which are required when defrost                modified to address the transient
                                                      the settings required to be reported in                  interferes with steady-state operation                operation occurring during and after oil
                                                      order for third-party laboratories to                    sufficiently frequently to prevent                    recovery, and how this should be done.
                                                      reproduce unit performance in a rating                   completion of a steady-state test (see, for           In addition, DOE requests comment on
                                                      test.                                                    example, sections 8.8.2.5.1 and 8.8.2.5.2             the performance variation associated
                                                         Section 6.3.4 of AHRI 1230–Draft                      of that test standard). Specific                      with oil level and whether all
                                                      requires that for air-cooled VRF multi-                  instructions are provided for how to                  measurements should be made within a
                                                      split systems with a cooling capacity                    determine an average heating capacity                 certain time after the last oil recovery.
                                                      less than 65,000 Btu/h, at least one                     for the transient test, with different                Lastly, DOE requests comment on how
                                                      indoor unit must be turned off for tests                 instructions depending on the number                  the energy use of oil recovery mode
                                                      conducted at minimum compressor                          and completion of defrost cycles. Tables              might be addressed in the test procedure
                                                      speed. DOE also established a similar                    2a and 2b of ASHRAE 37–2009 specify                   without imposing excessive test burden.
                                                      requirement for CACs in the June 2016                    the test tolerances to be used when
                                                      CAC TP final rule. 81 FR 36992, 37038                    conducting a transient heating capacity               b. Airflow Setting and Minimum
                                                      (June 8, 2016). However, AHRI 1230-                      test.                                                 External Static Pressure
                                                      Draft does not include a corresponding                      VRF multi-split systems may
                                                      requirement for equipment with a                         periodically operate in an oil recovery                 DOE notes AHRI 1230–Draft contains
                                                      cooling capacity greater than or equal to                mode in order to return oil from the                  one set of instructions for setting the
                                                      65,000 Btu/h or for water-source VRF                     refrigeration loop to the compressor.                 indoor air flow rates for systems with
                                                      multi-split systems. This requirement                    Section 5.1.3 of AHRI 1230–Draft                      capacities less than 65,000 Btu/h
                                                      for equipment less than 65,000 Btu/h                     requires that if a manufacturer indicates             (section 6.3.3.1) and another set for
                                                      considers the wide range of loads that                   that a VRF multi-split system is                      systems with capacities larger than
                                                      can occur in the field. However, DOE                     designed to recover oil more frequently               65,000 Btu/h (section 6.4.1). It is not
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      expects that load diversity would also                   than every two hours of continuous                    clear why alternate approaches are
                                                      be an issue for larger-capacity VRF                      operation, the oil recovery mode shall                required for different systems because
                                                      multi-split systems used in commercial                   be activated during testing, and the                  the indoor units generally do not differ
                                                      applications.                                            additional power shall be included in                 by system capacity.
                                                         Issue VRF–3: DOE requests                             the efficiency calculations. However,                   Issue VRF–5: DOE requests comment
                                                      information and data on the field                        there is no specific instruction in the               on whether there should be a consistent
                                                      operating states of indoor units of VRF                  AHRI 1230–Draft that indicates how the                approach for setting indoor airflow
                                                      multi-split systems when operating at                    additional power should be                            across all capacity ranges of VRF multi-
                                                      low compressor speeds (i.e., near 25-                    incorporated into the efficiency metric.              split systems.


                                                 VerDate Sep<11>2014   18:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00020   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                             34447

