83_FR_56283 83 FR 56065 - Energy Conservation Program: Decision and Order Granting a Waiver to GD Midea Heating & Ventilating Equipment Co., Ltd. From the Department of Energy Central Air Conditioners and Heat Pumps Test Procedure Test Procedure

83 FR 56065 - Energy Conservation Program: Decision and Order Granting a Waiver to GD Midea Heating & Ventilating Equipment Co., Ltd. From the Department of Energy Central Air Conditioners and Heat Pumps Test Procedure Test Procedure

DEPARTMENT OF ENERGY

Federal Register Volume 83, Issue 218 (November 9, 2018)

Page Range56065-56069
FR Document2018-24547

The U.S. Department of Energy (``DOE'') gives notice of a Decision and Order (Case Number 2017-013) that grants to GD Midea Heating & Ventilating Equipment Co., Ltd. (``GD Midea'') a waiver from specified portions of the DOE test procedure for determining the energy efficiency of central air conditioners and heat pumps. Under the Decision and Order, GD Midea is required to test and rate specified basic models of its central air conditioners and heat pumps in accordance with the alternate test procedure specified in the Decision and Order.

Federal Register, Volume 83 Issue 218 (Friday, November 9, 2018)
[Federal Register Volume 83, Number 218 (Friday, November 9, 2018)]
[Notices]
[Pages 56065-56069]
From the Federal Register Online  [www.thefederalregister.org]
[FR Doc No: 2018-24547]


-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

[Case Number 2017-013; EERE-2017-BT-WAV-060]


Energy Conservation Program: Decision and Order Granting a Waiver 
to GD Midea Heating & Ventilating Equipment Co., Ltd. From the 
Department of Energy Central Air Conditioners and Heat Pumps Test 
Procedure Test Procedure

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy.

ACTION: Notice of decision and order.

-----------------------------------------------------------------------

SUMMARY: The U.S. Department of Energy (``DOE'') gives notice of a 
Decision and Order (Case Number 2017-013) that grants to GD Midea 
Heating & Ventilating Equipment Co., Ltd. (``GD Midea'') a waiver from 
specified portions of the DOE test procedure for determining the energy 
efficiency of central air conditioners and heat pumps. Under the 
Decision and Order, GD Midea is required to test and rate specified 
basic models of its central air conditioners and heat pumps in 
accordance with the alternate test procedure specified in the Decision 
and Order.

DATES: The Decision and Order is effective on November 9, 2018. The 
Decision and Order will terminate upon the compliance date of any 
future amendment to the test procedure for central air conditioners and 
heat pumps located at 10 CFR part 430, subpart B, appendix M that 
addresses the issues presented in this waiver. At such time, GD Midea 
must use the relevant test procedure for this product for any testing 
to demonstrate compliance with the applicable standards, and any other 
representations of energy use.

FOR FURTHER INFORMATION CONTACT: Ms. Lucy deButts, U.S. Department of 
Energy, Office of Energy Efficiency and Renewable Energy, Building 
Technologies Office, EE-5B, 1000 Independence Avenue SW, Washington, DC 
20585-0121. E-mail: [email protected].
    Mr. Pete Cochran, U.S. Department of Energy, Office of the General 
Counsel, Mail Stop GC-33, Forrestal Building, 1000 Independence Avenue 
SW, Washington, DC 20585-0103. Telephone: (202) 586-9496. Email: 
[email protected].

SUPPLEMENTARY INFORMATION: In accordance with Title 10 of the Code of 
Federal Regulations (10 CFR 430.27(f)(2)), DOE gives notice of the 
issuance of its Decision and Order as set forth below. The Decision and 
Order grants GD Midea a waiver from the applicable test procedure in 10 
CFR part 430, subpart B, appendix M for specified basic models of 
central air conditioners and heat pumps, provided that GD Midea tests 
and rates such products using the alternate test procedure specified in 
the Decision and Order. GD Midea's representations concerning the 
energy efficiency of the specified basic models must be based on 
testing according to the provisions and restrictions in the alternate 
test procedure set forth in the Decision and Order, and the 
representations must fairly disclose the test results. Distributors, 
retailers, and private labelers are held to the same requirements when 
making representations regarding the energy efficiency of these 
products. (42 U.S.C. 6293(c))
    Consistent with 10 CFR 430.27(j), not later than January 8, 2019, 
any manufacturer currently distributing in commerce in the United 
States products employing a technology or characteristic that results 
in the same need for a waiver from the applicable test procedure must 
submit a petition for waiver. Manufacturers not currently distributing 
such products in commerce in the United States must petition for and be 
granted a waiver prior to the distribution in commerce of those 
products in the United States. Manufacturers may also submit a request 
for interim waiver pursuant to the requirements of 10 CFR 430.27.

    Signed in Washington, DC, on November 1, 2018.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and 
Renewable Energy.

Case #2017-013

Decision and Order

I. Background and Authority

    The Energy Policy and Conservation Act of 1975 (``EPCA''),\1\ 
Public Law 94-163 (42 U.S.C. 6291-6317, as codified), among other 
things, authorizes the U.S. Department of Energy (``DOE'') to regulate 
the energy efficiency of a number of consumer products and industrial 
equipment. Title III, Part B \2\ of EPCA established the Energy 
Conservation Program for Consumer Products Other Than Automobiles, 
which sets forth a variety of provisions designed to improve energy 
efficiency

[[Page 56066]]

for certain types of consumer products. These products include central 
air conditioners (CACs) and heat pumps (HPs), the focus of this 
document. (42 U.S.C. 6292(a)(3)) EPCA also requires the Secretary of 
Energy to prescribe test procedures that are reasonably designed to 
produce results that measure energy efficiency, energy use, or 
estimated operating costs during a representative average-use cycle, 
and that are not unduly burdensome to conduct. (42 U.S.C. 6293(b)(3)) 
The test procedure for CACs and HPs is contained in 10 CFR part 430, 
subpart B, appendix M.
---------------------------------------------------------------------------

    \1\ All references to EPCA in this document refer to the statute 
as amended through the EPS Improvement Act of 2017, Public Law 115-
115 (January 12, 2018).
    \2\ For editorial reasons, upon codification in the U.S. Code, 
Part B was re-designated as Part A.
---------------------------------------------------------------------------

    DOE's regulations set forth at 10 CFR 430.27 contain provisions 
that allow an interested person to seek a waiver from the test 
procedure requirements for a particular basic model when the 
petitioner's basic model for which the petition for waiver was 
submitted contains one or more design characteristics that either (1) 
prevent testing according to the prescribed test procedure, or (2) 
cause the prescribed test procedures to evaluate the basic model in a 
manner so unrepresentative of its true energy consumption 
characteristics as to provide materially inaccurate comparative data. 
10 CFR 430.27(a)(1). A petitioner must include in its petition any 
alternate test procedures known to the petitioner to evaluate the basic 
model in a manner representative of its energy consumption 
characteristics. 10 CFR 430.27(b)(1)(iii).
    DOE may grant a waiver subject to conditions, including adherence 
to alternate test procedures. 10 CFR 430.27(f)(2). As soon as 
practicable after the granting of any waiver, DOE will publish in the 
Federal Register a notice of proposed rulemaking to amend its 
regulations so as to eliminate any need for the continuation of such 
waiver. 10 CFR 430.27(l). As soon thereafter as practicable, DOE will 
publish in the Federal Register a final rule. Id.
    The wavier process also provides that DOE may grant an interim 
waiver if it appears likely that the petition for waiver will be 
granted and/or if DOE determines that it would be desirable for public 
policy reasons to grant immediate relief pending a determination on the 
underlying petition for waiver. 10 CFR 430.27(e)(2). Within one year of 
issuance of an interim waiver, DOE will either: (i) Publish in the 
Federal Register a determination on the petition for waiver; or (ii) 
publish in the Federal Register a new or amended test procedure that 
addresses the issues presented in the waiver. 10 CFR 430.27(h)(1). When 
DOE amends the test procedure to address the issues presented in a 
waiver, the waiver will automatically terminate on the date on which 
use of that test procedure is required to demonstrate compliance. 10 
CFR 430.27(h)(2).

