81_FR_22325 81 FR 22252 - Notice of Petition for Waiver From Cleaver-Brooks From the Department of Energy Commercial Packaged Boiler Test Procedure

81 FR 22252 - Notice of Petition for Waiver From Cleaver-Brooks From the Department of Energy Commercial Packaged Boiler Test Procedure

DEPARTMENT OF ENERGY
Office of Energy Efficiency and Renewable Energy

Federal Register Volume 81, Issue 73 (April 15, 2016)

Page Range22252-22255
FR Document2016-08750

This notice announces receipt of a petition for waiver from Cleaver-Brooks seeking an exemption from specified portions of the U.S. Department of Energy (DOE) test procedure applicable to commercial packaged boilers. Cleaver-Brooks contends that some of their commercial packaged boilers cannot be accurately tested using the currently applicable DOE test procedure and, as a result, seeks to use an alternate test procedure to test these basic models. DOE solicits comments, data, and information concerning Cleaver-Brooks' petition and the suggested alternate test procedure.

Federal Register, Volume 81 Issue 73 (Friday, April 15, 2016)
[Federal Register Volume 81, Number 73 (Friday, April 15, 2016)]
[Notices]
[Pages 22252-22255]
From the Federal Register Online  [www.thefederalregister.org]
[FR Doc No: 2016-08750]


-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

Office of Energy Efficiency and Renewable Energy

[Case No. BLR-007]


Notice of Petition for Waiver From Cleaver-Brooks From the 
Department of Energy Commercial Packaged Boiler Test Procedure

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy.

ACTION: Notice of petition for waiver and request for public comments.

-----------------------------------------------------------------------

SUMMARY: This notice announces receipt of a petition for waiver from 
Cleaver-Brooks seeking an exemption from specified portions of the U.S. 
Department of Energy (DOE) test procedure applicable to commercial 
packaged boilers. Cleaver-Brooks contends that some of their commercial 
packaged boilers cannot be accurately tested using the currently 
applicable DOE test procedure and, as a result, seeks to use an 
alternate test procedure to test these basic models. DOE solicits 
comments, data, and information

[[Page 22253]]

concerning Cleaver-Brooks' petition and the suggested alternate test 
procedure.

DATES: DOE will accept comments, data, and information with respect to 
the Cleaver-Brooks petition until May 16, 2016.

ADDRESSES: You may submit comments, identified by case number ``BLR-
007,'' by any of the following methods:
     Federal eRulemaking Portal: http://www.regulations.gov. 
Follow the instructions for submitting comments.
     Email: [email protected]. Include the case 
number [Case No. BLR-007] in the subject line of the message.
     Mail: Ms. Brenda Edwards, U.S. Department of Energy, 
Building Technologies Program, Mailstop EE-2B, 1000 Independence Avenue 
SW., Washington, DC 20585-0121. Telephone: (202) 586-2945. Please 
submit one signed original paper copy.
     Hand Delivery/Courier: Ms. Brenda Edwards, U.S. Department 
of Energy, Building Technologies Program, 950 L'Enfant Plaza SW., Suite 
600, Washington, DC 20024. Please submit one signed original paper 
copy.
    Docket: For access to the docket to review the background documents 
relevant to this matter, you may visit http://www.regulations.gov. 
Available documents include the following items: (1) This notice; (2) 
public comments received; and (3) the petition for waiver.

FOR FURTHER INFORMATION CONTACT: Mr. Bryan Berringer, U.S. Department 
of Energy, Building Technologies Program, Mail Stop EE-2B, Forrestal 
Building, 1000 Independence Avenue SW., Washington, DC 20585-0121. 
Telephone: (202) 586-0371. Email: [email protected].
    Mr. Peter Cochran, U.S. Department of Energy, Office of the General 
Counsel, Mail Stop GC-33, Forrestal Building, 1000 Independence Avenue 
SW., Washington, DC 20585-0103. Telephone: (202) 586-9496. Email: 
[email protected].

SUPPLEMENTARY INFORMATION: In a petition received July 24, 2015, 
Cleaver-Brooks requested that the U.S. Department of Energy (``DOE'') 
grant a waiver to certain models of larger commercial package boilers 
that cannot be tested under the existing DOE test procedure. The models 
of commercial packaged boilers at issue are models with higher input 
capacities that typically require higher steam pressure and alternative 
instrumentation due to the large quantities of fluids being measured.

I. Background and Authority

    Title III, Part C of the Energy Policy and Conservation Act of 1975 
(EPCA), as amended (42 U.S.C. 6311 et seq.), established the Energy 
Conservation Program for certain industrial equipment, which includes 
commercial packaged boilers.\1\ Part C specifically includes 
definitions (42 U.S.C. 6311), energy conservation standards (42 U.S.C 
6313), test procedures (42 U.S.C. 6314), labeling provisions (42 U.S.C. 
6315), and the authority to require information and reports from 
manufacturers (42 U.S.C. 6316). Part C authorizes the Secretary of 
Energy (the Secretary) to prescribe test procedures that are reasonably 
designed to produce results that measure energy efficiency, energy use, 
and estimated annual operating costs, and that are not unduly 
burdensome to conduct. (42 U.S.C. 6314(a)(2)) With respect to 
commercial packaged boilers, Part C requires DOE to use industry test 
procedures developed or recognized by the Air-Conditioning, Heating, 
and Refrigeration Institute (AHRI) or the American Society of Heating, 
Refrigerating, and Air-Conditioning Engineers (ASHRAE), as referenced 
in ASHRAE/IES \2\ Standard 90.1, ``Energy Standard for Buildings Except 
Low-Rise Residential Buildings.'' (42 U.S.C. 6314(a)(4)(A)) Further, if 
such an industry test procedure is amended, DOE is required to amend 
its test procedure to be consistent with the amended industry test 
procedure, unless it determines, by rule published in the Federal 
Register and supported by clear and convincing evidence, that the 
amended test procedure would be unduly burdensome to conduct or would 
not produce test results that reflect the energy efficiency, energy 
use, and estimated operating costs of that equipment during a 
representative average use cycle. (42 U.S.C. 6314(a)(4)(B)). The test 
procedure for commercial packaged boilers is contained in 10 CFR part 
431, subpart E.
---------------------------------------------------------------------------

    \1\ For editorial reasons, upon codification in the U.S. Code, 
Part C was re-designated Part A-1.
    \2\ Illuminating Engineering Society.
---------------------------------------------------------------------------

    DOE's regulations for covered products and equipment permit a 
person to seek a waiver from the test procedure requirements for 
covered commercial equipment if at least one of the following 
conditions is met: (1) The petitioner's basic model contains one or 
more design characteristics that prevent testing according to the 
prescribed test procedures; or (2) the prescribed test procedures may 
evaluate the basic model in a manner so unrepresentative of its true 
energy consumption as to provide materially inaccurate comparative 
data. 10 CFR 431.401(a)(1). Petitioners must include in their petition 
any alternate test procedures known to the petitioner to evaluate the 
basic model in a manner representative of its energy consumption. 10 
CFR 431.401(b)(1)(iii).
    DOE may grant a waiver subject to conditions, including adherence 
to alternate test procedures. 10 CFR 431.401(f)(2). As soon as 
practicable after the granting of any waiver, DOE will publish in the 
Federal Register a notice of proposed rulemaking to amend its 
regulations so as to eliminate any need for the continuation of such 
waiver. As soon thereafter as practicable, DOE will publish in the 
Federal Register a final rule. 10 CFR 431.401(l).