                                                      c. Condenser Head Pressure Controls                      inconsistent with field operation.                     having a total cooling capacity less than
                                                         Condenser head pressure controls                      Section 6.3.3.1.1.3 of AHRI 1230–Draft                 135,000 Btu/h) can or cannot be
                                                      regulate the flow of refrigerant through                 added an upper limit on air flow per                   performed. DOE also requests comment
                                                      the condenser and/or adjust operation of                 capacity for non-ducted units for                      on how to standardize the selection of
                                                      condenser fans to prevent condenser                      systems with capacity less than 65,000                 test methods for measuring the capacity
                                                      pressures from dropping too low during                   Btu/h—the rated air volume for each                    of VRF multi-split systems. Finally,
                                                      low-ambient operation. When                              indoor unit must not exceed 55 scfm per                DOE requests comment on whether
                                                      employed, these controls ensure that the                 1,000 Btu/h.18                                         there are issues with achieving heat
                                                                                                                  Issue VRF–7: DOE requests comment                   balance in part-load tests for VRF multi-
                                                      refrigerant pressure is high enough to
                                                                                                               on how to confirm air flow for each                    split systems, similar to those cited for
                                                      maintain adequate flow through
                                                                                                               indoor unit individually when there is                 variable speed CAC/HP, and if so,
                                                      refrigerant expansion devices such as
                                                                                                               a common duct for each unit and when                   whether there is sufficient assurance of
                                                      thermostatic expansion valves. In the
                                                                                                               there is potential deviation from free-                proper measurement for all test points
                                                      December 2015 CUAC test procedure                        discharge operation if a discharge duct
                                                      final rule, DOE required that CUACs                                                                             of VRF multi-split systems if the heat
                                                                                                               is connected. DOE also requests                        balance is verified only for full capacity.
                                                      and CUHPs equipped with head                             comment on whether there should be an
                                                      pressure controls have these controls                    upper limit of air flow per capacity for               f. Heat Recovery
                                                      activated during testing. 80 FR 79655,                   non-ducted units, such as the 55 scfm                     VRF multi-split systems with heat
                                                      79660 (Dec. 23, 2015). For VRF multi-                    per 1,000 Btu/h limit in the AHRI 1230–                recovery include a heat recovery unit
                                                      split systems equipped with heat                         Draft.                                                 (sometimes referred to as a branch
                                                      recovery, it is unclear whether the head
                                                                                                               e. Secondary Test Method                               circuit controller) that controls
                                                      pressure would be elevated when one of
                                                                                                                                                                      refrigerant flow between indoor units,
                                                      the indoor units calls for heating during                   In AHRI 1230–Draft, ASHRAE 37–                      allowing for simultaneous cooling and
                                                      cooling-based operation. It is also not                  2009 is referenced as the test procedure               heating operation. However, DOE
                                                      clear how the head pressure differs                      for both air-cooled and water-cooled                   believes that VRF multi-split systems
                                                      during cool outdoor conditions between                   units across all capacities. Section 7.2.1             with the heat recovery capability may be
                                                      units with and without heat recovery                     in ASHRAE 37–2009 requires a                           able to operate without the heat
                                                      function.                                                secondary test method in addition to the
                                                         Issue VRF–6: DOE requests comment                                                                            recovery unit attached, although in such
                                                                                                               primary method (i.e., indoor air                       case, simultaneous heating and cooling
                                                      on the appropriateness of requiring head                 enthalpy method) for units having a
                                                      pressure control activation during                                                                              would not be possible. It is not clear in
                                                                                                               total cooling capacity less than 135,000               AHRI 1230–Draft whether VRF multi-
                                                      testing of VRF multi-split systems. In                   Btu/h. ASHRAE 37–2009 provides
                                                      addition, DOE requests comment on any                                                                           split systems capable of heat recovery
                                                                                                               multiple options for the secondary test
                                                      methods to control VRF multi-split                                                                              must be tested with the heat recovery
                                                                                                               method. For units with a cooling