II. GD Midea's Petition for Waiver: Assertions and Determinations

    By letter dated October 27, 2017, GD Midea filed a petition for 
waiver and an application for interim waiver from the applicable CAC 
and HP test procedure set forth in Appendix M.\3\ According to GD 
Midea, Appendix M does not include provisions for determining cooling 
intermediate air volume rate, cooling minimum air volume rate, and 
heating intermediate air volume rate for its variable-speed coil-only 
single-split systems. Consequently, GD Midea stated that it cannot test 
or rate these systems in accordance with the DOE test procedure. GD 
Midea stated that its variable-speed outdoor units are non-
communicative systems (i.e., the outdoor unit does not communicate with 
the indoor unit) for which compressor speed varies based only on 
controls located on the outdoor unit and the indoor unit maintains a 
constant indoor blower fan speed.
---------------------------------------------------------------------------

    \3\ On June 10, 2010, and June 20, 2018, GD Midea supplemented 
the list of basic models listed in its petition to confirm the 
manufacturer and individual model numbers of the paired indoor and 
outdoor units for which it seeks a waiver. The updated list of basic 
models is available at: https://www.regulations.gov/document?D=EERE-2017-BT-WAV-0060-0001.
---------------------------------------------------------------------------

    GD Midea seeks to use an alternate test procedure to test and rate 
specific CAC and HP basic models of its variable-speed coil-only 
single-split systems, which would specify the use of cooling full-load 
air volume rates as determined in section 3.1.4.1.1.c of Appendix M as 
cooling intermediate and cooling minimum air volume rates, and would 
specify the use of heating full-load air volume rates as determined in 
section 3.1.4.4.1.a of Appendix M as heating intermediate air volume 
rate.
    On May 30, 2018, DOE published a notice that announced its receipt 
of the petition for waiver and granted GD Midea an interim waiver. 83 
FR 24767. (``Notice of Petition for Waiver''). In the Notice of 
Petition for Waiver, DOE granted GD Midea's application for an interim 
waiver for specified basic models of CACs and HPs. In the Notice of 
Petition for Waiver, DOE stated that absent an interim waiver, the 
specified variable-speed coil-only single-split models that are subject 
of the waiver cannot be tested under the existing test procedure 
because Appendix M does not include provisions for determining certain 
air volume rates for variable-speed coil-only single-split systems. 83 
FR 24769. Typical variable-speed single-split systems have a 
communicating system, i.e., the condensing units and indoor units 
communicate and indoor unit air flow varies based on the operation of 
the outdoor unit. However, as presented in GD Midea's petition, its 
variable-speed outdoor units are non-communicative systems and the 
indoor blower section maintains a constant indoor blower fan speed.\4\ 
DOE also determined that the alternate test procedure suggested by GD 
Midea allows for the accurate measurement of efficiency of these 
products, while alleviating the testing problems associated with GD 
Midea's implementation of CAC and HP testing for the basic models 
specified in GD Midea's petition. Id.
---------------------------------------------------------------------------

    \4\ DOE reviewed public -facing materials (e.g., marketing 
materials, product specification sheets, and installation manuals) 
for the units identified in the petition, which supported GD Midea's 
assertion that the units are installed as variable-speed coil-only 
systems, in which the indoor fan speed remains constant at full and 
part-load operation.
---------------------------------------------------------------------------

    In the Notice of Petition for Waiver, DOE also solicited comments 
from interested parties on all aspects of the petition and the 
specified alternate test procedure. 83 FR 24770. In response, DOE 
received comments from the Natural Resources Defense Council 
(``NRDC''), Goodman Manufacturing Company, LP (``Goodman''), and 
Advanced Distributor Products, LLC (ADP).\5\
---------------------------------------------------------------------------

    \5\ The comments can be accessed at: https://www.regulations.gov/docket?D=EERE-2017-BT-WAV-0060.
---------------------------------------------------------------------------

    NRDC commented that it understood the issue identified by GD Midea 
with the current test procedure for GD Midea's products, but that it 
was concerned that the alternate test procedure suggested by GD Midea 
would overstate the energy efficiency of variable speed coil-only 
single-split systems. NRDC stated that in the field, it would expect 
these systems to modulate compressor speed to maintain a constant 
capacity regardless of outdoor ambient conditions. However, because the 
fan speed in the specified CACs and HPs is fixed, under test conditions 
the systems may deliver reduced capacity, but at a higher coefficient 
of performance (``COP''). NRDC states that this effect would be more 
pronounced with a slower compressor speed.
    In response to NRDC's comment, DOE notes that the DOE test 
procedure calls for adjusting the measured capacity and the total power 
input to account for the fan input power (see Appendix M, section 
3.3.d) using an adjustment that

[[Page 56067]]

is proportional to air volume rate. In the alternate test procedure, 
this adjustment remains constant because of the constant air volume 
rate. Consequently, the lower the capacity, the more the fan power 
adjustment reduces COP, contrary to NRDC's concern. The fan power 
adjustment is intended to reflect typical fan power of indoor fan 
motors in the field, with which coil-only indoor units would be paired. 
Hence, even if the COP is higher at a lower capacity, that COP would be 
consistent with the pairing of the indoor unit with a typical field air 
moving system. In addition, even though a system may be tested at 
minimum capacity, the seasonal energy efficiency ratio (SEER) and 
heating seasonal performance factor (HSPF) are calculated using the 
energy efficiency ratio (EER) and heating performance factor (HPF) for 
each temperature bin based on capacities matching conditioning loads 
representative for the temperatures (see, e.g., Appendix M section 
4.1.4.2, which provides a method to determine system EER when the 
system delivers capacity between minimum and maximum capacity). Thus, 
the alternate test procedure appropriately measures the energy 
efficiency of the GD Midea products subject to this waiver.
    Goodman stated the alternate test procedure should provide the 
exact same air volume rate for testing of both the cooling mode and 
heating mode, but it was not clear that the alternate test procedure 
accomplished this for heating mode.
    DOE notes that the air volume rates are the same for all tests 
under the alternate test procedure. As instructed in the alternate test 
procedure specified in the interim waiver and this Decision and Order, 
the heating intermediate air volume rate is the same as the heating 
full-load air volume rate determined in section 3.1.4.4.1.a of Appendix 
M. Section 3.1.4.4.1.a requires use of the cooling full-load air volume 
rate for full-load heating. Further, the heating minimum-load air-
volume rate is specified to be equal to the heating full-load air 
volume rate for ducted coil-only systems. Hence, air volume rates are 
the same for all operating conditions under the alternate test 
procedure, as recommended by Goodman.
    ADP agreed that the current test procedure does not allow for 
testing of variable-speed coil-only single-split systems, and that an 
alternate test procedure is needed. ADP suggested that to address other 
potential waiver requests, allowance should be made for different air 
volume rate settings, similar to the allowances in the current DOE test 
procedure for two-stage coil-only systems. ADP also expressed concern 
that GD Midea appeared to publish ratings in the AHRI certification 
database for the specified basic units prior to submission of the 
waiver request, and prior to being granted an interim waiver. ADP also 
noted that this also calls into question any compliance statement made 
to DOE about these products pursuant to 10 CFR 429.12(c). ADP further 
expressed concern regarding the length of time between the submission 
of the petition for waiver and the publication of the Notice of 
Petition for Waiver.
    DOE notes that a Decision and Order applies only to those basic 
models specified in the Order. The petition for waiver for GC Midea did 
not require DOE to consider or evaluate a test procedure that specifies 
different air volume rate settings such as that used in the current 
test procedure for two-stage coil-only systems. Accordingly, DOE is 
treating ADP's comment on this point to apply more generally than to 
the specific waiver request at issue. DOE will consider this issue in 
greater detail if it should decide to amend the CAC and HP test 
procedure in the future, or if it receives an application for a test 
procedure waiver for other basic models in which issues with different 
air volume rates are presented.
    DOE appreciates ADP's remaining comments regarding the timeframe of 
the waiver process and GD Midea's basic models appearing on the AHRI 
Certification Directory, but because they are outside the scope of the 
petition for waiver they will be considered separate from this Decision 
and Order.
    For the reasons explained here and in the Notice of Petition for 
Waiver, DOE understands that absent a waiver, the basic models 
identified by GD Midea in its petition cannot be tested and rated for 
energy consumption on a basis representative of their true energy 
consumption characteristics. DOE has reviewed the recommended procedure 
suggested by GD Midea and concludes that it will allow for the accurate 
measurement of the energy use of the products, while alleviating the 
testing problems associated with GD Midea's implementation of DOE's 
applicable CAC and HP test procedure for the specified basic models. 
Thus, DOE is requiring that GD Midea test and rate the specified CAC 
and HP basic models according to the alternate test procedure specified 
in this Decision and Order, which is identical to the procedure 
provided in the interim waiver.
    This Decision and Order applies only to the basic models listed and 
does not extend to any other basic models. DOE evaluates and grants 
waivers for only those basic models specifically set out in the 
petition, not future models that may be manufactured by the petitioner.
    GD Midea may request that the scope of this waiver be extended to 
include additional basic models that employ the same technology as 
those listed in this waiver. 10 CFR 430.27(g). GD Midea may also submit 
another petition for waiver from the test procedure for additional 
basic models that employ a different technology and meet the criteria 
for test procedure waivers. 10 CFR 430.27(a)(1).
    DOE notes that it may modify or rescind the waiver at any time upon 
DOE's determination that the factual basis underlying the petition for 
waiver is incorrect, or upon a determination that the results from the 
alternate test procedure are unrepresentative of the basic models' true 
energy consumption characteristics. 10 CFR 430.27(k)(1). Likewise, GD 
Midea may request that DOE rescind or modify the waiver if the company 
discovers an error in the information provided to DOE as part of its 
petition, determines that the waiver is no longer needed, or for other 
appropriate reasons. 10 CFR 430.27(k)(2).