II. Petition for Waiver of Test Procedure

    On July 24, 2015, Cleaver-Brooks submitted a petition for waiver 
from the DOE test procedure for certain basic models of its commercial 
packaged boilers. The DOE test procedure for commercial packaged 
boilers is set forth at 10 CFR 431.86 and incorporates by reference 
Hydronics Institute (HI) BTS-2000, ``Method to Determine Efficiency of 
Commercial Space Heating Boilers'' (BTS-2000).
    According to Cleaver-Brooks, there are several issues that make 
BTS-2000 incompatible with larger commercial packaged boilers, 
including those identified in its petition for waiver. Cleaver-Brooks 
stated that the requirements to use test conditions specified in BTS-
2000 and the instrumentation requirements are outdated. Specifically, 
Cleaver-Brooks indicated the following regarding the test conditions:
     The 0 to 2 psig test pressure for steam boilers may be 
adequate for residential and small commercial (cast iron) boilers sized 
[commercial packaged] boilers, however such steam pressures are not 
compatible with large [commercial packaged] boilers as it will cause 
water carryover in large quantities, and an inability to meet design 
water flow rates and firing rates;
     Typically test steam pressures in the range of 10 to 12 
psig are required; and
     Test temperatures defined for hot water [commercial 
packaged] boilers cause thermal shock problems in large [commercial 
packaged] boilers.
    Cleaver-Brooks also indicated the following regarding the 
instrumentation chart in Table 1 of section 6.0, ``Instruments,'' of 
BTS-2000:
     Steam pressure cannot be measured by mercury manometer as 
the use of

[[Page 22254]]

mercury in instruments and controls is banned; the correct instrument 
is a Bourdon Tube Gauge for pressures of 0 to 30 psig;
     Large boilers typically fire into a positive pressure 
combustion chamber, thus gas pressure, firebox pressure and vent/flue 
pressure instruments all need to reflect this;
     The use of scales to measure water/condensate/moisture 
flow rates is incompatible with the volume of these fluids being used 
or generated by large [commercial packaged] boilers;
     Water flow meters should be used and in the case of 
moisture content, current practice is to use a throttling calorimeter;
     The measurement of carbon dioxide as a means of 
calculating excess air or oxygen is considered obsolete in the large 
[commercial packaged] boiler industry; direct measurement of excess 
oxygen is the preferred method as modern oxygen meters can easily be 
calibrated against the oxygen in the ambient air;
     Carbon Monoxide levels are no longer measured as a 
percentage; the current preferred unit is parts per million (ppm).
    To address these concerns, Cleaver-Brooks proposes to use the newly 
published American National Standards Institute (ANSI)/Air-
Conditioning, Heating, and Refrigeration Institute (AHRI) 1500-2015, 
``Standard for Performance Rating of Commercial Space Heating Boilers'' 
(ANSI/AHRI Standard 1500-2015) in place of BTS-2000. AHRI developed 
ANSI/AHRI Standard 1500-2015 as a replacement for BTS-2000 in order to 
make the test procedure suitable for use with larger commercial 
packaged boilers, as well as improve and clarify the test method. 
Cleaver-Brooks claims that use of this ANSI/AHRI Standard 1500-2015 is 
necessary as it is compatible with the size of commercial packaged 
boilers they manufacture.
    Additionally, for the large commercial packaged boilers capable of 
supplying either steam or hot water identified in this petition, 
Cleaver-Brooks requests that, when determining the combustion 
efficiency in hot water mode based on testing in steam mode only, the 
combustion efficiency rating be determined based on an adjusted 
combustion efficiency. Cleaver-Brooks requests that an adjustment be 
made to the measured stack temperature to be used in calculating 
combustion efficiency based on the relative difference between the flue 
gas temperature and the bulk fluid temperature when operating in steam 
mode as opposed to hot water using the following relationship:
 Tstack, hw = (Tstack, steam - Tsat) + 
Tbulk, hw

where Tstack, hw is the stack temperature to be used to 
determine the combustion efficiency in hot water mode, 
Tstack, steam is the measured stack temperature when 
testing on steam, Tsat is the saturation temperature of 
steam at the test pressure, and Tbulk, hw is the 
temperature of the outlet water when testing in hot water mode and 
is equal to 180 [deg]F. According to Cleaver-Brooks, using this 
adjusted stack temperature to calculate combustion efficiency is a 
more accurate representation of the actual efficiency when operating 
as a hot water commercial packaged boiler than simply using 
combustion efficiency value for steam mode.

    The following basic models are included in Cleaver-Brooks' 
petition: CBEX-E, CBEX-P, 4WI/4WG, CBLE, CBR, CBL, CB, CFC, CFLC, CFW, 
CFH, FLX and M5.
    DOE notes that it has published a notice of proposed rulemaking 
(March 2016 CPB TP NOPR) to amend its test procedure for commercial 
packaged boilers prescribed in 10 CFR part 431 subpart E. 81 FR 14641 
(Mar. 17, 2016). The proposed amended test procedure addresses, among 
other changes, the issues raised in this waiver request by 
incorporating by reference ANSI/AHRI Standard 1500-2015 as a 
replacement for BTS-2000 in the DOE test procedure for commercial 
packaged boilers. In addition to adopting ANSI/AHRI Standard 1500-2015 
as a replacement for BTS-2000, DOE further proposes several 
modifications to its test procedure that are not captured in ANSI/AHRI 
Standard 1500-2015 in order to improve repeatability, add 
clarification, and accommodate testing of some equipment that has 
experienced difficulty in testing to the existing DOE test procedure. 
Among these changes, DOE proposes to adopt the stack temperature 
adjustment described by Cleaver-Brooks when using the tested combustion 
efficiency of large steam commercial packaged boilers to represent the 
combustion efficiency of large commercial packaged boilers in hot water 
mode.