                                                      systems during testing to ensure stable                                                                         unit attached in tests for determining
                                                                                                               capacity larger than 135,000 Btu/h,
                                                      operation with head pressure controls                                                                           EER, IEER, and COP. DOE seeks
                                                                                                               section 7.2.2 of ASHRAE 37–2009 only
                                                      activated. Further, DOE requests                                                                                clarification on industry practice for
                                                                                                               requires a single method, but provides
                                                      comment on any methods that could be                                                                            testing VRF multi-split systems with the
                                                                                                               multiple test method options.
                                                      added to the test procedure for                             Section 11.1.1.7 of AHRI 1230–Draft                 heat recovery feature because
                                                      calculation of system efficiency of VRF                  indicates the redundant measurement                    attachment of the heat recovery unit
                                                      multi-split systems if head pressure                     verification method as an alternative to               may affect test results.
                                                      controls prevent stable operation at low-                refrigerant enthalpy method or outdoor                    Issue VRF–9: DOE seeks comment on
                                                      ambient, part-load conditions.                           enthalpy method when they cannot be                    whether VRF multi-split systems with
                                                                                                               performed. However, the draft does not                 the heat recovery feature can be
                                                      d. Air Volume Rate for Non-Ducted                        provide guidance on how to determine                   operated without the heat recovery unit
                                                      Indoor Units                                             whether the refrigerant enthalpy method                attached, and if so, whether such
                                                         DOE notes the following issues                        or outdoor enthalpy method can or                      systems are typically tested for
                                                      associated with testing multi-split                      cannot be performed. DOE is                            determining EER, IEER, and COP with
                                                      systems with free discharge air flow                     considering whether there are other                    the heat recovery unit attached.
                                                      from the indoor unit (i.e., airflow                      alternatives to the refrigerant enthalpy               Additionally, DOE seeks data showing
                                                      provided directly from the indoor unit                   method or outdoor enthalpy method                      the difference in test results between
                                                      to the conditioned space without the                     (other than the duplicate measurement                  having the heat recovery unit attached
                                                      use of ducts). In testing, if a common                   method), such as the cooling condensate                or not.
                                                      duct is used for the combined discharge                  and indirect airflow measurement                       4. Representations
                                                      airflow of multiple individual units, the                method.
                                                      airflow for each individual unit cannot                     Issue VRF–8: DOE requests comment                   a. Tested Combination
                                                      be verified. Second, even if the ESP is                  on the methods generally used for                         AHRI specified requirements for
                                                      set to zero—which is intended to                         measurement of capacity when testing                   tested combinations for systems with
                                                      replicate operation without ducting—                     VRF multi-split systems and whether                    capacities more than 65,000 Btu/h in
                                                      based on a measurement of downstream                     the selection of methods differs between               section 6.2.2 of the AHRI 1230–Draft.
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      pressure in a discharge duct, this does                  cooling and heating tests. DOE requests                The AHRI requirement specifies
                                                      not always guarantee that flow is                        comment on how to determine whether                    selecting standard 4-way ceiling cassette
                                                      identical to free discharge conditions,                  the refrigerant enthalpy method or                     indoor units with the smallest coil
                                                      due to sensitivity of such in-duct                       outdoor air enthalpy method (for units                 volume per nominal capacity for non-
                                                      pressure measurements to the air                                                                                ducted indoor units and selecting mid-
                                                                                                                 18 DOE notes that test methods associated with
                                                      movement in the duct. Finally,                                                                                  static units for ducted indoor units. DOE
                                                                                                               the indoor units of systems with capacity <65,000
                                                      specification of unusually high air flows                Btu/h are relevant for testing of systems with
                                                                                                                                                                      is aware that there is a range of ductless
                                                      for testing of free discharge in indoor                  capacity ≥65,000 Btu/h because the capacities of the   indoor unit styles, which may have a
                                                      units may boost measured performance                     indoor units are comparable.                           range of efficiency characteristics. In