III. Consultations With Other Agencies

    In accordance with 10 CFR 430.27(f)(2), DOE consulted with the 
Federal Trade Commission (``FTC'') staff concerning the GD Midea 
petition for waiver. The FTC staff did not have any objections to DOE 
granting a waiver to GD Midea for the specified basic models.

IV. Order

    After careful consideration of all the material that was submitted 
by GD Midea, the various public-facing materials (e.g., marketing 
materials, product specification sheets, and installation manuals) for 
the units identified in the petition, and the comments received in this 
matter, it is ORDERED that:
    (1) GD Midea must, as of the date of publication of this Order in 
the Federal Register, test and rate the GD Midea Heating & Ventilating 
Equipment Co., Ltd brand and Bosch Thermotechnology Corp brand single-
split CAC and HP basic models MOVA-36HDN1-M18M and MOVA-60HDN1-M18M 
(which contain individual combinations that each consist of an outdoor 
unit that uses a variable speed compressor matched with a coil-only 
indoor unit, and is designed to operate as part of a non-communicative 
system in which the compressor speed varies based only on controls 
located in the outdoor unit and the indoor blower unit maintains a

[[Page 56068]]

constant indoor blower fan speed), using the alternate test procedure 
set forth in paragraph (2):
    GD Midea basic models MOVA-36HDN1-M18M and MOVA-60HDN1-M18M include 
the following individual combinations, which do not specify a 
particular air mover, listed by brand name:

----------------------------------------------------------------------------------------------------------------
          Brand name                   Basic model No.                Outdoor unit              Indoor unit
----------------------------------------------------------------------------------------------------------------
GD MIDEA HEATING & VENTILATING  MOVA-36HDN1-M18M............  MOVA-36HDN1-M18M...........  MC**2430ANTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-36HDN1-M18M............  MOVA-36HDN1-M18M...........  MC**2430BNTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-36HDN1-M18M............  MOVA-36HDN1-M18M...........  MC**3036ANTD
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-36HDN1-M18M............  MOVA-36HDN1-M18M...........  MC**3036BNTD
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-36HDN1-M18M............  MOVA-36HDN1-M18M...........  MC**3036CNTD
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-60HDN1-M18M............  MOVA-60HDN1-M18M...........  MC**4248BNTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-60HDN1-M18M............  MOVA-60HDN1-M18M...........  MC**4248CNTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-60HDN1-M18M............  MOVA-60HDN1-M18M...........  MC**4248DNTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-60HDN1-M18M............  MOVA-60HDN1-M18M...........  MC**4860CNTF
 EQUIPMENT CO., LTD.
GD MIDEA HEATING & VENTILATING  MOVA-60HDN1-M18M............  MOVA-60HDN1-M18M...........  MC**4860DNTF
 EQUIPMENT CO., LTD.
BOSCH THERMOTECHNOLOGY CORP...  MOVA-36HDN1-M18M............  BOVA-36HDN1-M18M...........  BMA*2430ANTD
BOSCH THERMOTECHNOLOGY CORP...  MOVA-36HDN1-M18M............  BOVA-36HDN1-M18M...........  BMA*2430BNTD
BOSCH THERMOTECHNOLOGY CORP...  MOVA-36HDN1-M18M............  BOVA-36HDN1-M18M...........  BMA*3036ANTD
BOSCH THERMOTECHNOLOGY CORP...  MOVA-36HDN1-M18M............  BOVA-36HDN1-M18M...........  BMA*3036BNTD
BOSCH THERMOTECHNOLOGY CORP...  MOVA-36HDN1-M18M............  BOVA-36HDN1-M18M...........  BMA*3036CNTD
BOSCH THERMOTECHNOLOGY CORP...  MOVA-60HDN1-M18M............  BOVA-60HDN1-M18M...........  BMA*4248BNTF
BOSCH THERMOTECHNOLOGY CORP...  MOVA-60HDN1-M18M............  BOVA-60HDN1-M18M...........  BMA*4248CNTF
BOSCH THERMOTECHNOLOGY CORP...  MOVA-60HDN1-M18M............  BOVA-60HDN1-M18M...........  BMA*4248DNTF
BOSCH THERMOTECHNOLOGY CORP...  MOVA-60HDN1-M18M............  BOVA-60HDN1-M18M...........  BMA*4860CNTF
BOSCH THERMOTECHNOLOGY CORP...  MOVA-60HDN1-M18M............  BOVA-60HDN1-M18M...........  BMA*4860DNTF
----------------------------------------------------------------------------------------------------------------

    (2) The alternate test procedure for the GD Midea basic models 
identified in paragraph (1) is the test procedure for CACs and HPs 
prescribed by DOE at 10 CFR part 430, subpart B, appendix M, except 
that as described below, for coil-only combinations: The cooling full-
load air volume rate as determined in section 3.1.4.1.1.c of Appendix M 
shall also be used as the cooling intermediate and cooling minimum air 
volume rates, and the heating full-load air volume rate as determined 
in section 3.1.4.4.1.a of Appendix M shall also be used as the heating 
intermediate air volume rate. All other requirements of Appendix M 
remain applicable.
    In 3.1.4.2, Cooling Minimum Air Volume Rate, include:
    f. For ducted variable-speed compressor systems tested with a coil-
only indoor unit, the cooling minimum air volume rate is the same as 
the cooling full-load air volume rate determined in section 
3.1.4.1.1.c.
    In 3.1.4.3, Cooling Intermediate Air Volume Rate, include:
    d. For ducted variable-speed compressor systems tested with a coil-
only indoor unit, the cooling intermediate air volume rate is the same 
as the cooling full-load air volume rate determined in section 
3.1.4.1.1.c.
    In 3.1.4.6, Heating Intermediate Air Volume Rate, include:
    d. For ducted variable-speed compressor systems tested with a coil-
only indoor unit, the heating intermediate air volume rate is the same 
as the heating full-load air volume rate determined in section 
3.1.4.4.1.a.
    (3) Representations. GD Midea may not make representations about 
the efficiency of the basic models identified in paragraph (1) of this 
Order for compliance, marketing, or other purposes unless the basic 
model has been tested in accordance with the provisions set forth above 
and such representations fairly disclose the results of such testing in 
accordance with 10 CFR part 430, subpart B, appendix M, as specified in 
this Order, and 10 CFR part 429, subpart B.
    (4) This waiver shall remain in effect according to the provisions 
of 10 CFR 430.27.
    (5) If GD Midea makes any modifications to the controls or 
configurations of these basic models, the waiver would no longer be 
valid and GD Midea would either be required to use the current Federal 
test method or submit a new application for a test procedure waiver. 
DOE may revoke or modify this waiver at any time if it determines the 
factual basis underlying the petition for waiver is incorrect, or the 
results from the alternate test procedure are unrepresentative of the 
basic models' true energy consumption

[[Page 56069]]

characteristics. 10 CFR 430.27(k)(1). Likewise, GD Midea may request 
that DOE rescind or modify the waiver if GD Midea discovers an error in 
the information provided to DOE as part of its petition, determines 
that the waiver is no longer needed, or for other appropriate reasons. 
10 CFR 430.27(k)(2).
    (6) Granting of this waiver does not release GD Midea from the 
certification requirements set forth at 10 CFR part 429.