III. Summary and Request for Comments

    Through this notice, DOE is publishing Cleaver-Brooks' petition for 
waiver pursuant to 10 CFR 431.401(b)(1)(iv). The petition contains no 
confidential information. The petition includes a suggested alternate 
test procedure applicable to measurement of energy efficiency of 
certain models of commercial packaged boilers manufactured by Cleaver-
Brooks.
    DOE solicits comments from interested parties on all aspects of the 
petition, including the suggested alternate test procedure. Pursuant to 
10 CFR 431.401(d), any person submitting written comments to DOE must 
also send a copy of such comments to the petitioner. The contact 
information for the petitioner is: Peter A. Molvie, P.E., Manager, 
Codes & Standards, Cleaver-Brooks Product Development, 3232 W. 
Lancaster Ave., Milwaukee, WI 53209. All submissions received must 
include the agency name and case number for this proceeding. Submit 
electronic comments in WordPerfect, Microsoft Word, Portable Document 
Format (PDF), or text (American Standard Code for Information 
Interchange (ASCII)) file format and avoid the use of special 
characters or any form of encryption. Wherever possible, include the 
electronic signature of the author. DOE does not accept telefacsimiles 
(faxes).
    According to 10 CFR 1004.11, any person submitting information that 
he or she believes to be confidential and exempt by law from public 
disclosure should submit two copies: One copy of the document including 
all the information believed to be confidential, and one copy of the 
document with the information believed to be confidential deleted. DOE 
will make its own determination about the confidential status of the 
information and treat it according to its determination.

    Issued in Washington, DC, on April 7, 2016.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and 
Renewable Energy.
From: Peter Molvie
Sent: Friday, July 24, 2015 2:44 p.m.
To: AS_Waiver_Request
Subject: RE: Test Procedure Waiver
    In accordance with the provisions of the Code of Federal 
Regulations Part 431, paragraph 431.401, Cleaver-Brooks is hereby 
petitioning for a waiver from the following test procedures specified 
for Commercial Packaged Boilers:
    1. Paragraph 431.86 Uniform test method for the measurement of 
energy efficiency of commercial packaged boilers. This section requires 
the boilers be tested using the provisions of HI BTS-2000. We propose 
to use the newly published AHRI 1500, 2015 Standard for Performance 
Rating of Commercial Space Heating Boilers. There are several issues 
that make BTS 2000 incompatible with the larger boilers that were 
identified in previous waiver requests. AHRI has worked diligently over 
the past year to revise BTS-2000 in order to address those issues and 
make BTS-

[[Page 22255]]

2000 suitable for use with larger boilers. AHRI Standard 1500 is the 
result of that work. Use of this new standard is required as it is 
compatible with the size boilers we manufacture.
    2. Paragraph 431.86(c)(1)(iv) The requirement to use test 
conditions specified in BTS-2000 specifically the requirements for the 
test pressure for steam boilers, the required water temperatures for 
hot water boilers and instrumentation requirements seem to refer back 
to the middle of the last century rather than the present day, for 
example:
     The 0 to 2 psig test pressure for steam boilers may be 
perfectly adequate for residential and small commercial (cast iron) 
boilers sized boilers, however is not compatible with large boilers as 
it will cause water carryover in large quantities, and an inability to 
meet design water flow rates and firing rates. Typically test pressures 
in range 10 to 12 psig are required.
     Test temperatures defined for hot water boilers are 
guaranteed to cause thermal shock problems in large boilers.
     The instrumentation chart, Table 1, has several problem 
areas, as follows:
    [cir] Steam pressure cannot be measured by mercury manometer as the 
use of mercury in instruments and controls is banned. The correct 
instrument is a Bourdon Tube Gauge 0 to 30 psig
    [cir] Large boilers typically fire into a positive pressure 
combustion chamber, thus gas pressure, firebox pressure and vent/flue 
pressure instruments all need to reflect this.
    [cir] The use of scales to measure water/condensate/moisture flow 
rates is incompatible with the sheer volume of these fluids being used 
or generated by large boilers. Water flow meters should be used and in 
the case of moisture content, current practice is to use a throttling 
calorimeter.
    [cir] The measurement of carbon dioxide as a means of calculating 
excess air or oxygen is considered obsolete in the large boiler 
industry. Direct measurement of excess oxygen is the preferred method 
as modern oxygen meters can easily be calibrated against the oxygen in 
the ambient air.
    [cir] Carbon Monoxide levels are no longer measured as a 
percentage. The current preferred unit is ppm.
AHRI 1500 has taken into account these changes.
    3. Paragraph 431.86(c)(2)(iii)(B) Rating. This paragraph specifies 
that for boilers capable of supplying either steam or hot water, that 
they are tested on steam only, the hot water efficiency shall be based 
on the testing in the steam mode. We propose to use an adjusted steam 
efficiency for hot water when testing on steam only. The adjustment is 
made to the measured stack temperature to be used in calculating 
efficiency based on the relative difference between the flue gas 
temperature and the bulk fluid temperature when operating on steam v 
hot water using the following relationship:

Tstackhw = (Tstacksteam-Tsat) + 
Tbulkhw
Where:

Tstackhw = Stack temperature to be used to determine the 
efficiency on hot water
Tstacksteam = Measured stack temperature when testing on 
steam
Tsat = Saturation temperature of steam at the test pressure
Tbulkhw = 180 [deg]F

    The dominant heat transfer variable for both steam and hot water 
boilers is the gas side coefficient and there is very little difference 
in the overall heat transfer coefficient between steam and hot water 
boilers. It is possible therefore to determine what a hot water boiler 
stack temperature will be, based on a steam test and the bulk fluid 
temperature difference within the boiler. We believe that using this 
adjusted stack temperature to calculate efficiency is a more accurate 
representation of the actual efficiency when operating as a hot water 
boiler than simply using the steam efficiency value.
    The basic models that this request is applicable to are as follows: 
CBEX-E, CBEX-P, 4WI/4WG, CBLE, CBR, CBL, CB, CFC, CFLC, CFW, CFH, FLX 
and M5.
    Other known Manufacturers of similar products are listed below. 
These manufacturers will be notified by Cleaver-Brooks of this waiver, 
if and when the deviation is granted, in accordance with paragraph 
431.401(c).