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00021   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                      34448                    Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules

                                                      addition, ducted systems may serve a                     E. Other Test Procedure Topics                           Instructions: All submissions received
                                                      range of external static pressures.                        In addition to the issues identified                must include the agency name and
                                                         A report by the Cadeo Group 19                        earlier in this document, DOE welcomes                docket number and/or RIN for this
                                                      indicates that 4-way ceiling cassettes are               comment on any other aspect of the                    rulemaking. No telefacsimilies (faxes)
                                                      the most prevalent non-ducted indoor                     existing test procedures for commercial               will be accepted.
                                                      units. On the other hand, while DOE                                                                               Docket: The docket is available for
                                                                                                               package air conditioning and heating
                                                      notes that ducted units can be classified                                                                      review at https://www.regulations.gov,
                                                                                                               equipment that is the subject of this
                                                      by the amount of static pressure they                                                                          including Federal Register notices,
                                                                                                               notice not already addressed by the
                                                      produce as either low-static, mid-static,                                                                      comments, and other supporting
                                                                                                               specific areas identified in this
                                                      or conventional-static units, DOE has no                                                                       documents/materials. All documents in
                                                                                                               document. DOE particularly seeks
                                                      data indicating which ducted unit style                                                                        the docket are listed in the https://
                                                                                                               information that would improve the                    www.regulations.gov index. However,
                                                      or static pressure classification is the                 representativeness of the test
                                                      most prevalent.                                                                                                not all documents listed in the index
                                                                                                               procedures, as well as information that               may be publicly available, such as
                                                         Issue VRF–10: DOE requests comment                    would help DOE create a procedure that
                                                      and data on variation of system                                                                                information that is exempt from public
                                                                                                               would limit manufacturer test burden                  disclosure.
                                                      efficiency related to indoor unit styles                 through streamlining or simplifying
                                                      (both for ducted and non-ducted indoor                                                                            A link to the docket Web page can be
                                                                                                               testing requirements. Comments                        found at: https://www.regulations.gov/
                                                      units). For example, for a system tested                 regarding repeatability and
                                                      with non-ducted units, what is the                                                                             docket?D=EERE-2017-BT-TP-0018. This
                                                                                                               reproducibility are also welcome.                     Web page contains a link to the docket
                                                      potential range of EER and/or IEER                         DOE also requests feedback on any
                                                      comparing the most-efficient indoor                                                                            for this notice on the https://
                                                                                                               potential amendments to the existing                  www.regulations.gov Web site. The
                                                      units with the most energy-intensive                     test procedures that could be considered
                                                      indoor units? DOE requests comment on                                                                          https://www.regulations.gov Web page
                                                                                                               to address impacts on manufacturers,                  contains instructions on how to access
                                                      its assumption that 4-way ceiling                        including small businesses. Regarding                 all documents, including public
                                                      cassettes are the most prevalent non-                    the Federal test methods, DOE seeks                   comments, in the docket.
                                                      ducted indoor unit style. DOE also                       comment on the degree to which the                       For information on how to submit a
                                                      requests data on the most prevalent                      DOE test procedures should consider                   comment, review other public
                                                      style and static pressure classification                 and be harmonized with the most recent                comments and the docket, or participate
                                                      (low-static, mid-static, or conventional-                relevant industry standards for the                   in the public meeting, contact the
                                                      static) of ducted units.                                 commercial package air conditioning                   Appliance Standards Program at (202)
                                                      b. Determination of Represented Values                   and heating equipment that is the                     586–6636 or by email:
                                                                                                               subject of this notice, and whether there             ApplianceStandardsQuestions@
                                                        DOE recognizes that non-ducted                         are any changes to the Federal test                   ee.doe.gov. DOE considers public
                                                      indoor units and ducted indoor units                     methods that would provide additional                 participation to be a very important part
                                                      operate at different levels of ESP and                   benefits to the public.                               of the process for developing test
                                                      have different limitations on ESP. The                     Additionally, DOE requests comment                  procedures and energy conservation
                                                      ESP affects the power consumed by the                    on whether the existing test procedures               standards. DOE actively encourages the
                                                      indoor fan, and, therefore, also affects                 limit a manufacturer’s ability to provide             participation and interaction of the
                                                      the measured efficiency of a VRF multi-                  additional features to consumers on the               public during the comment period at
                                                      split system. DOE is considering                         commercial package air conditioning                   each stage of the rulemaking process.
                                                      requiring separate ratings for different                 and heating equipment that is the                     Interactions with and between members
                                                      ESP levels to account for differences                    subject of this notice. DOE particularly              of the public provide a balanced
                                                      between ducted indoor units, non-                        seeks information on how the test                     discussion of the issues and assist DOE
                                                      ducted indoor units, and possibly other                  procedures could be amended to reduce                 in the rulemaking process. Anyone who
                                                      distinctions in indoor units.                            the cost of new or additional features                wishes to be added to the DOE mailing
                                                        Issue VRF–11: DOE requests comment                     and make it more likely that such                     list to receive future notices and
                                                      on how many distinctly identifiable ESP                  features are included on the equipment.               information about this rulemaking
                                                      levels are generally represented in a                                                                          should contact Appliance and
                                                      family of VRF multi-split systems and                    III. Submission of Comments
                                                                                                                                                                     Equipment Standards Program staff at
                                                      what ESP levels are typical for VRF                        DOE invites all interested parties to               (202) 586–6636 or by email at
                                                      multi-split systems. DOE also requests                   submit in writing by August 24, 2017,                 ApplianceStandardsQuestions@
                                                      data that demonstrate how different ESP                  comments, data, and information on                    ee.doe.gov.
                                                      levels affect measured efficiency for the                matters addressed in this notice and on                  Submitting comments via https://
                                                      system, both in terms of EER and IEER.                   other matters relevant to DOE’s                       www.regulations.gov. The https://
                                                        Issue VRF–12: DOE requests comment                     consideration of amended test                         www.regulations.gov Web page will
                                                      on what specific topics pertaining to the                procedures for VRF multi-split systems,               require you to provide your name and
                                                      test procedure for VRF multi-split air                   CRAC and DOAS equipment, and water-                   contact information. Your contact
                                                      conditioners and heat pumps, in                          cooled, evaporatively-cooled, and air-                information will be viewable to DOE
                                                      addition to the topics discussed                         cooled commercial unitary air                         Building Technologies staff only. Your
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      previously, are not fully or                             conditioners (WCUACs, ECUACs, and                     contact information will not be publicly
                                                      appropriately addressed in the docketed                  ACUACs). These comments and                           viewable except for your first and last
                                                      AHRI–1230–Draft.                                         information will aid in the development               names, organization name (if any), and
                                                                                                               of a test procedure NOPR for the subject              submitter representative name (if any).
                                                        19 Cadeo Report. See docket: EERE–2017–BT–TP–          VRF multi-split systems, and CRAC,                    If your comment is not processed
                                                      0018. No. 2. The report presents market share by         DOAS, WCUAC, ECUAC, and ACUAC                         properly because of technical
                                                      VRF multi-split system equipment class, based on
                                                      confidential sales data given in interviews with
                                                                                                               equipment, if DOE determines that                     difficulties, DOE will use this
                                                      several major manufacturers of VRF multi-split           amended test procedures may be                        information to contact you. If DOE
                                                      equipment and DOE’s CCMS database.                       appropriate for these products.                       cannot read your comment due to