    Signed in Washington, DC, on November 1, 2018.

Kathleen B. Hogan,

Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency 
and Renewable Energy.

[FR Doc. 2018-24547 Filed 11-8-18; 8:45 am]
 BILLING CODE 6450-01-P



                                                                            Federal Register / Vol. 83, No. 218 / Friday, November 9, 2018 / Notices                                                     56065

                                                 4) distribute its products in commerce and            DEPARTMENT OF ENERGY                                  grants GD Midea a waiver from the
                                               provide US customers with systems that offer                                                                  applicable test procedure in 10 CFR part
                                               ease of use and installation, as well as                [Case Number 2017–013; EERE–2017–BT–
                                                                                                                                                             430, subpart B, appendix M for
                                                                                                       WAV–060]
                                               significant energy-efficiency savings.                                                                        specified basic models of central air
                                               VII. Arguments for Granting Waiver                      Energy Conservation Program:                          conditioners and heat pumps, provided
                                                                                                       Decision and Order Granting a Waiver                  that GD Midea tests and rates such
                                                 TCL AC believes there are strong                                                                            products using the alternate test
                                               arguments for granting its petition:                    to GD Midea Heating & Ventilating
                                                                                                       Equipment Co., Ltd. From the                          procedure specified in the Decision and
                                                 • From a procedural stand-point, TCL AC                                                                     Order. GD Midea’s representations
                                               has identified a void in the current test               Department of Energy Central Air
                                                                                                       Conditioners and Heat Pumps Test                      concerning the energy efficiency of the
                                               procedure.                                                                                                    specified basic models must be based on
                                                 • DOE has granted GD Midea’s alternative              Procedure Test Procedure
                                                                                                                                                             testing according to the provisions and
                                               test procedure that is technically sound,               AGENCY: Office of Energy Efficiency and               restrictions in the alternate test
                                               proven, easily justifiable, aligned with the            Renewable Energy, Department of                       procedure set forth in the Decision and
                                               spirit and intent of the existing Appendix M            Energy.                                               Order, and the representations must
                                               test procedure.
                                                                                                       ACTION: Notice of decision and order.                 fairly disclose the test results.
                                                 • From a competitive stand-point, the
                                                                                                                                                             Distributors, retailers, and private
                                               current void in the test procedure puts TCL             SUMMARY:   The U.S. Department of                     labelers are held to the same
                                               AC and any other manufacturers whose                    Energy (‘‘DOE’’) gives notice of a                    requirements when making
                                               products may be similar, at a significant               Decision and Order (Case Number                       representations regarding the energy
                                               competitive disadvantage.                               2017–013) that grants to GD Midea                     efficiency of these products. (42 U.S.C.
                                                 • From a public policy stand-point, the               Heating & Ventilating Equipment Co.,                  6293(c))
                                               current void in the test procedure prevents             Ltd. (‘‘GD Midea’’) a waiver from                        Consistent with 10 CFR 430.27(j), not
                                               TCL AC’s distribution in commerce of
                                                                                                       specified portions of the DOE test                    later than January 8, 2019, any
                                               products that offer US costumers with
                                                                                                       procedure for determining the energy                  manufacturer currently distributing in
                                               systems that are easy to install and use, and
                                                                                                       efficiency of central air conditioners and            commerce in the United States products
                                               which provide significant energy-efficiency
                                                                                                       heat pumps. Under the Decision and                    employing a technology or characteristic
                                               savings.
                                                                                                       Order, GD Midea is required to test and               that results in the same need for a
                                               VIII. Conclusion                                        rate specified basic models of its central            waiver from the applicable test
                                                  TCL AC is the second manufacturer to                 air conditioners and heat pumps in                    procedure must submit a petition for
                                               develop the non-communicative variable-                 accordance with the alternate test                    waiver. Manufacturers not currently
                                               speed outdoor condensing unit. As                       procedure specified in the Decision and               distributing such products in commerce
                                               mentioned above, the main issue both GD                 Order.                                                in the United States must petition for
                                               Midea and TCL AC encountered when trying                DATES: The Decision and Order is                      and be granted a waiver prior to the
                                               to rate the variable-speed coil-only single-            effective on November 9, 2018. The                    distribution in commerce of those
                                               split systems to appendix M is the absence              Decision and Order will terminate upon                products in the United States.
                                               of specific provisions for cooling                      the compliance date of any future                     Manufacturers may also submit a
                                               intermediate air volume rate, cooling                   amendment to the test procedure for                   request for interim waiver pursuant to
                                               minimum air volume rate and heating                     central air conditioners and heat pumps               the requirements of 10 CFR 430.27.
                                               intermediate air volume rate.                           located at 10 CFR part 430, subpart B,                  Signed in Washington, DC, on November 1,
                                                  For the reasons stated above, TCL AC                 appendix M that addresses the issues                  2018.
                                               respectfully requests that DOE grants this              presented in this waiver. At such time,               Kathleen B. Hogan,
                                               petition for waiver to test its variable-speed          GD Midea must use the relevant test                   Deputy Assistant Secretary for Energy
                                               coil-only single-split systems using                    procedure for this product for any                    Efficiency, Energy Efficiency and Renewable
                                               Appendix M to Subpart B of 10 CFR part 430              testing to demonstrate compliance with                Energy.
                                               with the supplemental instructions provided             the applicable standards, and any other               Case #2017–013
                                               by GD Midea in section II of this petition.             representations of energy use.
                                                  Should you have any questions or would                                                                     Decision and Order
                                                                                                       FOR FURTHER INFORMATION CONTACT: Ms.
                                               like to discuss this request, please contact me                                                               I. Background and Authority
                                                                                                       Lucy deButts, U.S. Department of
                                               at kt_zhengkai@tcl.com. We greatly
                                                                                                       Energy, Office of Energy Efficiency and                  The Energy Policy and Conservation
                                               appreciate your attention to this matter.
                                                                                                       Renewable Energy, Building                            Act of 1975 (‘‘EPCA’’),1 Public Law 94–
                                               Sincerely,                                              Technologies Office, EE–5B, 1000                      163 (42 U.S.C. 6291–6317, as codified),
                                               Kevin Zheng,                                            Independence Avenue SW, Washington,                   among other things, authorizes the U.S.
                                               Certification Engineer.                                 DC 20585–0121. E-mail: AS_Waiver_                     Department of Energy (‘‘DOE’’) to
                                               kt_zhengkai@tcl.com.
                                                                                                       Requests@ee.doe.gov.                                  regulate the energy efficiency of a
                                                                                                          Mr. Pete Cochran, U.S. Department of               number of consumer products and
                                               [FR Doc. 2018–24548 Filed 11–8–18; 8:45 am]             Energy, Office of the General Counsel,                industrial equipment. Title III, Part B 2
                                               BILLING CODE 6450–01–P                                  Mail Stop GC–33, Forrestal Building,                  of EPCA established the Energy
                                                                                                       1000 Independence Avenue SW,                          Conservation Program for Consumer
                                                                                                       Washington, DC 20585–0103.                            Products Other Than Automobiles,
                                                                                                       Telephone: (202) 586–9496. Email:                     which sets forth a variety of provisions
khammond on DSK30JT082PROD with NOTICES




                                                                                                       peter.cochran@hq.doe.gov.                             designed to improve energy efficiency
                                                                                                       SUPPLEMENTARY INFORMATION: In
                                                                                                       accordance with Title 10 of the Code of                  1 All references to EPCA in this document refer

                                                                                                       Federal Regulations (10 CFR                           to the statute as amended through the EPS
                                                                                                                                                             Improvement Act of 2017, Public Law 115–115
                                                                                                       430.27(f)(2)), DOE gives notice of the                (January 12, 2018).
                                                                                                       issuance of its Decision and Order as set                2 For editorial reasons, upon codification in the

                                                                                                       forth below. The Decision and Order                   U.S. Code, Part B was re-designated as Part A.