AESYS Technologies, LLC
Bryan Steam
Burnham Commercial
Easco
Fulton Boiler Works
Hurst
Johnston Boiler Company
Lattner Boiler Company
Miura
Precision Boilers LLC
Superior Boiler Works
Unilux
Vapor Power International LLC
Victory Energy Operations LLC
Williams & Davis
Peter A. Molvie, P.E.
Manager, Codes & Standards
Cleaver-Brooks Product Development
3232 W. Lancaster Ave.
Milwaukee, WI 53209
414-438-5465

[FR Doc. 2016-08750 Filed 4-14-16; 8:45 am]
 BILLING CODE 6450-01-P



                                                    22252                            Federal Register / Vol. 81, No. 73 / Friday, April 15, 2016 / Notices

                                                    specified for Commercial Packaged                       large boiler industry. Direct                           10. SX–6
                                                    Boilers:                                                measurement of excess oxygen is the                     11. SX–8
                                                       1. Paragraph 431.86 Uniform test                     preferred method as modern oxygen                       Other know manufacturers of similar
                                                    method for the measurement of energy                    meters can easily be calibrated against               products are listed below. These
                                                    efficiency of commercial packaged                       the oxygen in the ambient air.                        manufacturers will be notified by
                                                    boilers. This section requirements that                    Æ Carbon Monoxide levels are no                    Superior Boiler Works, Inc. of this
                                                    boilers be tested using the provisions of               longer measured as a percentage. The                  waiver, if and when the deviation is
                                                    HI BTS–2000. We propose to use the                      current preferred unit is ppm.                        granted, in accordance with paragraph
                                                    newly published AHRI Standard 1500,                     AHRI 1500 has taken into account these                431.401(c).
                                                    2015 Standard for Performance Rating of                 changes.                                              AESYS Technologies, LLC
                                                    Commercial Space Heating Boilers.                          3. Paragraph 431.86(c)(2)(iii)(B)                  Bryan Steam
                                                    There are several issues that make BTS                  Rating. This paragraph specifies that for             Burnham Commercial
                                                    2000 incompatible with larger boilers                   boilers capable of supplying either                   Cleaver-Brooks
                                                    that were previously identified and                     steam or hot water, that are tested on                Easco
                                                    discussed. AHRI has worked diligently                   steam only, the hot water efficiency                  Fulton Boiler Works
                                                    over the last year or so to revise BTS–                 shall be based on the testing in the                  Hurst Boiler
                                                    2000 in order to address those issues                   steam mode. We propose to use an                      Johnston Boiler Company
                                                    and make BTS 2000 suitable for larger                   adjusted steam efficiency for hot water               Lattner Boiler Company
                                                    boilers. AHRI Standard 1500 is the                      when testing on steam only. The                       Miura
                                                    result of that work. Use of this new                    adjustment is made to the measured                    Precision Boilers, LLC
                                                    standard is desirable as it is compatible               stack temperature to be used in                       Unilux
                                                    with the various size boilers we                        calculating efficiency based on the                   Vapor Power International, LLC
                                                    manufacture.                                            relative difference between the flue gas              Victory Energy Operations, LLC
                                                       2. Paragraph 431.86(c)(1)(iv) The                                                                          Williams & Davis Boilers
                                                                                                            temperature and the bulk fluid
                                                    requirement to use test conditions
                                                                                                            temperature when operating on steam                     We appreciate your consideration of
                                                    specified in BTS–2000 specifically the
                                                                                                            vs. hot water using the following                     this request. If you have any additional
                                                    requirements for the test pressure for
                                                                                                            relationship:                                         questions please don’t hesitate to
                                                    steam boilers, the required water
                                                                                                            Tstackhw = (Tstacksteam ¥ Tsat) +                     contact me.
                                                    temperatures for hot water boilers and
                                                    instrumentation requirements seem to                          Tbulkhw, where                                  Sincerely,
                                                    refer back to the middle of the last                    Tstackhw = stack temperature to be used               Mokhtar Matallah
                                                    century rather than the present day, for                      to determine the efficiency on hot              Vice President, Engineering
                                                    example:                                                      water.                                          Cc: Mr. Doug Wright, President & CEO,
                                                       • The 0 to 2 psig test pressure for                  Tstacksteam = measured stack                          Superior Boiler Works, Inc.
                                                    steam boilers may be perfectly adequate                       temperature when testing on steam.              [FR Doc. 2016–08738 Filed 4–14–16; 8:45 am]
                                                    for residential and small commercial                    Tbulkhw = 180 °F
                                                                                                                                                                  BILLING CODE P
                                                    (cast iron) boilers sized boilers, however                 The dominant heat transfer variable
                                                    is not compatible with large boilers as                 for both steam and hot water boilers is
                                                    it will cause water carryover in large                  the gas side coefficient and there is very            DEPARTMENT OF ENERGY
                                                    quantities, and an inability to meet                    little difference in the overall heat
                                                    design water flow rates and firing rates.               transfer coefficient between steam and                Office of Energy Efficiency and
                                                    Typically test pressures in range 10 to                 hot water boilers. It is possible therefore           Renewable Energy
                                                    12 psig are required.                                   to determine what a hot water boiler                  [Case No. BLR–007]
                                                       • Test temperatures defined for hot                  stack temperature will be based on a
                                                    water boilers are guaranteed to cause                   steam test based on the difference in the             Notice of Petition for Waiver From
                                                    thermal shock problems in large boilers.                bulk fluid temperature in the boiler. We              Cleaver-Brooks From the Department
                                                       • The instrumentation chart, Table 1,                believe that using this adjusted stack                of Energy Commercial Packaged Boiler
                                                    has several problem areas, as follows:                  temperature to calculate efficiency is a              Test Procedure
                                                       Æ Steam pressure cannot be measured                  more accurate representation of the
                                                    by mercury manometer as the use of                      actual efficiency when operating as a                 AGENCY:  Office of Energy Efficiency and
                                                    mercury in instruments and controls is                  hot water boiler than simply using the                Renewable Energy, Department of
                                                    banned. The correct instrument is a                     steam efficiency value.                               Energy.
                                                    Bourdon Tube Gauge 0 to 30 psig                            The basic models that this request is              ACTION: Notice of petition for waiver and
                                                       Æ Large boilers typically fire into a                applicable to are scotch marine, firetube             request for public comments.
                                                    positive pressure combustion chamber,                   boilers used for commercial packaged
                                                    thus gas pressure, firebox pressure and                 space heating, Section IV ASME                        SUMMARY:    This notice announces receipt
                                                    vent/flue pressure instruments all need                 applications. The specific models                     of a petition for waiver from Cleaver-
                                                    to reflect this.                                        offered by Superior Boiler Works in this              Brooks seeking an exemption from
                                                       Æ The use of scales to measure water/                category for section IV ASME                          specified portions of the U.S.
                                                    condensate/moisture flow rates is                       applications includes the following:                  Department of Energy (DOE) test
                                                    incompatible with the sheer volume of                                                                         procedure applicable to commercial
asabaliauskas on DSK3SPTVN1PROD with NOTICES