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00022   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1


                                                                               Federal Register / Vol. 82, No. 141 / Tuesday, July 25, 2017 / Proposed Rules                                                 34449

                                                      technical difficulties and cannot contact                   Comments, data, and other                          actively encourages the participation
                                                      you for clarification, DOE may not be                    information submitted to DOE                          and interaction of the public during the
                                                      able to consider your comment.                           electronically should be provided in                  comment period in each stage of the
                                                         However, your contact information                     PDF (preferred), Microsoft Word or                    rulemaking process. Interactions with
                                                      will be publicly viewable if you include                 Excel, WordPerfect, or text (ASCII) file              and between members of the public
                                                      it in the comment itself or in any                       format. Provide documents that are not                provide a balanced discussion of the
                                                      documents attached to your comment.                      secured, that are written in English, and             issues and assist DOE in the rulemaking
                                                      Any information that you do not want                     that are free of any defects or viruses.              process. Anyone who wishes to be
                                                      to be publicly viewable should not be                    Documents should not contain special                  added to the DOE mailing list to receive
                                                      included in your comment, nor in any                     characters or any form of encryption                  future notices and information about
                                                      document attached to your comment.                       and, if possible, they should carry the               this rulemaking should contact
                                                      Otherwise, persons viewing comments                      electronic signature of the author.                   Appliance and Equipment Standards
                                                      will see only first and last names,                         Campaign form letters. Please submit               Program staff at (202) 586–6636 or via
                                                      organization names, correspondence                       campaign form letters by the originating              email at
                                                      containing comments, and any                             organization in batches of between 50 to              ApplianceStandardsQuestions@
                                                      documents submitted with the                             500 form letters per PDF or as one form               ee.doe.gov.
                                                      comments.                                                letter with a list of supporters’ names
                                                                                                                                                                       Issued in Washington, DC, on July 11,
                                                         Do not submit to https://                             compiled into one or more PDFs. This                  2017.
                                                      www.regulations.gov information for                      reduces comment processing and
                                                                                                                                                                     Kathleen B. Hogan,
                                                      which disclosure is restricted by statute,               posting time.
                                                      such as trade secrets and commercial or                     Confidential Business Information.                 Deputy Assistant Secretary for Energy
                                                                                                               According to 10 CFR 1004.11, any                      Efficiency, Energy Efficiency and Renewable
                                                      financial information (hereinafter
                                                                                                                                                                     Energy.
                                                      referred to as Confidential Business                     person submitting information that he
                                                                                                                                                                     [FR Doc. 2017–15580 Filed 7–24–17; 8:45 am]
                                                      Information (CBI)). Comments                             or she believes to be confidential and
                                                      submitted through https://                               exempt by law from public disclosure                  BILLING CODE 6450–01–P