                                          VerDate Sep<11>2014   17:36 Nov 08, 2018   Jkt 247001   PO 00000   Frm 00020   Fmt 4703   Sfmt 4703   E:\FR\FM\09NON1.SGM   09NON1


                                               56066                        Federal Register / Vol. 83, No. 218 / Friday, November 9, 2018 / Notices

                                               for certain types of consumer products.                 presented in a waiver, the waiver will                speed coil-only single-split systems. 83
                                               These products include central air                      automatically terminate on the date on                FR 24769. Typical variable-speed single-
                                               conditioners (CACs) and heat pumps                      which use of that test procedure is                   split systems have a communicating
                                               (HPs), the focus of this document. (42                  required to demonstrate compliance. 10                system, i.e., the condensing units and
                                               U.S.C. 6292(a)(3)) EPCA also requires                   CFR 430.27(h)(2).                                     indoor units communicate and indoor
                                               the Secretary of Energy to prescribe test                                                                     unit air flow varies based on the
                                                                                                       II. GD Midea’s Petition for Waiver:
                                               procedures that are reasonably designed                                                                       operation of the outdoor unit. However,
                                               to produce results that measure energy                  Assertions and Determinations
                                                                                                                                                             as presented in GD Midea’s petition, its
                                               efficiency, energy use, or estimated                       By letter dated October 27, 2017, GD               variable-speed outdoor units are non-
                                               operating costs during a representative                 Midea filed a petition for waiver and an              communicative systems and the indoor
                                               average-use cycle, and that are not                     application for interim waiver from the               blower section maintains a constant
                                               unduly burdensome to conduct. (42                       applicable CAC and HP test procedure                  indoor blower fan speed.4 DOE also
                                               U.S.C. 6293(b)(3)) The test procedure for               set forth in Appendix M.3 According to                determined that the alternate test
                                               CACs and HPs is contained in 10 CFR                     GD Midea, Appendix M does not                         procedure suggested by GD Midea
                                               part 430, subpart B, appendix M.                        include provisions for determining                    allows for the accurate measurement of
                                                  DOE’s regulations set forth at 10 CFR                cooling intermediate air volume rate,                 efficiency of these products, while
                                               430.27 contain provisions that allow an                 cooling minimum air volume rate, and                  alleviating the testing problems
                                               interested person to seek a waiver from                 heating intermediate air volume rate for              associated with GD Midea’s
                                               the test procedure requirements for a                   its variable-speed coil-only single-split             implementation of CAC and HP testing
                                               particular basic model when the                         systems. Consequently, GD Midea stated                for the basic models specified in GD
                                               petitioner’s basic model for which the                  that it cannot test or rate these systems             Midea’s petition. Id.
                                               petition for waiver was submitted                       in accordance with the DOE test                          In the Notice of Petition for Waiver,
                                               contains one or more design                             procedure. GD Midea stated that its                   DOE also solicited comments from
                                               characteristics that either (1) prevent                 variable-speed outdoor units are non-                 interested parties on all aspects of the
                                               testing according to the prescribed test                communicative systems (i.e., the                      petition and the specified alternate test
                                               procedure, or (2) cause the prescribed                  outdoor unit does not communicate                     procedure. 83 FR 24770. In response,
                                               test procedures to evaluate the basic                   with the indoor unit) for which                       DOE received comments from the
                                               model in a manner so unrepresentative                   compressor speed varies based only on                 Natural Resources Defense Council
                                               of its true energy consumption                          controls located on the outdoor unit and              (‘‘NRDC’’), Goodman Manufacturing
                                               characteristics as to provide materially                the indoor unit maintains a constant                  Company, LP (‘‘Goodman’’), and
                                               inaccurate comparative data. 10 CFR                     indoor blower fan speed.                              Advanced Distributor Products, LLC
                                               430.27(a)(1). A petitioner must include                    GD Midea seeks to use an alternate                 (ADP).5
                                               in its petition any alternate test                      test procedure to test and rate specific                 NRDC commented that it understood
                                               procedures known to the petitioner to                   CAC and HP basic models of its                        the issue identified by GD Midea with
                                               evaluate the basic model in a manner                    variable-speed coil-only single-split                 the current test procedure for GD
                                               representative of its energy                            systems, which would specify the use of               Midea’s products, but that it was
                                               consumption characteristics. 10 CFR                     cooling full-load air volume rates as                 concerned that the alternate test
                                               430.27(b)(1)(iii).                                      determined in section 3.1.4.1.1.c of                  procedure suggested by GD Midea
                                                  DOE may grant a waiver subject to                    Appendix M as cooling intermediate                    would overstate the energy efficiency of
                                               conditions, including adherence to                      and cooling minimum air volume rates,                 variable speed coil-only single-split
                                               alternate test procedures. 10 CFR                       and would specify the use of heating                  systems. NRDC stated that in the field,
                                               430.27(f)(2). As soon as practicable after              full-load air volume rates as determined
                                               the granting of any waiver, DOE will                                                                          it would expect these systems to
                                                                                                       in section 3.1.4.4.1.a of Appendix M as               modulate compressor speed to maintain
                                               publish in the Federal Register a notice                heating intermediate air volume rate.
                                               of proposed rulemaking to amend its                                                                           a constant capacity regardless of
                                                                                                          On May 30, 2018, DOE published a                   outdoor ambient conditions. However,
                                               regulations so as to eliminate any need                 notice that announced its receipt of the
                                               for the continuation of such waiver. 10                                                                       because the fan speed in the specified
                                                                                                       petition for waiver and granted GD                    CACs and HPs is fixed, under test
                                               CFR 430.27(l). As soon thereafter as                    Midea an interim waiver. 83 FR 24767.
                                               practicable, DOE will publish in the                                                                          conditions the systems may deliver
                                                                                                       (‘‘Notice of Petition for Waiver’’). In the           reduced capacity, but at a higher
                                               Federal Register a final rule. Id.                      Notice of Petition for Waiver, DOE
                                                  The wavier process also provides that                                                                      coefficient of performance (‘‘COP’’).
                                                                                                       granted GD Midea’s application for an                 NRDC states that this effect would be
                                               DOE may grant an interim waiver if it                   interim waiver for specified basic
                                               appears likely that the petition for                                                                          more pronounced with a slower
                                                                                                       models of CACs and HPs. In the Notice                 compressor speed.
                                               waiver will be granted and/or if DOE                    of Petition for Waiver, DOE stated that
                                               determines that it would be desirable for                                                                        In response to NRDC’s comment, DOE
                                                                                                       absent an interim waiver, the specified               notes that the DOE test procedure calls
                                               public policy reasons to grant                          variable-speed coil-only single-split
                                               immediate relief pending a                                                                                    for adjusting the measured capacity and
                                                                                                       models that are subject of the waiver                 the total power input to account for the
                                               determination on the underlying                         cannot be tested under the existing test
                                               petition for waiver. 10 CFR 430.27(e)(2).                                                                     fan input power (see Appendix M,
                                                                                                       procedure because Appendix M does                     section 3.3.d) using an adjustment that
                                               Within one year of issuance of an                       not include provisions for determining
                                               interim waiver, DOE will either: (i)                    certain air volume rates for variable-                  4 DOE reviewed public -facing materials (e.g.,
                                               Publish in the Federal Register a
khammond on DSK30JT082PROD with NOTICES




                                                                                                                                                             marketing materials, product specification sheets,
                                               determination on the petition for                         3 On June 10, 2010, and June 20, 2018, GD Midea     and installation manuals) for the units identified in
                                               waiver; or (ii) publish in the Federal                  supplemented the list of basic models listed in its   the petition, which supported GD Midea’s assertion
                                               Register a new or amended test                          petition to confirm the manufacturer and individual   that the units are installed as variable-speed coil-
                                               procedure that addresses the issues                     model numbers of the paired indoor and outdoor        only systems, in which the indoor fan speed
                                                                                                       units for which it seeks a waiver. The updated list   remains constant at full and part-load operation.
                                               presented in the waiver. 10 CFR                         of basic models is available at: https://               5 The comments can be accessed at: https://
                                               430.27(h)(1). When DOE amends the test                  www.regulations.gov/document?D=EERE-2017-BT-          www.regulations.gov/docket?D=EERE-2017-BT-
                                               procedure to address the issues                         WAV-0060-0001.                                        WAV-0060.