                                                                                                               1. Arrowhead
                                                    these fluids being used or generated by                    2. Triad                                           packaged boilers. Cleaver-Brooks
                                                    large boilers. Water flow meters should                    3. Apache                                          contends that some of their commercial
                                                    be used and in the case of moisture                        4. Seminole                                        packaged boilers cannot be accurately
                                                    content, current practice is to use a                      5. Super Seminole                                  tested using the currently applicable
                                                    throttling calorimeter.                                    6. Mohican                                         DOE test procedure and, as a result,
                                                       Æ The measurement of carbon dioxide                     7. Aztec                                           seeks to use an alternate test procedure
                                                    as a means of calculating excess air or                    8. Mohawk                                          to test these basic models. DOE solicits
                                                    oxygen is considered obsolete in the                       9. Osage                                           comments, data, and information


                                               VerDate Sep<11>2014   17:27 Apr 14, 2016   Jkt 238001   PO 00000   Frm 00045   Fmt 4703   Sfmt 4703   E:\FR\FM\15APN1.SGM   15APN1


                                                                                     Federal Register / Vol. 81, No. 73 / Friday, April 15, 2016 / Notices                                         22253

                                                    concerning Cleaver-Brooks’ petition and                 I. Background and Authority                           provide materially inaccurate
                                                    the suggested alternate test procedure.                    Title III, Part C of the Energy Policy             comparative data. 10 CFR 431.401(a)(1).
                                                    DATES: DOE will accept comments, data,                  and Conservation Act of 1975 (EPCA),                  Petitioners must include in their
                                                                                                            as amended (42 U.S.C. 6311 et seq.),                  petition any alternate test procedures
                                                    and information with respect to the
                                                                                                            established the Energy Conservation                   known to the petitioner to evaluate the
                                                    Cleaver-Brooks petition until May 16,
                                                                                                            Program for certain industrial                        basic model in a manner representative
                                                    2016.
                                                                                                            equipment, which includes commercial                  of its energy consumption. 10 CFR
                                                    ADDRESSES:   You may submit comments,                   packaged boilers.1 Part C specifically                431.401(b)(1)(iii).
                                                    identified by case number ‘‘BLR–007,’’                  includes definitions (42 U.S.C. 6311),                   DOE may grant a waiver subject to
                                                    by any of the following methods:                        energy conservation standards (42 U.S.C               conditions, including adherence to
                                                      • Federal eRulemaking Portal: http://                 6313), test procedures (42 U.S.C. 6314),              alternate test procedures. 10 CFR
                                                    www.regulations.gov. Follow the                         labeling provisions (42 U.S.C. 6315),                 431.401(f)(2). As soon as practicable
                                                    instructions for submitting comments.                   and the authority to require information              after the granting of any waiver, DOE
                                                                                                            and reports from manufacturers (42                    will publish in the Federal Register a
                                                      • Email: AS_Waiver_Requests@                                                                                notice of proposed rulemaking to amend
                                                    ee.doe.gov. Include the case number                     U.S.C. 6316). Part C authorizes the
                                                                                                            Secretary of Energy (the Secretary) to                its regulations so as to eliminate any
                                                    [Case No. BLR–007] in the subject line                                                                        need for the continuation of such
                                                    of the message.                                         prescribe test procedures that are
                                                                                                            reasonably designed to produce results                waiver. As soon thereafter as
                                                      • Mail: Ms. Brenda Edwards, U.S.                      that measure energy efficiency, energy                practicable, DOE will publish in the
                                                    Department of Energy, Building                          use, and estimated annual operating                   Federal Register a final rule. 10 CFR
                                                    Technologies Program, Mailstop EE–2B,                   costs, and that are not unduly                        431.401(l).
                                                    1000 Independence Avenue SW.,                           burdensome to conduct. (42 U.S.C.
                                                    Washington, DC 20585–0121.                                                                                    II. Petition for Waiver of Test Procedure
                                                                                                            6314(a)(2)) With respect to commercial
                                                    Telephone: (202) 586–2945. Please                       packaged boilers, Part C requires DOE to                 On July 24, 2015, Cleaver-Brooks
                                                    submit one signed original paper copy.                  use industry test procedures developed                submitted a petition for waiver from the
                                                      • Hand Delivery/Courier: Ms. Brenda                   or recognized by the Air-Conditioning,                DOE test procedure for certain basic
                                                    Edwards, U.S. Department of Energy,                     Heating, and Refrigeration Institute                  models of its commercial packaged
                                                    Building Technologies Program, 950                      (AHRI) or the American Society of                     boilers. The DOE test procedure for
                                                    L’Enfant Plaza SW., Suite 600,                          Heating, Refrigerating, and Air-                      commercial packaged boilers is set forth
                                                    Washington, DC 20024. Please submit                     Conditioning Engineers (ASHRAE), as                   at 10 CFR 431.86 and incorporates by
                                                    one signed original paper copy.                         referenced in ASHRAE/IES 2 Standard                   reference Hydronics Institute (HI) BTS–
                                                                                                            90.1, ‘‘Energy Standard for Buildings                 2000, ‘‘Method to Determine Efficiency
                                                      Docket: For access to the docket to
                                                                                                            Except Low-Rise Residential Buildings.’’              of Commercial Space Heating Boilers’’
                                                    review the background documents
                                                                                                            (42 U.S.C. 6314(a)(4)(A)) Further, if such            (BTS–2000).
                                                    relevant to this matter, you may visit
                                                                                                            an industry test procedure is amended,                   According to Cleaver-Brooks, there
                                                    http://www.regulations.gov. Available
                                                                                                            DOE is required to amend its test                     are several issues that make BTS–2000
                                                    documents include the following items:
                                                                                                            procedure to be consistent with the                   incompatible with larger commercial
                                                    (1) This notice; (2) public comments
                                                                                                            amended industry test procedure,                      packaged boilers, including those
                                                    received; and (3) the petition for waiver.
                                                                                                            unless it determines, by rule published               identified in its petition for waiver.
                                                    FOR FURTHER INFORMATION CONTACT:   Mr.                  in the Federal Register and supported                 Cleaver-Brooks stated that the
                                                    Bryan Berringer, U.S. Department of                     by clear and convincing evidence, that                requirements to use test conditions
                                                    Energy, Building Technologies Program,                  the amended test procedure would be                   specified in BTS–2000 and the
                                                    Mail Stop EE–2B, Forrestal Building,                    unduly burdensome to conduct or                       instrumentation requirements are
                                                    1000 Independence Avenue SW.,                           would not produce test results that                   outdated. Specifically, Cleaver-Brooks
                                                    Washington, DC 20585–0121.                              reflect the energy efficiency, energy use,            indicated the following regarding the
                                                    Telephone: (202) 586–0371. Email:                       and estimated operating costs of that                 test conditions:
                                                    Bryan.Berringer@ee.doe.gov.                             equipment during a representative                        • The 0 to 2 psig test pressure for
                                                      Mr. Peter Cochran, U.S. Department of                 average use cycle. (42 U.S.C.                         steam boilers may be adequate for
                                                    Energy, Office of the General Counsel,                  6314(a)(4)(B)). The test procedure for                residential and small commercial (cast
                                                    Mail Stop GC–33, Forrestal Building,                    commercial packaged boilers is                        iron) boilers sized [commercial
                                                    1000 Independence Avenue SW.,                           contained in 10 CFR part 431, subpart                 packaged] boilers, however such steam
                                                    Washington, DC 20585–0103.                              E.                                                    pressures are not compatible with large
                                                    Telephone: (202) 586–9496. Email:                          DOE’s regulations for covered                      [commercial packaged] boilers as it will
                                                    Peter.Cochran@hq.doe.gov.                               products and equipment permit a                       cause water carryover in large
                                                                                                            person to seek a waiver from the test                 quantities, and an inability to meet
                                                    SUPPLEMENTARY INFORMATION:      In a                                                                          design water flow rates and firing rates;
                                                                                                            procedure requirements for covered
                                                    petition received July 24, 2015, Cleaver-
                                                                                                            commercial equipment if at least one of                  • Typically test steam pressures in
                                                    Brooks requested that the U.S.                                                                                the range of 10 to 12 psig are required;
                                                                                                            the following conditions is met: (1) The
                                                    Department of Energy (‘‘DOE’’) grant a                                                                        and
                                                                                                            petitioner’s basic model contains one or
                                                    waiver to certain models of larger
                                                                                                            more design characteristics that prevent                 • Test temperatures defined for hot
                                                    commercial package boilers that cannot
asabaliauskas on DSK3SPTVN1PROD with NOTICES