                                                      www.regulations.gov cannot be claimed                    should submit via email, postal mail, or
                                                      as CBI. Comments received through the                    hand delivery/courier two well-marked
                                                      Web site will waive any CBI claims for                   copies: One copy of the document                      DEPARTMENT OF TRANSPORTATION
                                                      the information submitted. For                           marked ‘‘confidential’’ including all the
                                                      information on submitting CBI, see the                   information believed to be confidential,              Federal Aviation Administration
                                                      Confidential Business Information                        and one copy of the document marked
                                                      section.                                                 ‘‘non-confidential’’ with the information             14 CFR Part 39
                                                         DOE processes submissions made                        believed to be confidential deleted.                  [Docket No. FAA–2017–0707; Directorate
                                                      through https://www.regulations.gov                      Submit these documents via email or on                Identifier 2016–NM–014–AD]
                                                      before posting. Normally, comments                       a CD, if feasible. DOE will make its own
                                                                                                                                                                     RIN 2120–AA64
                                                      will be posted within a few days of                      determination about the confidential
                                                      being submitted. However, if large                       status of the information and treat it                Airworthiness Directives; Airbus
                                                      volumes of comments are being                            according to its determination.                       Airplanes
                                                      processed simultaneously, your                              Factors of interest to DOE when
                                                      comment may not be viewable for up to                    evaluating requests to treat submitted                AGENCY: Federal Aviation
                                                      several weeks. Please keep the comment                   information as confidential include: (1)              Administration (FAA), DOT.
                                                      tracking number that https://                            A description of the items, (2) whether               ACTION: Notice of proposed rulemaking
                                                      www.regulations.gov provides after you                   and why such items are customarily                    (NPRM).
                                                      have successfully uploaded your                          treated as confidential within the
                                                      comment.                                                 industry, (3) whether the information is              SUMMARY:    We propose to adopt a new
                                                         Submitting comments via email, hand                   generally known by or available from                  airworthiness directive (AD) for certain
                                                      delivery/courier, or postal mail.                        other sources, (4) whether the                        Airbus Model A318 series airplanes;
                                                      Comments and documents submitted                         information has previously been made                  Model A319 series airplanes; Model
                                                      via email, hand delivery/courier, or                     available to others without obligation                A320–211, –212, –214, –231, –232, and
                                                      postal mail also will be posted to                       concerning its confidentiality, (5) an                –233 airplanes; and Model A321 series
                                                      https://www.regulations.gov. If you do                   explanation of the competitive injury to              airplanes. This proposed AD was
                                                      not want your personal contact                           the submitting person which would                     prompted by reports of fatigue damage
                                                      information to be publicly viewable, do                  result from public disclosure, (6) when               in the structure for the door stop fittings
                                                      not include it in your comment or any                    such information might lose its                       on certain fuselage frames (FR). This
                                                      accompanying documents. Instead,                         confidential character due to the                     proposed AD would require repetitive
                                                      provide your contact information in a                    passage of time, and (7) why disclosure               rototest inspections for cracking of the
                                                      cover letter. Include your first and last                of the information would be contrary to               fastener holes in certain door stop
                                                      names, email address, telephone                          the public interest.                                  fittings, and repair if necessary. We are
                                                      number, and optional mailing address.                       It is DOE’s policy that all comments               proposing this AD to address the unsafe
                                                      The cover letter will not be publicly                    may be included in the public docket,                 condition on these products.
asabaliauskas on DSKBBY8HB2PROD with PROPOSALS




                                                      viewable as long as it does not include                  without change and as received,                       DATES: We must receive comments on
                                                      any comments.                                            including any personal information                    this proposed AD by September 8, 2017.
                                                         Include contact information each time                 provided in the comments (except                      ADDRESSES: You may send comments,
                                                      you submit comments, data, documents,                    information deemed to be exempt from                  using the procedures found in 14 CFR
                                                      and other information to DOE. If you                     public disclosure).                                   11.43 and 11.45, by any of the following
                                                      submit via mail or hand delivery/                           DOE considers public participation to              methods:
                                                      courier, please provide all items on a                   be a very important part of the process                  • Federal eRulemaking Portal: Go to
                                                      CD, if feasible, in which case it is not                 for developing test procedures and                    http://www.regulations.gov. Follow the
                                                      necessary to submit printed copies.                      energy conservation standards. DOE                    instructions for submitting comments.


                                                 VerDate Sep<11>2014   17:17 Jul 24, 2017   Jkt 241001   PO 00000   Frm 00023   Fmt 4702   Sfmt 4702   E:\FR\FM\25JYP1.SGM   25JYP1



Document Created: 2018-10-24 11:20:58
Document Modified: 2018-10-24 11:20:58
CategoryRegulatory Information
CollectionFederal Register
sudoc ClassAE 2.7:
GS 4.107:
AE 2.106:
PublisherOffice of the Federal Register, National Archives and Records Administration
SectionProposed Rules
ActionRequest for information (RFI).
DatesWritten comments, data, and information are requested and will be accepted on or before August 24, 2017.
ContactMs. Catherine Rivest, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202) 586-7335. Email: ApplianceS[email protected]
FR Citation82 FR 34427 
RIN Number1904-AD93
CFR Citation10 CFR 429
10 CFR 431

2025 Federal Register | Disclaimer | Privacy Policy
USC | CFR | eCFR