                                          VerDate Sep<11>2014   17:36 Nov 08, 2018   Jkt 247001   PO 00000   Frm 00021   Fmt 4703   Sfmt 4703   E:\FR\FM\09NON1.SGM   09NON1


                                                                            Federal Register / Vol. 83, No. 218 / Friday, November 9, 2018 / Notices                                          56067

                                               is proportional to air volume rate. In the              only systems. ADP also expressed                      those basic models specifically set out
                                               alternate test procedure, this adjustment               concern that GD Midea appeared to                     in the petition, not future models that
                                               remains constant because of the                         publish ratings in the AHRI certification             may be manufactured by the petitioner.
                                               constant air volume rate. Consequently,                 database for the specified basic units                   GD Midea may request that the scope
                                               the lower the capacity, the more the fan                prior to submission of the waiver                     of this waiver be extended to include
                                               power adjustment reduces COP,                           request, and prior to being granted an                additional basic models that employ the
                                               contrary to NRDC’s concern. The fan                     interim waiver. ADP also noted that this              same technology as those listed in this
                                               power adjustment is intended to reflect                 also calls into question any compliance               waiver. 10 CFR 430.27(g). GD Midea
                                               typical fan power of indoor fan motors                  statement made to DOE about these                     may also submit another petition for
                                               in the field, with which coil-only indoor               products pursuant to 10 CFR 429.12(c).                waiver from the test procedure for
                                               units would be paired. Hence, even if                   ADP further expressed concern                         additional basic models that employ a
                                               the COP is higher at a lower capacity,                  regarding the length of time between the              different technology and meet the
                                               that COP would be consistent with the                   submission of the petition for waiver                 criteria for test procedure waivers. 10
                                               pairing of the indoor unit with a typical               and the publication of the Notice of                  CFR 430.27(a)(1).
                                               field air moving system. In addition,                   Petition for Waiver.                                     DOE notes that it may modify or
                                               even though a system may be tested at                      DOE notes that a Decision and Order                rescind the waiver at any time upon
                                               minimum capacity, the seasonal energy                   applies only to those basic models                    DOE’s determination that the factual
                                               efficiency ratio (SEER) and heating                     specified in the Order. The petition for              basis underlying the petition for waiver
                                               seasonal performance factor (HSPF) are                  waiver for GC Midea did not require                   is incorrect, or upon a determination
                                               calculated using the energy efficiency                  DOE to consider or evaluate a test                    that the results from the alternate test
                                               ratio (EER) and heating performance                     procedure that specifies different air                procedure are unrepresentative of the
                                               factor (HPF) for each temperature bin                   volume rate settings such as that used                basic models’ true energy consumption
                                               based on capacities matching                            in the current test procedure for two-                characteristics. 10 CFR 430.27(k)(1).
                                               conditioning loads representative for the               stage coil-only systems. Accordingly,                 Likewise, GD Midea may request that
                                               temperatures (see, e.g., Appendix M                     DOE is treating ADP’s comment on this                 DOE rescind or modify the waiver if the
                                               section 4.1.4.2, which provides a                       point to apply more generally than to                 company discovers an error in the
                                               method to determine system EER when                     the specific waiver request at issue. DOE             information provided to DOE as part of
                                               the system delivers capacity between                    will consider this issue in greater detail            its petition, determines that the waiver
                                               minimum and maximum capacity).                          if it should decide to amend the CAC                  is no longer needed, or for other
                                               Thus, the alternate test procedure                      and HP test procedure in the future, or               appropriate reasons. 10 CFR
                                               appropriately measures the energy                       if it receives an application for a test              430.27(k)(2).
                                               efficiency of the GD Midea products                     procedure waiver for other basic models
                                                                                                                                                             III. Consultations With Other Agencies
                                               subject to this waiver.                                 in which issues with different air
                                                  Goodman stated the alternate test                    volume rates are presented.                              In accordance with 10 CFR
                                               procedure should provide the exact                         DOE appreciates ADP’s remaining                    430.27(f)(2), DOE consulted with the
                                               same air volume rate for testing of both                comments regarding the timeframe of                   Federal Trade Commission (‘‘FTC’’) staff
                                               the cooling mode and heating mode, but                  the waiver process and GD Midea’s                     concerning the GD Midea petition for
                                               it was not clear that the alternate test                basic models appearing on the AHRI                    waiver. The FTC staff did not have any
                                               procedure accomplished this for heating                 Certification Directory, but because they             objections to DOE granting a waiver to
                                               mode.                                                   are outside the scope of the petition for             GD Midea for the specified basic
                                                  DOE notes that the air volume rates                  waiver they will be considered separate               models.
                                               are the same for all tests under the                    from this Decision and Order.
                                                                                                          For the reasons explained here and in              IV. Order
                                               alternate test procedure. As instructed
                                               in the alternate test procedure specified               the Notice of Petition for Waiver, DOE                  After careful consideration of all the
                                               in the interim waiver and this Decision                 understands that absent a waiver, the                 material that was submitted by GD
                                               and Order, the heating intermediate air                 basic models identified by GD Midea in                Midea, the various public-facing
                                               volume rate is the same as the heating                  its petition cannot be tested and rated               materials (e.g., marketing materials,
                                               full-load air volume rate determined in                 for energy consumption on a basis                     product specification sheets, and
                                               section 3.1.4.4.1.a of Appendix M.                      representative of their true energy                   installation manuals) for the units
                                               Section 3.1.4.4.1.a requires use of the                 consumption characteristics. DOE has                  identified in the petition, and the
                                               cooling full-load air volume rate for full-             reviewed the recommended procedure                    comments received in this matter, it is
                                               load heating. Further, the heating                      suggested by GD Midea and concludes                   ORDERED that:
                                               minimum-load air-volume rate is                         that it will allow for the accurate                     (1) GD Midea must, as of the date of
                                               specified to be equal to the heating full-              measurement of the energy use of the                  publication of this Order in the Federal
                                               load air volume rate for ducted coil-only               products, while alleviating the testing               Register, test and rate the GD Midea
                                               systems. Hence, air volume rates are the                problems associated with GD Midea’s                   Heating & Ventilating Equipment Co.,
                                               same for all operating conditions under                 implementation of DOE’s applicable                    Ltd brand and Bosch Thermotechnology
                                               the alternate test procedure, as                        CAC and HP test procedure for the                     Corp brand single-split CAC and HP
                                               recommended by Goodman.                                 specified basic models. Thus, DOE is                  basic models MOVA–36HDN1–M18M
                                                  ADP agreed that the current test                     requiring that GD Midea test and rate                 and MOVA–60HDN1–M18M (which
                                               procedure does not allow for testing of                 the specified CAC and HP basic models                 contain individual combinations that
                                               variable-speed coil-only single-split                                                                         each consist of an outdoor unit that uses
khammond on DSK30JT082PROD with NOTICES