                                                                                                            testing according to the prescribed test              water [commercial packaged] boilers
                                                    be tested under the existing DOE test                                                                         cause thermal shock problems in large
                                                                                                            procedures; or (2) the prescribed test
                                                    procedure. The models of commercial                     procedures may evaluate the basic                     [commercial packaged] boilers.
                                                    packaged boilers at issue are models                    model in a manner so unrepresentative                    Cleaver-Brooks also indicated the
                                                    with higher input capacities that                       of its true energy consumption as to                  following regarding the instrumentation
                                                    typically require higher steam pressure                                                                       chart in Table 1 of section 6.0,
                                                    and alternative instrumentation due to                    1 For editorial reasons, upon codification in the   ‘‘Instruments,’’ of BTS–2000:
                                                    the large quantities of fluids being                    U.S. Code, Part C was re-designated Part A–1.            • Steam pressure cannot be measured
                                                    measured.                                                 2 Illuminating Engineering Society.                 by mercury manometer as the use of


                                               VerDate Sep<11>2014   17:27 Apr 14, 2016   Jkt 238001   PO 00000   Frm 00046   Fmt 4703   Sfmt 4703   E:\FR\FM\15APN1.SGM   15APN1


                                                    22254                            Federal Register / Vol. 81, No. 73 / Friday, April 15, 2016 / Notices

                                                    mercury in instruments and controls is                  mode as opposed to hot water using the                   DOE solicits comments from
                                                    banned; the correct instrument is a                     following relationship:                               interested parties on all aspects of the
                                                    Bourdon Tube Gauge for pressures of 0                   Tstack, hw = (Tstack, steam ¥ Tsat) + Tbulk, hw       petition, including the suggested
                                                    to 30 psig;                                             where Tstack, hw is the stack temperature to be       alternate test procedure. Pursuant to 10
                                                       • Large boilers typically fire into a                   used to determine the combustion                   CFR 431.401(d), any person submitting
                                                    positive pressure combustion chamber,                      efficiency in hot water mode, Tstack, steam        written comments to DOE must also
                                                    thus gas pressure, firebox pressure and                    is the measured stack temperature when             send a copy of such comments to the
                                                    vent/flue pressure instruments all need                    testing on steam, Tsat is the saturation           petitioner. The contact information for
                                                                                                               temperature of steam at the test pressure,
                                                    to reflect this;                                                                                              the petitioner is: Peter A. Molvie, P.E.,
                                                                                                               and Tbulk, hw is the temperature of the
                                                       • The use of scales to measure water/                   outlet water when testing in hot water             Manager, Codes & Standards, Cleaver-
                                                    condensate/moisture flow rates is                          mode and is equal to 180 °F. According             Brooks Product Development, 3232 W.
                                                    incompatible with the volume of these                      to Cleaver-Brooks, using this adjusted             Lancaster Ave., Milwaukee, WI 53209.
                                                    fluids being used or generated by large                    stack temperature to calculate                     All submissions received must include
                                                    [commercial packaged] boilers;                             combustion efficiency is a more accurate           the agency name and case number for
                                                       • Water flow meters should be used                      representation of the actual efficiency            this proceeding. Submit electronic
                                                                                                               when operating as a hot water                      comments in WordPerfect, Microsoft
                                                    and in the case of moisture content,                       commercial packaged boiler than simply
                                                    current practice is to use a throttling                    using combustion efficiency value for              Word, Portable Document Format (PDF),
                                                    calorimeter;                                               steam mode.                                        or text (American Standard Code for
                                                       • The measurement of carbon dioxide                                                                        Information Interchange (ASCII)) file
                                                                                                               The following basic models are                     format and avoid the use of special
                                                    as a means of calculating excess air or
                                                                                                            included in Cleaver-Brooks’ petition:                 characters or any form of encryption.
                                                    oxygen is considered obsolete in the
                                                                                                            CBEX–E, CBEX–P, 4WI/4WG, CBLE,                        Wherever possible, include the
                                                    large [commercial packaged] boiler                      CBR, CBL, CB, CFC, CFLC, CFW, CFH,
                                                    industry; direct measurement of excess                                                                        electronic signature of the author. DOE
                                                                                                            FLX and M5.                                           does not accept telefacsimiles (faxes).
                                                    oxygen is the preferred method as                          DOE notes that it has published a
                                                    modern oxygen meters can easily be                                                                               According to 10 CFR 1004.11, any
                                                                                                            notice of proposed rulemaking (March
                                                    calibrated against the oxygen in the                                                                          person submitting information that he
                                                                                                            2016 CPB TP NOPR) to amend its test
                                                    ambient air;                                                                                                  or she believes to be confidential and
                                                                                                            procedure for commercial packaged
                                                       • Carbon Monoxide levels are no                      boilers prescribed in 10 CFR part 431
                                                                                                                                                                  exempt by law from public disclosure
                                                    longer measured as a percentage; the                    subpart E. 81 FR 14641 (Mar. 17, 2016).               should submit two copies: One copy of
                                                    current preferred unit is parts per                     The proposed amended test procedure                   the document including all the
                                                    million (ppm).                                          addresses, among other changes, the                   information believed to be confidential,
                                                       To address these concerns, Cleaver-                  issues raised in this waiver request by               and one copy of the document with the
                                                    Brooks proposes to use the newly                        incorporating by reference ANSI/AHRI                  information believed to be confidential
                                                    published American National Standards                   Standard 1500–2015 as a replacement                   deleted. DOE will make its own
                                                    Institute (ANSI)/Air-Conditioning,                      for BTS–2000 in the DOE test procedure                determination about the confidential
                                                    Heating, and Refrigeration Institute                    for commercial packaged boilers. In                   status of the information and treat it
                                                    (AHRI) 1500–2015, ‘‘Standard for                        addition to adopting ANSI/AHRI                        according to its determination.
                                                    Performance Rating of Commercial                        Standard 1500–2015 as a replacement                     Issued in Washington, DC, on April 7,
                                                    Space Heating Boilers’’ (ANSI/AHRI                      for BTS–2000, DOE further proposes                    2016.
                                                    Standard 1500–2015) in place of BTS–                    several modifications to its test                     Kathleen B. Hogan,
                                                    2000. AHRI developed ANSI/AHRI                          procedure that are not captured in                    Deputy Assistant Secretary for Energy
                                                    Standard 1500–2015 as a replacement                     ANSI/AHRI Standard 1500–2015 in                       Efficiency, Energy Efficiency and Renewable
                                                    for BTS–2000 in order to make the test                  order to improve repeatability, add                   Energy.
                                                    procedure suitable for use with larger                  clarification, and accommodate testing                From: Peter Molvie
                                                    commercial packaged boilers, as well as                 of some equipment that has experienced                Sent: Friday, July 24, 2015 2:44 p.m.
                                                    improve and clarify the test method.                    difficulty in testing to the existing DOE             To: AS_Waiver_Request
                                                    Cleaver-Brooks claims that use of this                  test procedure. Among these changes,                  Subject: RE: Test Procedure Waiver
                                                    ANSI/AHRI Standard 1500–2015 is                         DOE proposes to adopt the stack                          In accordance with the provisions of
                                                    necessary as it is compatible with the                  temperature adjustment described by                   the Code of Federal Regulations Part
                                                    size of commercial packaged boilers                     Cleaver-Brooks when using the tested                  431, paragraph 431.401, Cleaver-Brooks
                                                    they manufacture.                                       combustion efficiency of large steam                  is hereby petitioning for a waiver from
                                                       Additionally, for the large commercial               commercial packaged boilers to                        the following test procedures specified
                                                    packaged boilers capable of supplying                   represent the combustion efficiency of                for Commercial Packaged Boilers:
                                                    either steam or hot water identified in                 large commercial packaged boilers in                     1. Paragraph 431.86 Uniform test
                                                    this petition, Cleaver-Brooks requests                  hot water mode.                                       method for the measurement of energy
                                                    that, when determining the combustion                                                                         efficiency of commercial packaged
                                                    efficiency in hot water mode based on                   III. Summary and Request for                          boilers. This section requires the boilers
                                                    testing in steam mode only, the                         Comments                                              be tested using the provisions of HI
                                                    combustion efficiency rating be                            Through this notice, DOE is                        BTS–2000. We propose to use the newly
                                                    determined based on an adjusted                         publishing Cleaver-Brooks’ petition for               published AHRI 1500, 2015 Standard
asabaliauskas on DSK3SPTVN1PROD with NOTICES