                                                                                                       according to the alternate test procedure
                                               systems, and that an alternate test                     specified in this Decision and Order,                 a variable speed compressor matched
                                               procedure is needed. ADP suggested                      which is identical to the procedure                   with a coil-only indoor unit, and is
                                               that to address other potential waiver                  provided in the interim waiver.                       designed to operate as part of a non-
                                               requests, allowance should be made for                     This Decision and Order applies only               communicative system in which the
                                               different air volume rate settings,                     to the basic models listed and does not               compressor speed varies based only on
                                               similar to the allowances in the current                extend to any other basic models. DOE                 controls located in the outdoor unit and
                                               DOE test procedure for two-stage coil-                  evaluates and grants waivers for only                 the indoor blower unit maintains a


                                          VerDate Sep<11>2014   17:36 Nov 08, 2018   Jkt 247001   PO 00000   Frm 00022   Fmt 4703   Sfmt 4703   E:\FR\FM\09NON1.SGM   09NON1


                                               56068                        Federal Register / Vol. 83, No. 218 / Friday, November 9, 2018 / Notices

                                               constant indoor blower fan speed),                        GD Midea basic models MOVA–                          combinations, which do not specify a
                                               using the alternate test procedure set                  36HDN1–M18M and MOVA–60HDN1–                           particular air mover, listed by brand
                                               forth in paragraph (2):                                 M18M include the following individual                  name:

                                                                                     Brand name                                             Basic model No.             Outdoor unit      Indoor unit

                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–36HDN1–             MOVA–36HDN1–          MC**2430ANTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–36HDN1–             MOVA–36HDN1–          MC**2430BNTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–36HDN1–             MOVA–36HDN1–          MC**3036ANTD
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–36HDN1–             MOVA–36HDN1–          MC**3036BNTD
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–36HDN1–             MOVA–36HDN1–          MC**3036CNTD
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–60HDN1–             MOVA–60HDN1–          MC**4248BNTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–60HDN1–             MOVA–60HDN1–          MC**4248CNTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–60HDN1–             MOVA–60HDN1–          MC**4248DNTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–60HDN1–             MOVA–60HDN1–          MC**4860CNTF
                                                                                                                                          M18M.                    M18M.
                                               GD MIDEA HEATING & VENTILATING EQUIPMENT CO., LTD ...................                     MOVA–60HDN1–             MOVA–60HDN1–          MC**4860DNTF
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–36HDN1–             BOVA–36HDN1–          BMA*2430ANTD
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–36HDN1–             BOVA–36HDN1–          BMA*2430BNTD
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–36HDN1–             BOVA–36HDN1–          BMA*3036ANTD
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–36HDN1–             BOVA–36HDN1–          BMA*3036BNTD
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–36HDN1–             BOVA–36HDN1–          BMA*3036CNTD
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–60HDN1–             BOVA–60HDN1–          BMA*4248BNTF
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–60HDN1–             BOVA–60HDN1–          BMA*4248CNTF
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–60HDN1–             BOVA–60HDN1–          BMA*4248DNTF
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–60HDN1–             BOVA–60HDN1–          BMA*4860CNTF
                                                                                                                                          M18M.                    M18M.
                                               BOSCH THERMOTECHNOLOGY CORP ........................................................      MOVA–60HDN1–             BOVA–60HDN1–          BMA*4860DNTF
                                                                                                                                          M18M.                    M18M.



                                                 (2) The alternate test procedure for the              cooling full-load air volume rate                      been tested in accordance with the
                                               GD Midea basic models identified in                     determined in section 3.1.4.1.1.c.                     provisions set forth above and such
                                               paragraph (1) is the test procedure for                   In 3.1.4.3, Cooling Intermediate Air                 representations fairly disclose the
                                               CACs and HPs prescribed by DOE at 10                    Volume Rate, include:                                  results of such testing in accordance
                                               CFR part 430, subpart B, appendix M,                      d. For ducted variable-speed                         with 10 CFR part 430, subpart B,
                                               except that as described below, for coil-               compressor systems tested with a coil-                 appendix M, as specified in this Order,
                                               only combinations: The cooling full-                    only indoor unit, the cooling                          and 10 CFR part 429, subpart B.
                                               load air volume rate as determined in                   intermediate air volume rate is the same                 (4) This waiver shall remain in effect
                                               section 3.1.4.1.1.c of Appendix M shall                 as the cooling full-load air volume rate               according to the provisions of 10 CFR
                                               also be used as the cooling intermediate                determined in section 3.1.4.1.1.c.                     430.27.
                                               and cooling minimum air volume rates,                     In 3.1.4.6, Heating Intermediate Air                   (5) If GD Midea makes any
                                               and the heating full-load air volume rate               Volume Rate, include:                                  modifications to the controls or
                                               as determined in section 3.1.4.4.1.a of                   d. For ducted variable-speed                         configurations of these basic models, the
                                               Appendix M shall also be used as the                    compressor systems tested with a coil-                 waiver would no longer be valid and GD
                                               heating intermediate air volume rate.                   only indoor unit, the heating                          Midea would either be required to use
                                               All other requirements of Appendix M                    intermediate air volume rate is the same               the current Federal test method or
                                                                                                       as the heating full-load air volume rate               submit a new application for a test
khammond on DSK30JT082PROD with NOTICES




                                               remain applicable.
                                                                                                       determined in section 3.1.4.4.1.a.                     procedure waiver. DOE may revoke or
                                                 In 3.1.4.2, Cooling Minimum Air                         (3) Representations. GD Midea may                    modify this waiver at any time if it
                                               Volume Rate, include:                                   not make representations about the                     determines the factual basis underlying
                                                 f. For ducted variable-speed                          efficiency of the basic models identified              the petition for waiver is incorrect, or
                                               compressor systems tested with a coil-                  in paragraph (1) of this Order for                     the results from the alternate test
                                               only indoor unit, the cooling minimum                   compliance, marketing, or other                        procedure are unrepresentative of the
                                               air volume rate is the same as the                      purposes unless the basic model has                    basic models’ true energy consumption


                                          VerDate Sep<11>2014   17:36 Nov 08, 2018   Jkt 247001   PO 00000   Frm 00023   Fmt 4703   Sfmt 4703   E:\FR\FM\09NON1.SGM   09NON1


                                                                            Federal Register / Vol. 83, No. 218 / Friday, November 9, 2018 / Notices                                          56069

                                               characteristics. 10 CFR 430.27(k)(1).                   Interconnection, LLC, Brady Wind, LLC,                   Comments Due: 5 p.m. ET 11/23/18.
                                               Likewise, GD Midea may request that                     Brady Wind II, LLC, Breckinridge Wind                    Docket Numbers: ER19–278–000.
                                               DOE rescind or modify the waiver if GD                  Project, LLC, Cedar Bluff Wind, LLC,                     Applicants: Midcontinent
                                               Midea discovers an error in the                         Chaves County Solar, LLC, Cimarron                    Independent System Operator, Inc.,
                                               information provided to DOE as part of                  Wind Energy, LLC, Cottonwood Wind                     ALLETE, Inc.
                                               its petition, determines that the waiver                Project, LLC, Day County Wind, LLC,                      Description: § 205(d) Rate Filing:
                                               is no longer needed, or for other                       Elk City Wind, LLC, Ensign Wind, LLC,                 2018–11–02_SA 3203 MP–GRE ICA
                                               appropriate reasons. 10 CFR                             Florida Power & Light Company, FPL                    (Baxter) to be effective 11/3/2018.
                                               430.27(k)(2).                                           Energy Burleigh County Wind, LLC, FPL                    Filed Date: 11/2/18.
                                                  (6) Granting of this waiver does not                 Energy Cowboy Wind, LLC, FPL Energy                      Accession Number: 20181102–5097.
                                               release GD Midea from the certification                 Oklahoma Wind, LLC, FPL Energy                           Comments Due: 5 p.m. ET 11/23/18.
                                               requirements set forth at 10 CFR part                   Sooner Wind, LLC, FPL Energy South                       Docket Numbers: ER19–279–000.
                                               429.                                                    Dakota Wind, LLC, Gray County Wind                       Applicants: Duke Energy Florida,
                                                 Signed in Washington, DC, on November 1,              Energy, LLC, High Majestic Wind                       LLC.
                                               2018.                                                   Energy Center, LLC, High Majestic Wind                   Description: § 205(d) Rate Filing:
                                               Kathleen B. Hogan,                                      II, LLC, Kingman Wind Energy I, LLC,                  DEF–RCID NITSA–NOA Amendment
                                               Deputy Assistant Secretary for Energy                   Kingman Wind Energy II, LLC,                          (SA–147) to be effective 12/1/2018.
                                               Efficiency, Energy Efficiency and Renewable             Mammoth Plains Wind Project, LLC,                        Filed Date: 11/2/18.
                                               Energy.                                                 Minco Wind, LLC, Minco Wind II, LLC,                     Accession Number: 20181102–5110.
                                               [FR Doc. 2018–24547 Filed 11–8–18; 8:45 am]             Minco Wind III, LLC, Minco Wind                          Comments Due: 5 p.m. ET 11/23/18.
                                               BILLING CODE 6450–01–P
                                                                                                       Interconnection Services, LLC, Minco                     Docket Numbers: ER19–280–000.
                                                                                                       Wind V, LLC, Ninnescah Wind Energy,                      Applicants: Midcontinent
                                                                                                       LLC, Osborn Wind Energy, LLC, Palo                    Independent System Operator, Inc.
                                               DEPARTMENT OF ENERGY                                    Duro Wind Energy, LLC, Palo Duro                         Description: § 205(d) Rate Filing:
                                                                                                       Wind Interconnection Services, LLC,                   2018–11–02_Revisions to Attachment
                                               Federal Energy Regulatory                               Roswell Solar, LLC, Rush Springs Wind                 FF–4 to be effective 1/2/2019.
                                               Commission                                              Energy, LLC, Seiling Wind, LLC, Seiling                  Filed Date: 11/2/18.
                                                                                                       Wind II, LLC, Seiling Wind                               Accession Number: 20181102–5126.
                                               Combined Notice of Filings #2                           Interconnection Services, LLC, Sholes                    Comments Due: 5 p.m. ET 11/23/18.
                                                  Take notice that the Commission                      Wind Energy, LLC, Steele Flats Wind                      Docket Numbers: ER19–281–000.
                                               received the following exempt                           Project, LLC, Wessington Wind Energy                     Applicants: PacifiCorp.
                                               wholesale generator filings:                            Center, LLC, Wilton Wind II, LLC,                        Description: § 205(d) Rate Filing: BPA
                                                  Docket Numbers: EG19–16–000.                         NEPM II, LLC, NextEra Energy                          Construct Agmt for Hilltop Happy Camp
                                                  Applicants: TG High Prairie, LLC.                    Marketing, LLC.                                       to be effective 12/24/2018.
                                                  Description: Notice of Self-                            Description: Notification of Non-                     Filed Date: 11/2/18.
                                               Certification of Exempt Wholesale                       Material Change in Status, et al. of                     Accession Number: 20181102–5131.
                                               Generator Status of TG High Prairie,                    NextEra Resources Entities.                              Comments Due: 5 p.m. ET 11/23/18.
                                               LLC.                                                       Filed Date: 11/1/18.                                  Docket Numbers: ER19–283–000.
                                                  Filed Date: 11/2/18.                                    Accession Number: 20181101–5228.                      Applicants: ALLETE, Inc.
                                                  Accession Number: 20181102–5067.                        Comments Due: 5 p.m. ET 11/23/18.                     Description: Initial rate filing:
                                                  Comments Due: 5 p.m. ET 11/23/18.                       Docket Numbers: ER19–256–000.                      Reactive Power to be effective 1/1/2019.
                                                  Take notice that the Commission                         Applicants: Wisconsin Power and                       Filed Date: 11/2/18.
                                               received the following electric rate                    Light Company.                                           Accession Number: 20181102–5166.
                                               filings:                                                   Description: § 205(d) Rate Filing:                    Comments Due: 5 p.m. ET 11/23/18.
                                                  Docket Numbers: ER10–2551–009;                       Wisconsin Power and Light Company                        Docket Numbers: ER19–284–000.
                                               ER10–1846–008; ER10–1849–014;                           Wholesale Formula Rate Changes to be                     Applicants: Florida Power & Light
                                               ER10–1852–020; ER10–1855–008;                           effective 12/31/2018.                                 Company.
                                               ER10–1887–014; ER10–1920–016;                              Filed Date: 11/1/18.                                  Description: § 205(d) Rate Filing: FPL
                                               ER10–1928–016; ER10–1952–014;                              Accession Number: 20181101–5224.                   and FKEC Amendments to Rate
                                               ER10–1961–014; ER10–1994–008;                              Comments Due: 5 p.m. ET 11/23/18.                  Schedule FERC No. 322 to be effective
                                               ER10–1995–009; ER10–2720–016;                              Docket Numbers: ER19–275–000.                      4/1/2018.
                                               ER11–2642–009; ER11–4428–016;                              Applicants: Midcontinent                              Filed Date: 11/2/18.
                                               ER11–4462–029; ER12–1228–016;                           Independent System Operator, Inc.                        Accession Number: 20181102–5170.
                                               ER12–1880–015; ER12–2227–014;                              Description: § 205(d) Rate Filing:                    Comments Due: 5 p.m. ET 11/23/18.
                                               ER12–569–015; ER12–895–014; ER13–                       2018–11–02_Q3 Clean-up Filing to be                      The filings are accessible in the
                                               2474–010; ER13–712–016; ER14–2707–                      effective 1/2/2019.                                   Commission’s eLibrary system by
                                               011; ER14–2708–012; ER14–2709–011;                         Filed Date: 11/2/18.                               clicking on the links or querying the
                                               ER14–2710–011; ER15–1925–008;                              Accession Number: 20181102–5079.                   docket number.
                                               ER15–2676–007; ER15–30–009; ER15–                          Comments Due: 5 p.m. ET 11/23/18.                     Any person desiring to intervene or
                                               58–009; ER16–1440–005; ER16–1672–                          Docket Numbers: ER19–277–000.                      protest in any of the above proceedings
                                                                                                          Applicants: Midcontinent                           must file in accordance with Rules 211
khammond on DSK30JT082PROD with NOTICES




                                               005; ER16–2190–004; ER16–2191–004;
                                               ER16–2240–005; ER16–2241–004;                           Independent System Operator, Inc.,                    and 214 of the Commission’s
                                               ER16–2275–004; ER16–2276–004;                           ALLETE, Inc.                                          Regulations (18 CFR 385.211 and
                                               ER16–2297–004; ER16–2453–005;                              Description: § 205(d) Rate Filing:                 385.214) on or before 5:00 p.m. Eastern
                                               ER17–2152–001; ER17–838–004; ER18–                      2018–11–02_SA 3201 MP–GRE ICA                         time on the specified comment date.
                                               2067–001; ER18–2314–001.                                (Brainerd) to be effective 11/3/2018.                 Protests may be considered, but
                                                  Applicants: Baldwin Wind, LLC,                          Filed Date: 11/2/18.                               intervention is necessary to become a
                                               Blackwell Wind, LLC, Brady                                 Accession Number: 20181102–5084.                   party to the proceeding.


                                          VerDate Sep<11>2014   17:36 Nov 08, 2018   Jkt 247001   PO 00000   Frm 00024   Fmt 4703   Sfmt 4703   E:\FR\FM\09NON1.SGM   09NON1



Document Created: 2018-11-09 03:34:00
Document Modified: 2018-11-09 03:34:00
CategoryRegulatory Information
CollectionFederal Register
sudoc ClassAE 2.7:
GS 4.107:
AE 2.106:
PublisherOffice of the Federal Register, National Archives and Records Administration
SectionNotices
ActionNotice of decision and order.
DatesThe Decision and Order is effective on November 9, 2018. The Decision and Order will terminate upon the compliance date of any future amendment to the test procedure for central air conditioners and heat pumps located at 10 CFR part 430, subpart B, appendix M that
ContactMs. Lucy deButts, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Office, EE-5B, 1000 Independence Avenue SW, Washington, DC 20585-0121. E-mail: [email protected]
FR Citation83 FR 56065 

2025 Federal Register | Disclaimer | Privacy Policy
USC | CFR | eCFR