                                                    combustion efficiency. Cleaver-Brooks                   waiver pursuant to 10 CFR                             for Performance Rating of Commercial
                                                    requests that an adjustment be made to                  431.401(b)(1)(iv). The petition contains              Space Heating Boilers. There are several
                                                    the measured stack temperature to be                    no confidential information. The                      issues that make BTS 2000 incompatible
                                                    used in calculating combustion                          petition includes a suggested alternate               with the larger boilers that were
                                                    efficiency based on the relative                        test procedure applicable to                          identified in previous waiver requests.
                                                    difference between the flue gas                         measurement of energy efficiency of                   AHRI has worked diligently over the
                                                    temperature and the bulk fluid                          certain models of commercial packaged                 past year to revise BTS–2000 in order to
                                                    temperature when operating in steam                     boilers manufactured by Cleaver-Brooks.               address those issues and make BTS–


                                               VerDate Sep<11>2014   17:27 Apr 14, 2016   Jkt 238001   PO 00000   Frm 00047   Fmt 4703   Sfmt 4703   E:\FR\FM\15APN1.SGM   15APN1


                                                                                     Federal Register / Vol. 81, No. 73 / Friday, April 15, 2016 / Notices                                                22255

                                                    2000 suitable for use with larger boilers.              when testing on steam only. The                       414–438–5465
                                                    AHRI Standard 1500 is the result of that                adjustment is made to the measured                    [FR Doc. 2016–08750 Filed 4–14–16; 8:45 am]
                                                    work. Use of this new standard is                       stack temperature to be used in                       BILLING CODE 6450–01–P
                                                    required as it is compatible with the size              calculating efficiency based on the
                                                    boilers we manufacture.                                 relative difference between the flue gas
                                                       2. Paragraph 431.86(c)(1)(iv) The                    temperature and the bulk fluid                        DEPARTMENT OF ENERGY
                                                    requirement to use test conditions                      temperature when operating on steam v
                                                    specified in BTS–2000 specifically the                  hot water using the following                         Office of Energy Efficiency and
                                                    requirements for the test pressure for                  relationship:                                         Renewable Energy
                                                    steam boilers, the required water
                                                                                                            Tstackhw = (Tstacksteam¥Tsat) + Tbulkhw               [Case No. BLR–005]
                                                    temperatures for hot water boilers and
                                                                                                            Where:
                                                    instrumentation requirements seem to                                                                          Notice of Petition for Waiver From
                                                    refer back to the middle of the last                    Tstackhw = Stack temperature to be used
                                                                                                                 to determine the efficiency on hot               York-Shipley Global, Division of
                                                    century rather than the present day, for                                                                      AESYS Technologies, LLC From the
                                                    example:                                                     water
                                                                                                                                                                  Department of Energy Commercial
                                                       • The 0 to 2 psig test pressure for                  Tstacksteam = Measured stack
                                                                                                                                                                  Packaged Boiler Test Procedure
                                                    steam boilers may be perfectly adequate                      temperature when testing on steam
                                                    for residential and small commercial                    Tsat = Saturation temperature of steam at             AGENCY:  Office of Energy Efficiency and
                                                    (cast iron) boilers sized boilers, however                   the test pressure                                Renewable Energy, Department of
                                                    is not compatible with large boilers as                 Tbulkhw = 180 °F                                      Energy.
                                                    it will cause water carryover in large                     The dominant heat transfer variable                ACTION: Notice of petition for waiver and
                                                    quantities, and an inability to meet                    for both steam and hot water boilers is               request for public comments.
                                                    design water flow rates and firing rates.               the gas side coefficient and there is very
                                                    Typically test pressures in range 10 to                 little difference in the overall heat                 SUMMARY:    This notice announces receipt
                                                    12 psig are required.                                   transfer coefficient between steam and                of a petition for waiver from York-
                                                       • Test temperatures defined for hot                  hot water boilers. It is possible therefore           Shipley Global, Division of AESYS
                                                    water boilers are guaranteed to cause                   to determine what a hot water boiler                  Technologies, LLC (York-Shipley)
                                                    thermal shock problems in large boilers.                stack temperature will be, based on a                 seeking an exemption from specified
                                                       • The instrumentation chart, Table 1,                steam test and the bulk fluid                         portions of the U.S. Department of
                                                    has several problem areas, as follows:                  temperature difference within the                     Energy (DOE) test procedure applicable
                                                       Æ Steam pressure cannot be measured                  boiler. We believe that using this                    to commercial packaged boilers. York-
                                                    by mercury manometer as the use of                      adjusted stack temperature to calculate               Shipley contends that some of their
                                                    mercury in instruments and controls is                  efficiency is a more accurate                         commercial packaged boilers cannot be
                                                    banned. The correct instrument is a                     representation of the actual efficiency               accurately tested using the currently
                                                    Bourdon Tube Gauge 0 to 30 psig                         when operating as a hot water boiler                  applicable DOE test procedure and, as a
                                                       Æ Large boilers typically fire into a                                                                      result, seeks to use an alternate test
                                                                                                            than simply using the steam efficiency
                                                    positive pressure combustion chamber,                                                                         procedure to test these basic models.
                                                                                                            value.
                                                    thus gas pressure, firebox pressure and                                                                       DOE solicits comments, data, and
                                                                                                               The basic models that this request is
                                                    vent/flue pressure instruments all need                                                                       information concerning York-Shipley’s
                                                                                                            applicable to are as follows: CBEX–E,
                                                    to reflect this.                                                                                              petition and the suggested alternate test
                                                                                                            CBEX–P, 4WI/4WG, CBLE, CBR, CBL,
                                                       Æ The use of scales to measure water/                                                                      procedure.
                                                                                                            CB, CFC, CFLC, CFW, CFH, FLX and
                                                    condensate/moisture flow rates is                                                                             DATES: DOE will accept comments, data,
                                                                                                            M5.
                                                    incompatible with the sheer volume of                                                                         and information with respect to the
                                                                                                               Other known Manufacturers of similar
                                                    these fluids being used or generated by                                                                       York-Shipley petition until May 16,
                                                                                                            products are listed below. These
                                                    large boilers. Water flow meters should                                                                       2016.
                                                                                                            manufacturers will be notified by
                                                    be used and in the case of moisture
                                                                                                            Cleaver-Brooks of this waiver, if and                 ADDRESSES:   You may submit comments,
                                                    content, current practice is to use a
                                                                                                            when the deviation is granted, in                     identified by case number ‘‘BLR–005,’’
                                                    throttling calorimeter.
                                                       Æ The measurement of carbon dioxide                  accordance with paragraph 431.401(c).                 by any of the following methods:
                                                    as a means of calculating excess air or                 AESYS Technologies, LLC                                 • Federal eRulemaking Portal: http://
                                                    oxygen is considered obsolete in the                    Bryan Steam                                           www.regulations.gov. Follow the
                                                    large boiler industry. Direct                           Burnham Commercial                                    instructions for submitting comments.
                                                    measurement of excess oxygen is the                     Easco                                                   • Email: AS_Waiver_Requests@
                                                    preferred method as modern oxygen                       Fulton Boiler Works                                   ee.doe.gov. Include the case number
                                                    meters can easily be calibrated against                 Hurst                                                 [Case No. BLR–005] in the subject line
                                                    the oxygen in the ambient air.                          Johnston Boiler Company                               of the message.
                                                       Æ Carbon Monoxide levels are no                      Lattner Boiler Company                                  • Mail: Ms. Brenda Edwards, U.S.
                                                    longer measured as a percentage. The                    Miura                                                 Department of Energy, Building
                                                    current preferred unit is ppm.                          Precision Boilers LLC                                 Technologies Program, Mailstop EE–2B,
                                                    AHRI 1500 has taken into account these                  Superior Boiler Works                                 1000 Independence Avenue SW.,
                                                    changes.                                                Unilux                                                Washington, DC 20585–0121.
asabaliauskas on DSK3SPTVN1PROD with NOTICES




                                                       3. Paragraph 431.86(c)(2)(iii)(B)                    Vapor Power International LLC                         Telephone: (202) 586–2945. Please
                                                    Rating. This paragraph specifies that for               Victory Energy Operations LLC                         submit one signed original paper copy.
                                                    boilers capable of supplying either                     Williams & Davis                                        • Hand Delivery/Courier: Ms. Brenda
                                                    steam or hot water, that they are tested                Peter A. Molvie, P.E.                                 Edwards, U.S. Department of Energy,
                                                    on steam only, the hot water efficiency                 Manager, Codes & Standards                            Building Technologies Program, 950
                                                    shall be based on the testing in the                    Cleaver-Brooks Product Development                    L’Enfant Plaza SW., Suite 600,
                                                    steam mode. We propose to use an                        3232 W. Lancaster Ave.                                Washington, DC 20024. Please submit
                                                    adjusted steam efficiency for hot water                 Milwaukee, WI 53209                                   one signed original paper copy.


                                               VerDate Sep<11>2014   17:27 Apr 14, 2016   Jkt 238001   PO 00000   Frm 00048   Fmt 4703   Sfmt 4703   E:\FR\FM\15APN1.SGM   15APN1



Document Created: 2016-04-15 00:54:52
Document Modified: 2016-04-15 00:54:52
CategoryRegulatory Information
CollectionFederal Register
sudoc ClassAE 2.7:
GS 4.107:
AE 2.106:
PublisherOffice of the Federal Register, National Archives and Records Administration
SectionNotices
ActionNotice of petition for waiver and request for public comments.
DatesDOE will accept comments, data, and information with respect to the Cleaver-Brooks petition until May 16, 2016.
ContactMr. Bryan Berringer, U.S. Department of Energy, Building Technologies Program, Mail Stop EE-2B, Forrestal Building, 1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202) 586-0371. Email: [email protected]
FR Citation81 FR 22252 